MO132-25 Manual Motor Starter Magnetic Only 1SAM360000R1014 from ABB offers dedicated short-circuit protection for industrial motor branch circuits.
Manual motor starters provide local disconnect capabilities and immediate fault interruption to protect electrical equipment from high fault currents. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Minimum Order Quantity: 1 piece
- Customs Tariff Number: 85362010
- Data Sheet, Technical Information: 2CDC131035D0202
- Instructions and Manuals: 2CDC131034M6801
- Instructions and Manuals (Part 2): 2CDC131060M0202
- Time-Current Characteristic Curve: 1SAM300515F0008
- I²t Characteristic: 1SAM300507F0001
- Cut-off Current Characteristic: 1SAM300508F0001
- CAD Dimensional Drawing: 2CDC001079B0201
- Dimension Diagram: 1SAM300402F0002
- Product Net Width: 45 mm
- Product Net Height: 97.8 mm
- Product Net Depth / Length: 86.55 mm
- Product Net Weight: 0.31 kg
- Rated Service Short-Circuit Breaking Capacity (I cs ): (230 V AC) 50 kA
- Rated Ultimate Short-Circuit Breaking Capacity (I cu ): (230 V AC) 50 kA
More info
▲| Ordering | |
|---|---|
| Minimum Order Quantity | 1 piece |
| Customs Tariff Number | 85362010 |
| Popular Downloads | |
| Data Sheet, Technical Information | 2CDC131035D0202 |
| Instructions and Manuals | 2CDC131034M6801 |
| Instructions and Manuals (Part 2) | 2CDC131060M0202 |
| Time-Current Characteristic Curve | 1SAM300515F0008 |
| I²t Characteristic | 1SAM300507F0001 |
| 1SAM300507F0003 | |
| Cut-off Current Characteristic | 1SAM300508F0001 |
| 1SAM300508F0003 | |
| CAD Dimensional Drawing | 2CDC001079B0201 |
| Dimension Diagram | 1SAM300402F0002 |
| Dimensions | |
| Product Net Width | 45 mm |
| Product Net Height | 97.8 mm |
| Product Net Depth / Length | 86.55 mm |
| Product Net Weight | 0.31 kg |
| Technical | |
| Rated Service Short-Circuit Breaking Capacity (Ics) | (230 V AC) 50 kA |
| (400 V AC) 50 kA | |
| (440 V AC) 20 kA | |
| (500 V AC) 10 kA | |
| (690 V AC) 3 kA | |
| Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (230 V AC) 50 kA |
| (400 V AC) 50 kA | |
| (440 V AC) 20 kA | |
| (500 V AC) 10 kA | |
| (690 V AC) 3 kA | |
| Rated Instantaneous Short-Circuit Current Setting (Ii) | 313 A |
| Setting Range | None |
| Rated Operational Power AC-3 (Pe) | (400 V) Three Phase 11 kW |
| Rated Operational Power AC-3e (Pe) | (400 V) Three Phase 11 kW |
| Rated Operational Voltage | Main Circuit 690 V AC |
| Rated Operational Current (Ie) | 25 A |
| Rated Operational Current AC-3 (Ie) | 25 A |
| Rated Operational Current AC-3e (Ie) | 25 A |
| Rated Frequency (f) | Main Circuit 50 Hz |
| Main Circuit 60 Hz | |
| Operating Frequency (fsw) | 0 ... 400 Hz |
| Rated Impulse Withstand Voltage (Uimp) | Main Circuit 6 kV |
| Rated Insulation Voltage (Ui) | 690 V |
| Power Loss | at Rated Operating Conditions per Pole 2.2 W |
| Number of Poles | 3P |
| Conventional Free-air Thermal Current (Ith) | Main Circuit 25 A |
| Degree of Protection | Housing IP20 |
| Main Circuit Terminals IP10 | |
| Pollution Degree | 3 |
| Electrical Durability | 50000 cycle |
| Mechanical Durability | Nr. Operations 100000 cycle |
| Terminal Type | Screw Terminals |
| Connecting Capacity Main Circuit | Flexible with Ferrule 1/2x 0.75 ... 6 mm² |
| Flexible with Insulated Ferrule 1/2x 0.75 ... 6 mm² | |
| Flexible 1/2x 1 ... 2.5 mm² | |
| Flexible 1/2x 2.5 ... 6 mm² | |
| Rigid 1/2x 1 ... 2.5 mm² | |
| Rigid 1/2x 2.5 ... 6 mm² | |
| Tightening Torque | Main Circuit 2 N·m |
| Wire Stripping Length | Main Circuit 10 mm |
| Recommended Screw Driver | Pozidriv 2 |
| Mounting Position | 1 ... 6 |
| Mounting on DIN Rail | TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715 |
| TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715 | |
| Minimum Mounting Distance | Electrical Conductive Board, Horizontal - Up to 400 V 0 mm |
| Electrical Conductive Board, Horizontal - Up to 690 V 1.5 mm | |
| Electrical Conductive Board, Vertical 75 mm | |
| Other Device Same Type, Horizontal 0 mm | |
| Other Device Same Type, Vertical 150 mm | |
| Actuator Type | Rotary Handle |
| Contact Position Indication | ON / OFF / TRIP |
| Standards | IEC/EN 60947-1 |
| IEC/EN 60947-2 | |
| IEC/EN 60947-4-1 | |
| UL 60947-1 | |
| UL 60947-4-1 | |
| IEC 60335-2-40 A2L | |
| Remarks | For overload protection of the motors, an appropriate thermal or electronic overload relays must be used |
| Technical UL/CSA | |
| Short-Circuit Current Rating (SCCR) | Any UL Listed Fuses or Circuit-Breakers, Group Installations (480 V AC) 35 kA |
| Any UL Listed Fuses or Circuit-Breakers, Group Installations (600 V AC) 35 kA | |
| Any UL Listed Fuses or Circuit-Breakers, Motor Disconnect (480 V AC) 30 kA | |
| Any UL Listed Fuses or Circuit-Breakers, Motor Disconnect (600 V AC) 18 kA | |
| Any UL Listed Fuses or Circuit-Breakers, Tap Conductor Protection in Group Installations (480Y / 277 V AC) 30 kA | |
| Any UL Listed Fuses or Circuit-Breakers, Tap Conductor Protection in Group Installations (600Y / 347 V AC) 18 kA | |
| Maximum Operating Voltage UL/CSA | Main Circuit 600 V AC |
| Horsepower Rating UL/CSA | (200 V AC) Three Phase 5 Hp |
| (208 V AC) Three Phase 7.5 Hp | |
| (220 ... 240 V AC) Three Phase 7.5 Hp | |
| (440 ... 480 V AC) Three Phase 15 Hp | |
| (550 ... 600 V AC) Three Phase 20 Hp | |
| Full Load Amps Motor Use | (200 V AC) Three Phase 17.5 A |
| (208 V AC) Three Phase 24.2 A | |
| (220 ... 240 V AC) Three Phase 22 A | |
| (440 ... 480 V AC) Three Phase 21 A | |
| (550 ... 600 V AC) Three Phase 22 A | |
| Locked Rotor Amps | (200 V AC) Three Phase 105.8 A |
| (208 V AC) Three Phase 140 A | |
| (220 ... 240 V AC) Three Phase 127 A | |
| (440 ... 480 V AC) Three Phase 116 A | |
| (550 ... 600 V AC) Three Phase 116 A | |
| General Use Rating UL/CSA | (600 V AC) 25 A |
| Connecting Capacity Main Circuit UL/CSA | Flexible 1/2x 16-8 AWG |
| Stranded 1/2x 16-8 AWG | |
| Tightening Torque UL/CSA | Main Circuit 18 in·lb |
| Environmental | |
| Ambient Air Temperature | Around the Enclosure 0 ... +40 °C |
| Operation -25 ... +60 °C | |
| Storage -50 ... +80 °C | |
| Ambient Air Temperature Compensation | No |
| Maximum Operating Altitude Permissible | 2000 m |
| Resistance to Shock acc. to IEC 60068-2-27 | 11 ms Pulse 25g |
| Resistance to Vibrations | 5g 3 ... 150 Hz |
| Material Compliance | |
| Conflict Minerals Reporting Template (CMRT) | 9AKK108467A5658 |
| REACH Declaration | 1SAA963005-4502 |
| RoHS Declaration | 1SAA963006-4501 |
| RoHS Information | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
| Toxic Substances Control Act - TSCA | 2CMT2023-006539 |
| WEEE B2C / B2B | Business To Business |
| WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) |
| ABB EcoSolutions | |
| End Of Life Disassembling Instructions | 1SAC200332H0001 |
| Environmental Product Declaration - EPD | 1SAC200360H0001 |
| Certificates and Declarations | |
| A2L Certificate – IEC | 1SAA963000-4601 |
| ABS Certificate | 1SAA963001-0101 |
| BV Certificate | 1SAA963001-0202 |
| CB Certificate | 1SAA963002-2002 |
| 1SAA963007-2002 | |
| CCC Certificate | 2024010307654702 |
| 2024010307658958 | |
| CQC Certificate | CQC2010010307387700 |
| CQC2019010307243864 | |
| Cut-off Current Characteristic | 1SAM300508F0001 |
| 1SAM300508F0003 | |
| Declaration of Conformity - CCC | 2020980307003526 |
| 2020980307003041 | |
| Declaration of Conformity - CE | 1SAD101100-3403 |
| Declaration of Conformity - UKCA | 1SAD201100-3403 |
| DNV GL Certificate | 1SAA963001-0304 |
| EAC Certificate | 1SAA963000-2701 |
| KC Certificate | 1SAA963002-1502 |
| LR Certificate | 1SAA963001-0502 |
| RINA Certificate | 1SAA963002-0802 |
| RMRS Certificate | 1SAA918000-0704 |
| UL Certificate | E137861-20090225 |
| E345003-20090225 | |
| Container Information | |
| Package Level 1 Units | box 1 piece |
| Package Level 1 Width | 92 mm |
| Package Level 1 Depth / Length | 102 mm |
| Package Level 1 Height | 50 mm |
| Package Level 1 Gross Weight | 0.325 kg |
| Package Level 1 EAN | 4013614400292 |
| Package Level 2 Units | carton 40 piece |
| Package Level 2 Width | 280 mm |
| Package Level 2 Depth / Length | 395 mm |
| Package Level 2 Height | 210 mm |
| Package Level 2 Gross Weight | 13.386 kg |
| Package Level 2 EAN | 4013614443749 |
| External Classifications and Standards | |
| Object Classification Code | F |
| ETIM 9 | EC000074 - Motor protection circuit-breaker |
| ETIM 10 | EC000074 - Motor protection circuit-breaker |
| eClass | V11.0 : 27370401 |
| UNSPSC | 39121521 |
| IDEA Granular Category Code (IGCC) | 4731 >> Manual Starters |
| E-Number (Finland) | 3705892 |
| E-Number (Norway) | 4364098 |
| E-Number (Sweden) | 3110042 |