View larger
2CDS271337R0087 ABB Miniature Circuit Breaker SU200M 1P K 0.2 A
2CDS271337R0087
271337
ABB
1 Pcs.
Automation > Miniature circuit breaker (MCB)
S200U
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Serving as a reliable protective link in electrical distribution boards, the 2CDS271337R0087 ABB Miniature Circuit Breaker SU200M 1P K 0.2 A intercepts dangerous overcurrents and short circuits. Miniature circuit breakers are essential components in commercial and industrial environments for isolating faulty circuits and protecting downstream equipment.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- ABB EcoSolutions: Yes
- Recyclability Rate of the Product acc. to EN45555: Design for Closing Resource Loops - Standard EN45555 - 62 %
- ABB Site Meeting Group Waste To Landfill Target: No non-hazardous waste is sent to a landfill
- Extended Product Lifetime: Product Durability
- End Of Life Disassembling Instructions: 9AKK108471A4773
- Environmental Product Declaration - EPD: 9AKK108470A9950
- Dielectric Test Voltage: 50 / 60 Hz - 1 min 2 kV
- Rated Ultimate Short-Circuit Breaking Capacity (I cu ): (230 V AC) 15 kA
- Rated Service Short-Circuit Breaking Capacity (I cs ): (230 V AC) 11.2 kA
- Power Supply Connection: Arbitrary
- Contact Position Indication: Red ON / Green OFF
- Energy Limiting Class: 3
- Electrical Endurance: 20000 AC cycle
- Mechanical Endurance: 20000 cycle
- Number of Protected Poles: 1
- Number of Poles: 1P
More info
▲| ABB EcoSolutions | |
|---|---|
| ABB EcoSolutions | Yes |
| Recyclability Rate of the Product acc. to EN45555 | Design for Closing Resource Loops - Standard EN45555 - 62 % |
| ABB Site Meeting Group Waste To Landfill Target | No non-hazardous waste is sent to a landfill |
| Extended Product Lifetime | Product Durability |
| End Of Life Disassembling Instructions | 9AKK108471A4773 |
| Environmental Product Declaration - EPD | 9AKK108470A9950 |
| Technical | |
| Dielectric Test Voltage | 50 / 60 Hz - 1 min 2 kV |
| Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (230 V AC) 15 kA |
| (230 V) 15 kA | |
| Rated Service Short-Circuit Breaking Capacity (Ics) | (230 V AC) 11.2 kA |
| Power Supply Connection | Arbitrary |
| Contact Position Indication | Red ON / Green OFF |
| Energy Limiting Class | 3 |
| Electrical Endurance | 20000 AC cycle |
| Mechanical Endurance | 20000 cycle |
| Number of Protected Poles | 1 |
| Number of Poles | 1P |
| Tightening Torque | 2.8 N·m |
| Actuator Type | Toggle |
| Screw Terminal Type | Failsafe Bi-directional Cylinder-lift Terminal |
| Actuator Marking | I / O |
| Actuator Material | Insulation Group II, Black, Sealable |
| Recommended Screw Driver | Pozidriv 2 |
| Accessories Available | Yes |
| Connecting Capacity | Busbar 10/10 mm² |
| Flexible with Ferrule 0.75 ... 25 mm² | |
| Flexible 0.75 ... 25 mm² | |
| Flexible 0.75 ... 25 mm² | |
| Rigid 0.75 ... 35 mm² | |
| Stranded 0.75 ... 35 mm² | |
| Installation Size | acc. to DIN 43880 3 |
| Terminal Type | Double Clamp |
| Electrical | |
| Tripping Characteristic | K |
| Rated Operational Voltage | acc. to IEC 60898-1 277 V AC |
| acc. to IEC 60947-2 230 V AC | |
| Rated Insulation Voltage (Ui) | acc. to IEC/EN 60664-1 440 V |
| Rated Impulse Withstand Voltage (Uimp) | 4 kV |
| at 2000 m 5 kV | |
| at Sea Level 6.2 kV | |
| Input Voltage Type | AC/DC |
| Rated Current (In) | 0.2 A |
| Rated Short-Circuit Capacity | (230 V AC) 11.2 kA |
| Rated Conditional Short-Circuit Current (Inc) | (230 V) 15 kA |
| Rated Frequency (f) | 50 / 60 Hz |
| DC | |
| Power Loss | 1.7 W |
| at Rated Operating Conditions per Pole 1.7 W | |
| Overvoltage Category | III |
| Design | |
| Housing Material | Insulation Group I, RAL 7035 |
| Technical UL/CSA | |
| Maximum Operating Voltage UL/CSA | 277 V AC |
| 48 V DC | |
| Interrupting Rating acc. to UL489 | (240 V AC) 10 kA |
| (277 V AC) 10 kA | |
| (48 V DC) 10 kA | |
| Connecting Capacity UL/CSA | Busbar 18-8 AWG |
| Conductor 18-4 AWG | |
| Material Compliance | |
| RoHS Declaration | 2CDK400595D2705 |
| RoHS Information | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
| RoHS Date | 20200514 |
| REACH Declaration | 9AKK107492A1906 |
| REACH Information | False - does not contain substances > 0.1 mass percentage |
| REACH Date | 20251028 |
| Conflict Minerals Reporting Template (CMRT) | 9AKK108468A3363 |
| SCIP | 89318623-ff2d-4ce0-aefe-5d16fac11138 Germany |
| WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) |
| WEEE B2C / B2B | Business To Business |
| Environmental | |
| Ambient Air Temperature | Operation -25 ... +55 °C |
| Storage -40 ... +70 °C | |
| Reference Ambient Air Temperature | 30 °C |
| Degree of Protection | IP20 |
| IP40 | |
| Enclosure with Cover IP40 | |
| Pollution Degree | 3 |
| Environmental Conditions | 28 cycles |
| with 55 °C / 90-96 % | |
| and 25 °C / 95-100 % | |
| Resistance to Vibrations | 20 Cycles with Load 0.8 In: 5g 5 ... 150 ... 5 Hz |
| Resistance to Shock acc. to IEC 60068-2-27 | 25g 2 shocks 13 ms |
| Environmental Information | 9AKK107680A9140 |
| Dimensions | |
| Width in Number of Modular Spacings | 1.0 |
| Product Net Width | 17.5 mm |
| Product Net Height | 111 mm |
| Product Net Depth / Length | 69 mm |
| Product Net Weight | 0.122 kg |
| Pole Net Weight | 0.125 kg |
| Built-In Depth (t2) | 69 mm |
| Ordering | |
| Package Level 1 Units | carton 1 piece |
| Package Level 1 Gross Weight | 0.162 kg |
| Certificates and Declarations | |
| Declaration of Conformity - CE | 2CDK400595D2705 |
| Declaration of Conformity - UKCA | 9AKK108467A5201 |
| Installation | |
| Instructions and Manuals | 2CDC002177D0202 |
| Mounting on DIN Rail | TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715 |
| TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715 | |
| Mounting Position | any |
| Popular Downloads | |
| Data Sheet, Technical Information | 2CDC002177D0204 |
| External Classifications and Standards | |
| ETIM 9 | EC000042 - Miniature circuit breaker (MCB) |
| ETIM 10 | EC000042 - Miniature circuit breaker (MCB) |
| UNSPSC | 39121603 |
| eClass | V11.0 : 27141901 |
| IDEA Granular Category Code (IGCC) | 4899 >> Miniature circuit breaker (MCB) screw-in model |
| Standards | CSA 22.2 No. 5 |
| IEC/EN 60947-2 | |
| UL 489 | |
| Certification Agency | CSA |
| EN | |
| IEC | |
| UL | |
| Standardization Body | CSA |
| EN | |
| IEC | |
| UL | |