View larger
GJH1213001R0401
1213001
ABB
1 Pcs.
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
| Ordering | |
|---|---|
| Minimum Order Quantity | 1 piece |
| Customs Tariff Number | 85365080 |
| Popular Downloads | |
| EPLAN Data | 9AAC202735_EPLAN |
| Data Sheet, Technical Information | 1SBC100214C0202 |
| Instructions and Manuals | 2CDC102047M6801 |
| CAD Dimensional Drawing | 2CDC001079B0201 |
| Dimensions | |
| Product Net Width | 52.5 mm |
| Product Net Depth / Length | 46.5 mm |
| Product Net Height | 57.5 mm |
| Product Net Weight | 0.175 kg |
| Dimension Diagram | GJL1200436F0001 |
| Technical | |
| Number of Main Contacts NO | 0 |
| Number of Main Contacts NC | 0 |
| Number of Auxiliary Contacts NO | 4 |
| Number of Auxiliary Contacts NC | 0 |
| Number of Poles | 4P |
| Standards | IEC/EN 60947-1 |
| IEC/EN 60947-4-1 | |
| IEC/EN 60947-5-1 | |
| UL 60947-1 | |
| UL 60947-4-1 | |
| IEC 60335-2-40 A2L | |
| Rated Operational Voltage | Auxiliary Circuit 690 V AC |
| Auxiliary Circuit 250 V DC | |
| Rated Frequency (f) | Auxiliary Circuit 50 Hz |
| Auxiliary Circuit 60 Hz | |
| Auxiliary Circuit DC | |
| Control Circuit DC | |
| Main Circuit 60 Hz | |
| Main Circuit 50 Hz | |
| Main Circuit DC | |
| Conventional Free-air Thermal Current (Ith) | Auxiliary Circuit 6 A |
| Rated Operational Current AC-15 (Ie) | (24 V) 4 A |
| (120 V) 4 A | |
| (240 V) 4 A | |
| (400 V) 3 A | |
| (500 V) 2 A | |
| Rated Operational Current DC-13 (Ie) | (24 V) 2.5 A |
| (110 V) 0.7 A | |
| (220 / 240 V) 0.4 A | |
| Short-Circuit Protective Devices | gG Type Fuses 6 A |
| Rated Insulation Voltage (Ui) | 690 V |
| acc. to UL/CSA 600 V | |
| Rated Impulse Withstand Voltage (Uimp) | Auxiliary Circuit 6 kV |
| Maximum Electrical Switching Frequency | (AC-15) 600 cycles per hour |
| (DC-13) 600 cycles per hour | |
| Mechanical Durability | Nr. Operations 10000000 cycle |
| Minimum Switching Capacity | 17 V |
| 5 mA | |
| Coil Operating Limits | (acc. to IEC 60947-5-1) for DC supply 0.85 ... 1.1 x Uc (at θ ≤ 55 °C) |
| Rated Control Circuit Voltage (Uc) | 24 V DC |
| Coil Consumption | Average Holding Value DC 3.5 W |
| Average Pull-in Value DC 3.5 W | |
| Power Loss | at Rated Operating Conditions per Pole 0.32 W |
| Mounting on DIN Rail | TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715 |
| TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715 | |
| Connecting Capacity Auxiliary Circuit | Flexible with Ferrule 1/2x 1 ... 2.5 mm² |
| Flexible with Insulated Ferrule 1/2x 1 ... 2.5 mm² | |
| Flexible 1/2x 1 ... 2.5 mm² | |
| Rigid 1/2x 1 ... 4 mm² | |
| Connecting Capacity Control Circuit | Flexible with Ferrule 1/2x 1 ... 2.5 mm² |
| Flexible with Insulated Ferrule 1/2x 1 ... 2.5 mm² | |
| Flexible 1/2x 1 ... 2.5 mm² | |
| Rigid 1/2x 1 ... 4 mm² | |
| Wire Stripping Length | Auxiliary Circuit 9 mm |
| Degree of Protection | Auxiliary Circuit Terminals IP20 |
| Control Circuit Terminals IP20 | |
| Recommended Screw Driver | M3 |
| Pozidriv 1 | |
| Tightening Torque | Auxiliary Circuit 0.8 ... 1.1 N·m |
| Control Circuit 0.8 ... 1.1 N·m | |
| Main Circuit 0.8 ... 1.1 N·m | |
| Terminal Type | Screw Terminals |
| Mini Contactor Type | Mini Contactor Relay |
| Product Name | Mini Contactor Relay |
| Technical UL/CSA | |
| Maximum Operating Voltage UL/CSA | 600 V AC |
| General Use Rating UL/CSA | (600 V AC) 5 A |
| Connecting Capacity Auxiliary Circuit UL/CSA | Stranded 1/2x 22-10 AWG |
| Contact Rating UL/CSA | A600 |
| Tightening Torque UL/CSA | Auxiliary Circuit 7 in·lb |
| Control Circuit 7 in·lb | |
| Environmental | |
| Ambient Air Temperature | Operation -25 ... +55 °C |
| Storage -40 ... +80 °C | |
| Maximum Operating Altitude Permissible | 2000 m |
| Resistance to Shock acc. to IEC 60068-2-27 | 11 ms Pulse 15g |
| Resistance to Vibrations | 3g 3 ... 150 Hz |
| Material Compliance | |
| Conflict Minerals Reporting Template (CMRT) | 9AKK108467A5658 |
| REACH Declaration | 2CMT2021-006202 |
| RoHS Declaration | 2CMT2021-006277 |
| RoHS Information | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
| Toxic Substances Control Act - TSCA | 2CMT2023-006525 |
| WEEE B2C / B2B | Business To Business |
| WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) |
| ABB EcoSolutions | |
| End Of Life Disassembling Instructions | 1SBC100156C0269 |
| Environmental Product Declaration - EPD | 1SAC200409H0001 |
| Certificates and Declarations | |
| A2L Certificate – IEC | 1SAA938000-4601 |
| CB Certificate | 1SAA938001-2001 |
| CQC Certificate | CQC2003010304064035 |
| Declaration of Conformity - CCC | 2020980304001309 |
| Declaration of Conformity - CE | 1SAD101100-3101 |
| Declaration of Conformity - UKCA | 1SAD201100-3101 |
| EAC Certificate | 1SAA938001-2701 |
| RMRS Certificate | 1SAA938001-0704 |
| UL Certificate | E48139-19881214 |
| Container Information | |
| Package Level 1 Units | box 10 piece |
| Package Level 1 Width | 115 mm |
| Package Level 1 Depth / Length | 280 mm |
| Package Level 1 Height | 54 mm |
| Package Level 1 Gross Weight | 1.82 kg |
| Package Level 1 EAN | 4013614410970 |
| External Classifications and Standards | |
| Object Classification Code | K |
| ETIM 7 | EC000196 - Contactor relay |
| ETIM 8 | EC000196 - Contactor relay |
| ETIM 9 | EC000196 - Contactor relay |
| eClass | V11.0 : 27371001 |
| UNSPSC | 39121529 |
| IDEA Granular Category Code (IGCC) | 4763 >> Power contactor, DC switching |
| E-Number (Finland) | 3709129 |