View larger
2CDS251001R0804 ABB Miniature Circuit Breaker S200 80-100A 1P C 80 A
2CDS251001R0804
251001
ABB
1 Pcs.
Automation > Miniature circuit breaker (MCB)
S200 80 y 100A
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Designed for high-current circuit protection, the Abb 2CDS251001R0804 ABB Miniature Circuit Breaker S200 80-100A 1P C 80 A defends single-phase electrical lines against severe overcurrent hazards. Industrial MCBs provide reliable mechanical and electrical isolation to prevent downtime and protect electrical assets.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- ABB EcoSolutions: Yes
- EcoSolutions Profile: 9AKK108471A1000
- Dielectric Test Voltage: 50 / 60 Hz - 1 min 2 kV
- Rated Ultimate Short-Circuit Breaking Capacity (I cu ): (230 V AC) 6 kA
- Rated Service Short-Circuit Breaking Capacity (I cs ): (230 V AC) 6 kA
- Power Supply Connection: Arbitrary
- Contact Position Indication: Red ON / Green OFF
- Energy Limiting Class: 3
- Electrical Endurance: 10000 AC cycle
- Mechanical Endurance: 20000 cycle
- Number of Protected Poles: 1
- Number of Poles: 1P
- Tightening Torque: 3 N·m
- Actuator Type: Toggle
- Screw Terminal Type: Failsafe Bi-directional Cylinder-lift Terminal
- Actuator Marking: I / O
More info
▲| ABB EcoSolutions | |
|---|---|
| ABB EcoSolutions | Yes |
| EcoSolutions Profile | 9AKK108471A1000 |
| Technical | |
| Dielectric Test Voltage | 50 / 60 Hz - 1 min 2 kV |
| Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (230 V AC) 6 kA |
| (400 V AC) 10 kA | |
| (230 V) 6 kA | |
| Rated Service Short-Circuit Breaking Capacity (Ics) | (230 V AC) 6 kA |
| Power Supply Connection | Arbitrary |
| Contact Position Indication | Red ON / Green OFF |
| Energy Limiting Class | 3 |
| Electrical Endurance | 10000 AC cycle |
| Mechanical Endurance | 20000 cycle |
| Number of Protected Poles | 1 |
| Number of Poles | 1P |
| Tightening Torque | 3 N·m |
| Actuator Type | Toggle |
| Screw Terminal Type | Failsafe Bi-directional Cylinder-lift Terminal |
| Actuator Marking | I / O |
| Actuator Material | Insulation Group II, Black, Sealable |
| Recommended Screw Driver | Pozidriv 2 |
| Accessories Available | Yes |
| Connecting Capacity | Busbar 16/16 mm² |
| Conductor 2.5 ... 50 mm² | |
| Flexible 4 ... 35 mm² | |
| Rigid 2.5 ... 50 mm² | |
| Stranded 2.5 ... 50 mm² | |
| Installation Size | acc. to DIN 43880 1 |
| Terminal Type | Screw Terminals |
| Electrical | |
| Tripping Characteristic | C |
| Rated Operational Voltage | acc. to IEC 60898-1 230/400 V AC |
| acc. to IEC 60947-2 230 V AC | |
| Operational Voltage | Maximum (Incl. Tolerance) 253 / 440 V AC |
| Maximum (Incl. Tolerance) 60 V DC | |
| Minimum 12 V AC | |
| Minimum 12 V DC | |
| Rated Insulation Voltage (Ui) | acc. to IEC/EN 60664-1 440 V |
| Rated Impulse Withstand Voltage (Uimp) | 4 kV |
| at 2000 m 5 kV | |
| at Sea Level 6.2 kV | |
| Input Voltage Type | AC |
| Rated Current (In) | 80 A |
| Rated Short-Circuit Capacity | (AC) 6 kA |
| (DC) 6 kA | |
| (230 / 400 V AC) 6 kA | |
| (60 V DC) 6 kA | |
| Rated Conditional Short-Circuit Current (Inc) | (230 V) 10 kA |
| (400 V) 10 kA | |
| Rated Frequency (f) | 50 / 60 Hz |
| Power Loss | 19.6 W |
| at Rated Operating Conditions per Pole 9.8 W | |
| Overvoltage Category | III |
| Design | |
| Housing Material | Insulation Group I, RAL 7035 |
| Material Compliance | |
| RoHS Declaration | 2CDK400601D2703 |
| RoHS Information | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
| RoHS Date | 20200320 |
| REACH Declaration | 9AKK107492A1906 |
| REACH Information | False - does not contain substances > 0.1 mass percentage |
| REACH Date | 20251028 |
| Conflict Minerals Reporting Template (CMRT) | 9AKK108468A3363 |
| WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) |
| WEEE B2C / B2B | Business To Business |
| Environmental | |
| Ambient Air Temperature | Operation -25 ... +55 °C |
| Storage -40 ... +70 °C | |
| Reference Ambient Air Temperature | 30 °C |
| Degree of Protection | IP20 |
| IP40 | |
| Enclosure with Cover IP40 | |
| Pollution Degree | 3 |
| Environmental Conditions | 28 cycles |
| with 55 °C / 90-96 % | |
| and 25 °C / 95-100 % | |
| Resistance to Vibrations | 20 Cycles with Load 0.8 In: 5g 5 ... 150 ... 5 Hz |
| Resistance to Shock acc. to IEC 60068-2-27 | 25g 2 shocks 13 ms |
| Dimensions | |
| Width in Number of Modular Spacings | 1.0 |
| Product Net Width | 17.5 mm |
| Product Net Height | 85 mm |
| Product Net Depth / Length | 69 mm |
| Product Net Weight | 0.12 kg |
| Built-In Depth (t2) | 69 mm |
| Engineering | |
| EPLAN Data | 9AAC185394_EPLAN |
| Ordering | |
| Package Level 1 Units | carton 10 piece |
| Package Level 1 Gross Weight | 1.24 kg |
| E-Number (Finland) | 3210633 |
| E-Number (Norway) | 1682940 |
| Certificates and Declarations | |
| Declaration of Conformity - CE | 2CDK400601D2703 |
| Declaration of Conformity - UKCA | 9AKK108467A5198 |
| Installation | |
| Instructions and Manuals | 2CDS207104P0002 |
| Mounting on DIN Rail | TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715 |
| TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715 | |
| Mounting Position | any |
| Popular Downloads | |
| Data Sheet, Technical Information | 9AKK107680A3031 |
| External Classifications and Standards | |
| ETIM 9 | EC000042 - Miniature circuit breaker (MCB) |
| ETIM 10 | EC000042 - Miniature circuit breaker (MCB) |
| UNSPSC | 39121603 |
| eClass | V11.0 : 27141901 |
| IDEA Granular Category Code (IGCC) | 4897 >> Miniature circuit breakers |
| Object Classification Code | F |
| Standards | IEC/EN 60898-1 |
| IEC/EN 60947-2 | |
| Certification Agency | EN |
| IEC | |
| Standardization Body | EN |
| IEC | |