ABB 2CDS253001R0034 2CDS253001R0034 ABB Miniature Circuit Breaker S200 3P C 3 A View larger
Images are for illustrative purposes only. Please refer to data sheet for details

2CDS253001R0034 ABB Miniature Circuit Breaker S200 3P C 3 A

2CDS253001R0034

253001

ABB

1 Pcs.

Miniature Circuit Breaker - S200 - 3P - C - 3 A Int.aut. S203-C3 3p 3A C 10kA Miniature Circuit Breaker - S200 - 3P - 3 A - C - (AC) 6 kA

Automation > Miniature circuit breaker (MCB)
S200

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.

Request Quote

Product Overview

ABB part 2CDS253001R0034 is a miniature circuit breaker S200 engineered to safeguard electrical distribution circuits against overloads and short-circuit faults. Such components provide reliable automated switching and protect connected assets in industrial plants.

Pricing, availability, and lead time are confirmed per enquiry through an RFQ.

  • ABB EcoSolutions: Yes
  • EcoSolutions Profile: 9AKK108469A3796
  • Recyclability Rate of the Product acc. to EN45555: Design for Closing Resource Loops - Standard EN45555 - 80.7 %
  • ABB Site Meeting Group Waste To Landfill Target: No non-hazardous waste is sent to a landfill
  • Extended Product Lifetime: Product Durability
  • Offered with Takeback Services: Take Back for Recycling
  • End Of Life Disassembling Instructions: 9AKK108468A3132
  • Environmental Product Declaration - EPD: 9AKK108467A7832
  • Dielectric Test Voltage: 50 / 60 Hz - 1 min 2 kV
  • Rated Ultimate Short-Circuit Breaking Capacity (I cu ): (230 V AC) 20 kA
  • Rated Service Short-Circuit Breaking Capacity (I cs ): (230 V AC) 15 kA
  • Power Supply Connection: Arbitrary
  • Contact Position Indication: Red ON / Green OFF
  • Energy Limiting Class: 3
  • Electrical Endurance: 20000 AC cycle
  • Mechanical Endurance: 20000 cycle

More info

▲
ABB EcoSolutions
ABB EcoSolutionsYes
EcoSolutions Profile9AKK108469A3796
Recyclability Rate of the Product acc. to EN45555Design for Closing Resource Loops - Standard EN45555 - 80.7 %
ABB Site Meeting Group Waste To Landfill TargetNo non-hazardous waste is sent to a landfill
Extended Product LifetimeProduct Durability
Offered with Takeback ServicesTake Back for Recycling
End Of Life Disassembling Instructions9AKK108468A3132
Environmental Product Declaration - EPD9AKK108467A7832
Technical
Dielectric Test Voltage50 / 60 Hz - 1 min 2 kV
Rated Ultimate Short-Circuit Breaking Capacity (Icu)(230 V AC) 20 kA
(400 V AC) 10 kA
(440 V AC) 10 kA
(230 V) 20 kA
(400 V) 10 kA
Rated Service Short-Circuit Breaking Capacity (Ics)(230 V AC) 15 kA
(400 V AC) 7.5 kA
(440 V AC) 7.5 kA
Power Supply ConnectionArbitrary
Contact Position IndicationRed ON / Green OFF
Energy Limiting Class3
Electrical Endurance20000 AC cycle
Mechanical Endurance20000 cycle
Number of Protected Poles3
Number of Poles3P
Tightening Torque2.8 N·m
Actuator TypeToggle
Screw Terminal TypeFailsafe Bi-directional Cylinder-lift Terminal
Actuator MarkingI / O
Actuator MaterialInsulation Group II, Black, Sealable
Recommended Screw DriverPozidriv 2
Accessories AvailableYes
Connecting CapacityBusbar 10/10 mm²
Flexible with Ferrule 0.75 ... 25 mm²
Flexible 0.75 ... 25 mm²
Rigid 0.75 ... 35 mm²
Rigid 0.75 ... 35 mm²
Stranded 0.75 ... 35 mm²
Installation Sizeacc. to DIN 43880 1
Wire Stripping Length12.5 mm
Terminal TypeScrew Terminals
Electrical
Tripping CharacteristicC
Rated Operational Voltageacc. to IEC 60898-1 400 V AC
acc. to IEC 60947-2 440 V AC
Operational VoltageMaximum (Incl. Tolerance) 440 V AC
Minimum 12 V AC
Minimum 12 V DC
Rated Insulation Voltage (Ui)acc. to IEC/EN 60664-1 440 V
Rated Impulse Withstand Voltage (Uimp)4 kV
at 2000 m 5 kV
at Sea Level 6.2 kV
Input Voltage TypeAC/DC
Rated Current (In)3 A
Rated Short-Circuit Capacity(AC) 6 kA
(DC) 6 kA
Rated Conditional Short-Circuit Current (Inc)(230 V) 20 kA
(400 V) 20 kA
Frequency (f)50 Hz
Rated Frequency (f)50 / 60 Hz
Power Loss3.9 W
at Rated Operating Conditions per Pole 1.3 W
Overvoltage CategoryIII
I²t Characteristic9AKK107992A5102
Design
Housing MaterialInsulation Group II, RAL 7035
Technical UL/CSA
Maximum Operating Voltage UL/CSA110 V DC
480Y/277 V AC
Interrupting Rating acc. to UL1077(277 V AC) 6 kA
(480Y / 277 V AC) 6 kA
(240 V) 10 kA
Connecting Capacity UL/CSABusbar 18-8 AWG
Conductor 18-4 AWG
Tightening Torque UL/CSA18 in·lb
Material Compliance
RoHS Declaration2CDK403001D0607
RoHS InformationFollowing EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
RoHS Date20240228
REACH Declaration9AKK107492A1906
REACH InformationFalse - does not contain substances > 0.1 mass percentage
REACH Date20251028
Conflict Minerals Reporting Template (CMRT)9AKK108468A3363
SCIPe6800e55-46b1-49a3-881b-0f66d0e903ad Germany
WEEE Category5. Small Equipment (No External Dimension More Than 50 cm)
WEEE B2C / B2BBusiness To Business
Environmental
Ambient Air TemperatureOperation -25 ... +55 °C
Storage -40 ... +70 °C
Reference Ambient Air Temperature30 °C
Degree of ProtectionIP20
IP40
Enclosure with Cover IP40
Pollution Degree3
Environmental Conditions28 cycles
with 55 °C / 90-96 %
and 25 °C / 95-100 %
Resistance to Vibrations20 Cycles with Load 0.8 In: 5g 5 ... 150 ... 5 Hz
Resistance to Shock acc. to IEC 60068-2-2725g 2 shocks 13 ms
Dimensions
Width in Number of Modular Spacings3.0
Product Net Width52.5 mm
Product Net Height88 mm
Product Net Depth / Length69 mm
Product Net Weight0.336 kg
Pole Net Weight0.125 kg
Built-In Depth (t2)69 mm
Dimension Diagram2CDC022007F0010
Engineering
EPLAN Data9AAC204436_EPLAN
Ordering
Package Level 1 Unitscarton 1 piece
Package Level 1 Gross Weight0.356 kg
E-Number (Finland)3211020
E-Number (Sweden)2100585
Certificates and Declarations
Declaration of Conformity - CE2CDK403001D0607
Declaration of Conformity - UKCA9AKK108467A5053
Installation
Instructions and Manuals2CDS207104P0002
Mounting TypeDIN-Rail
Mounting on DIN RailTH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715
TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
Mounting Positionany
Popular Downloads
Data Sheet, Technical Information9AKK107991A8329
I²t Characteristic9AKK107992A5102
External Classifications and Standards
ETIM 9EC000042 - Miniature circuit breaker (MCB)
ETIM 10EC000042 - Miniature circuit breaker (MCB)
UNSPSC39121603
eClassV11.0 : 27141901
IDEA Granular Category Code (IGCC)4897 >> Miniature circuit breakers
Object Classification CodeF
StandardsIEC/EN 60898-1
IEC/EN 60947-2
UL 1077
Certification AgencyEN
IEC
UL
Standardization BodyEN
IEC
UL

Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.