An ABB 2CDS252001R0981 miniature circuit breaker protects delicate electrical circuits by automatically interrupting current flow during overload and short-circuit conditions. Such protective devices are essential for maintaining safety and preventing equipment failure in control panels. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- ABB EcoSolutions: Yes
- EcoSolutions Profile: 9AKK108469A3796
- Recyclability Rate of the Product acc. to EN45555: Design for Closing Resource Loops - Standard EN45555 - 80.7 %
- ABB Site Meeting Group Waste To Landfill Target: No non-hazardous waste is sent to a landfill
- Extended Product Lifetime: Product Durability
- Offered with Takeback Services: Take Back for Recycling
- End Of Life Disassembling Instructions: 9AKK108468A3132
- Environmental Product Declaration - EPD: 9AKK108467A7832
- Dielectric Test Voltage: 50 / 60 Hz - 1 min 2 kV
- Rated Ultimate Short-Circuit Breaking Capacity (I cu ): (125 V DC) 10 kA
- Rated Service Short-Circuit Breaking Capacity (I cs ): (230 V AC) 15 kA
- Power Supply Connection: Arbitrary
- Contact Position Indication: Red ON / Green OFF
- Energy Limiting Class: 3
- Electrical Endurance: 20000 AC cycle
- Mechanical Endurance: 20000 cycle
More info
▲| ABB EcoSolutions | |
|---|---|
| ABB EcoSolutions | Yes |
| EcoSolutions Profile | 9AKK108469A3796 |
| Recyclability Rate of the Product acc. to EN45555 | Design for Closing Resource Loops - Standard EN45555 - 80.7 % |
| ABB Site Meeting Group Waste To Landfill Target | No non-hazardous waste is sent to a landfill |
| Extended Product Lifetime | Product Durability |
| Offered with Takeback Services | Take Back for Recycling |
| End Of Life Disassembling Instructions | 9AKK108468A3132 |
| Environmental Product Declaration - EPD | 9AKK108467A7832 |
| Technical | |
| Dielectric Test Voltage | 50 / 60 Hz - 1 min 2 kV |
| Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (125 V DC) 10 kA |
| (230 V AC) 20 kA | |
| (400 V AC) 10 kA | |
| (440 V AC) 10 kA | |
| (48 V DC) 20 kA | |
| (230 V) 20 kA | |
| (400 V) 10 kA | |
| Rated Service Short-Circuit Breaking Capacity (Ics) | (230 V AC) 15 kA |
| (400 V AC) 7.5 kA | |
| (440 V AC) 7.5 kA | |
| Power Supply Connection | Arbitrary |
| Contact Position Indication | Red ON / Green OFF |
| Energy Limiting Class | 3 |
| Electrical Endurance | 20000 AC cycle |
| Mechanical Endurance | 20000 cycle |
| Number of Protected Poles | 2 |
| Number of Poles | 2P |
| Tightening Torque | 2.8 N·m |
| Screw Terminal Type | Failsafe Bi-directional Cylinder-lift Terminal |
| Actuator Marking | I / O |
| Actuator Material | Insulation Group II, Black, Sealable |
| Recommended Screw Driver | Pozidriv 2 |
| Accessories Available | Yes |
| Connecting Capacity | Busbar 10/10 mm² |
| Flexible with Ferrule 0.75 ... 25 mm² | |
| Flexible 0.75 ... 25 mm² | |
| Rigid 0.75 ... 35 mm² | |
| Rigid 0.75 ... 35 mm² | |
| Stranded 0.75 ... 35 mm² | |
| Installation Size | acc. to DIN 43880 1 |
| Wire Stripping Length | 12.5 mm |
| Terminal Type | Screw Terminals |
| Electrical | |
| Tripping Characteristic | D |
| Rated Operational Voltage | acc. to IEC 60898-1 400 V AC |
| acc. to IEC 60947-2 440 V AC | |
| Operational Voltage | Maximum (Incl. Tolerance) 125 V DC |
| Maximum (Incl. Tolerance) 440 V AC | |
| Minimum 12 V AC | |
| Minimum 12 V DC | |
| Rated Insulation Voltage (Ui) | acc. to IEC/EN 60664-1 440 V |
| Rated Impulse Withstand Voltage (Uimp) | 4 kV |
| at 2000 m 5 kV | |
| at Sea Level 6.2 kV | |
| Input Voltage Type | AC/DC |
| Rated Current (In) | 0.5 A |
| Rated Short-Circuit Capacity | (AC) 6 kA |
| (DC) 6 kA | |
| (400 V AC) 6 kA | |
| Rated Conditional Short-Circuit Current (Inc) | (230 V) 10 kA |
| (400 V) 20 kA | |
| Rated Frequency (f) | 50 / 60 Hz |
| Power Loss | 2.2 W |
| at Rated Operating Conditions per Pole 1.1 W | |
| Overvoltage Category | III |
| I²t Characteristic | 9AKK107992A5103 |
| Design | |
| Housing Material | Insulation Group II, RAL 7035 |
| Technical UL/CSA | |
| Maximum Operating Voltage UL/CSA | 110 V DC |
| 480Y/277 V AC | |
| Interrupting Rating acc. to UL1077 | (277 V AC) 6 kA |
| (480Y / 277 V AC) 6 kA | |
| (240 V) 10 kA | |
| Connecting Capacity UL/CSA | Busbar 18-8 AWG |
| Conductor 18-4 AWG | |
| Tightening Torque UL/CSA | 18 in·lb |
| Material Compliance | |
| RoHS Declaration | 2CDK403001D0607 |
| RoHS Information | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
| RoHS Date | 20240228 |
| REACH Declaration | 9AKK107492A1906 |
| REACH Information | False - does not contain substances > 0.1 mass percentage |
| REACH Date | 20251028 |
| Conflict Minerals Reporting Template (CMRT) | 9AKK108468A3363 |
| SCIP | e6800e55-46b1-49a3-881b-0f66d0e903ad Germany |
| WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) |
| WEEE B2C / B2B | Business To Business |
| Environmental | |
| Ambient Air Temperature | Operation -25 ... +55 °C |
| Storage -40 ... +70 °C | |
| Reference Ambient Air Temperature | 30 °C |
| Degree of Protection | IP20 |
| IP40 | |
| Enclosure with Cover IP40 | |
| Pollution Degree | 3 |
| Environmental Conditions | 28 cycles |
| with 55 °C / 90-96 % | |
| and 25 °C / 95-100 % | |
| Resistance to Vibrations | 20 Cycles with Load 0.8 In: 5g 5 ... 150 ... 5 Hz |
| Resistance to Shock acc. to IEC 60068-2-27 | 25g 2 shocks 13 ms |
| Dimensions | |
| Width in Number of Modular Spacings | 2.0 |
| Product Net Width | 35 mm |
| Product Net Height | 88 mm |
| Product Net Depth / Length | 69 mm |
| Product Net Weight | 0.224 kg |
| Pole Net Weight | 0.125 kg |
| Built-In Depth (t2) | 69 mm |
| Dimension Diagram | 2CDC022007F0010 |
| Engineering | |
| EPLAN Data | 9AAC204436_EPLAN |
| Ordering | |
| Package Level 1 Units | carton 5 piece |
| Package Level 1 Gross Weight | 1.16 kg |
| E-Number (Norway) | 1665133 |
| E-Number (Sweden) | 2100641 |
| Certificates and Declarations | |
| Declaration of Conformity - CE | 2CDK403001D0607 |
| Declaration of Conformity - UKCA | 9AKK108467A5053 |
| Installation | |
| Instructions and Manuals | 2CDS207104P0002 |
| Mounting Type | DIN-Rail |
| Mounting on DIN Rail | TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715 |
| TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715 | |
| Mounting Position | any |
| Popular Downloads | |
| Data Sheet, Technical Information | 9AKK107991A8329 |
| I²t Characteristic | 9AKK107992A5103 |
| External Classifications and Standards | |
| ETIM 9 | EC000042 - Miniature circuit breaker (MCB) |
| ETIM 10 | EC000042 - Miniature circuit breaker (MCB) |
| UNSPSC | 39121603 |
| eClass | V11.0 : 27141901 |
| IDEA Granular Category Code (IGCC) | 4897 >> Miniature circuit breakers |
| Object Classification Code | F |
| Standards | IEC/EN 60898-1 |
| IEC/EN 60947-2 | |
| UL 1077 | |
| Certification Agency | EN |
| IEC | |
| UL | |
| Standardization Body | EN |
| IEC | |
| UL | |