View larger
2CSF204003R3400 ABB FH204 AC-40/0,3 Residual Current Dev.
2CSF204003R3400
204003
ABB
1 Pcs.
Automation > Residual current circuit breaker (RCCB)
FH200
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
This residual current device detects insulation degradation and earth faults, safely breaking the circuit to prevent electrical hazards in power distribution networks. It provides dependable fault protection for standard commercial and industrial layouts.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- ABB EcoSolutions: Yes
- EcoSolutions Profile: 9AKK108470A4863
- Recyclability Rate of the Product acc. to EN45555: Design for Closing Resource Loops - Standard EN45555 - 72.34 %
- ABB Site Meeting Group Waste To Landfill Target: No non-hazardous waste is sent to a landfill
- Sustainable Material Content in Packaging (wt. %): Recycled Paper - 0 %
- Extended Product Lifetime: Product Durability
- Offered with Takeback Services: Take Back for Recycling
- End Of Life Disassembling Instructions: 9AKK108469A2269
- Environmental Product Declaration - EPD: 9AKK108469A6622
- Type of Residual Current: Type AC
- Rated Service Short-Circuit Breaking Capacity (I cs ): 6 kA
- Maximum Surge Current: 0.25 kA
- Leakage Current Type: AC
- Electrical Endurance: 10000 cycle
- Mechanical Endurance: 20000 cycle
- Number of Poles: 4P
More info
▲| ABB EcoSolutions | |
|---|---|
| ABB EcoSolutions | Yes |
| EcoSolutions Profile | 9AKK108470A4863 |
| Recyclability Rate of the Product acc. to EN45555 | Design for Closing Resource Loops - Standard EN45555 - 72.34 % |
| ABB Site Meeting Group Waste To Landfill Target | No non-hazardous waste is sent to a landfill |
| UL 2799 Zero Waste To Landfill Validation available | |
| Sustainable Material Content in Packaging (wt. %) | Recycled Paper - 0 % |
| Recycled Cardboard - 19.59 % | |
| Recycled Cardboard - 78.37 % | |
| Extended Product Lifetime | Product Durability |
| Offered with Takeback Services | Take Back for Recycling |
| End Of Life Disassembling Instructions | 9AKK108469A2269 |
| Environmental Product Declaration - EPD | 9AKK108469A6622 |
| Technical | |
| Type of Residual Current | Type AC |
| Rated Service Short-Circuit Breaking Capacity (Ics) | 6 kA |
| Maximum Surge Current | 0.25 kA |
| Leakage Current Type | AC |
| Electrical Endurance | 10000 cycle |
| Mechanical Endurance | 20000 cycle |
| Number of Poles | 4P |
| Number of Modular Spacings per DIN Rail | 4 |
| Operating Characteristic | Instantaneous |
| Position of Neutral Terminals | Right |
| Options Provided | None |
| Accessories Available | No |
| Rated Cross-Section | 4 - Multi-Wired 10 ... 25 mm² |
| 1 - Solid-Core 25 ... 25 mm² | |
| Electrical | |
| Short-Circuit Current Rating (SCCR) | 0.3 A |
| Rated Voltage (Ur) | 230/400 V |
| Rated Operational Voltage | acc. to IEC 60898-1 400 V |
| Rated Insulation Voltage (Ui) | acc. to IEC/EN 60664-1 500 V |
| Rated Impulse Withstand Voltage (Uimp) | 4 kV |
| Input Voltage Type | AC |
| Rated Current (In) | 40 A |
| Rated Residual Current | 300 mA |
| Rated Conditional Short-Circuit Current (Inc) | 6 kA |
| Rated Frequency (f) | 50 Hz |
| Power Loss | Total 12.8 W |
| Design | |
| RAL Number | RAL 7035 - Light Grey |
| Color | Grey |
| Number of Modules | 4 |
| Material Compliance | |
| RoHS Declaration | 9AKK106713A5603 |
| RoHS Information | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
| RoHS Date | 20211115 |
| REACH Declaration | 9AKK108467A9482 |
| REACH Information | True - contains substances > 0.1 mass percentage |
| REACH Date | 20240429 |
| Conflict Minerals Reporting Template (CMRT) | 9AKK108468A3363 |
| SCIP | 719d39e9-c62c-4c41-a6dc-53de2a11e8ea Italy |
| WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) |
| WEEE B2C / B2B | Business To Consumer |
| Environmental | |
| Ambient Air Temperature | Operation -5 ... 40 °C |
| Degree of Protection | IP2X |
| Pollution Degree | 2 |
| Environmental Information | Refer to RoHS |
| Dimensions | |
| Width in Number of Modular Spacings | 4 |
| Product Net Width | 70 mm |
| Product Net Height | 85 mm |
| Product Net Depth / Length | 69 mm |
| Product Net Weight | 380 g |
| Built-In Depth (t2) | 69 mm |
| Ordering | |
| Package Level 1 Units | box 1 piece |
| Package Level 1 Gross Weight | 0.415 kg |
| Certificates and Declarations | |
| Declaration of Conformity - CE | 9AKK106713A5603 |
| Installation | |
| Mounting Type | DIN-Rail |
| Popular Downloads | |
| Data Sheet, Technical Information | 2CSC400030D0202 |
| External Classifications and Standards | |
| ETIM 9 | EC000003 - Residual current circuit breaker (RCCB) |
| ETIM 10 | EC000003 - Residual current circuit breaker (RCCB) |
| eClass | V11.0 : 27142201 |
| Object Classification Code | F |
| Standards | IEC/EN 61008 |