View larger
2CSF204592R4400 ABB F204 B-40/0,5 Residual Current Dev.
2CSF204592R4400
204592
ABB
1 Pcs.
Automation > Residual current circuit breaker (RCCB)
Special F200 (B, 400Hz)
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
A residual current device safeguards electrical installations by detecting earth leakage currents and disconnecting the circuit to prevent shock hazards. This Abb 2CSF204592R4400 unit is deployed in commercial and industrial distribution boards to provide reliable fault protection against complex waveforms.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- ABB EcoSolutions: Yes
- EcoSolutions Profile: 9AKK108469A3795
- Recyclability Rate of the Product acc. to EN45555: Design for Closing Resource Loops - Standard EN45555 - 77.05 %
- ABB Site Meeting Group Waste To Landfill Target: No non-hazardous waste is sent to a landfill
- Sustainable Material Content in Packaging (wt. %): Recycled Cardboard - 29.08 %
- Extended Product Lifetime: Product Durability
- Offered with Takeback Services: Take Back for Recycling
- End Of Life Disassembling Instructions: 9AKK108470A1744
- Environmental Product Declaration - EPD: 9AKK108468A5757
- Type of Residual Current: Type B
- Test Voltage (Ut): 110 ... 253 V
- Dielectric Test Voltage: 2500 kV
- Maximum Surge Current: 3 kA
- Leakage Current Type: B
- Power Supply Connection: Arbitrary
- Electrical Endurance: 10000 cycle
More info
▲| ABB EcoSolutions | |
|---|---|
| ABB EcoSolutions | Yes |
| EcoSolutions Profile | 9AKK108469A3795 |
| Recyclability Rate of the Product acc. to EN45555 | Design for Closing Resource Loops - Standard EN45555 - 77.05 % |
| ABB Site Meeting Group Waste To Landfill Target | No non-hazardous waste is sent to a landfill |
| UL 2799 Zero Waste To Landfill Validation available | |
| Sustainable Material Content in Packaging (wt. %) | Recycled Cardboard - 29.08 % |
| Recycled Cardboard - 61.23 % | |
| Recycled Cardboard - 2.66 % | |
| Recycled Paper - 0 % | |
| Recycled Paper - 0 % | |
| Extended Product Lifetime | Product Durability |
| Offered with Takeback Services | Take Back for Recycling |
| End Of Life Disassembling Instructions | 9AKK108470A1744 |
| Environmental Product Declaration - EPD | 9AKK108468A5757 |
| Technical | |
| Type of Residual Current | Type B |
| Test Voltage (Ut) | 110 ... 253 V |
| Dielectric Test Voltage | 2500 kV |
| Maximum Surge Current | 3 kA |
| Leakage Current Type | B |
| Power Supply Connection | Arbitrary |
| Electrical Endurance | 10000 cycle |
| Mechanical Endurance | 20000 cycle |
| Number of Poles | 4P |
| Number of Modular Spacings per DIN Rail | 4 |
| Operating Characteristic | 10ms Delay (High Immunity) |
| Position of Neutral Terminals | Right |
| Tightening Torque | 2.8 N·m |
| Accessory Type | Auxiliary contact |
| Signal contact/auxiliary contact | |
| Shunt trip | |
| Undervoltage release | |
| Overvoltage release | |
| Motor operating device | |
| Auto reclosing unit | |
| Actuator Type | Toggle - Insulation group I - II, RAL 5015 |
| Housing Type | Insulation group I - II, RAL 7035 |
| Screw Terminal Type | Failsafe Bi-directional Cylinder-lift Terminal |
| Options Provided | None |
| Accessories Available | Yes |
| Cable Size | 25 mm² |
| Connecting Capacity | Busbar 10 mm² |
| Rigid 25 ... 25 mm² | |
| Flexible 25 ... 25 mm² | |
| Rated Cross-Section | 4 - Multi-Wired 0...25 mm² |
| 1 - Solid-Core 25...25 mm² | |
| Wire Stripping Length | 12 mm |
| Terminal Type | Screw Terminals |
| Electrical | |
| Rated Voltage (Ur) | 230/400 V |
| Rated Operational Voltage | 230 … 400 V AC |
| Rated Insulation Voltage (Ui) | 500 V |
| Rated Impulse Withstand Voltage (Uimp) | 4 kV |
| Input Voltage Type | AC |
| Rated Current (In) | 40 A |
| Rated Residual Current | 500 mA |
| Rated Conditional Short-Circuit Current (Inc) | (Typ gG/gLfuse, 500 V) 100 A |
| Selective MCB S750-E 63A or S750DR-E/K 100 A | |
| Frequency (f) | 50/60 Hz |
| Rated Frequency (f) | 50 … 60 Hz |
| Power Loss | at Rated Operating Conditions per Pole 1.92 W |
| Total 9.26 W | |
| Design | |
| RAL Number | RAL 7035 - Light Grey |
| Number of Modules | 4 |
| Material Compliance | |
| RoHS Declaration | 9AKK106713A5610 |
| RoHS Information | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
| RoHS Date | 20141120 |
| REACH Declaration | 9AKK108467A9482 |
| REACH Information | True - contains substances > 0.1 mass percentage |
| REACH Date | 20240429 |
| Conflict Minerals Reporting Template (CMRT) | 9AKK108468A3363 |
| SCIP | 10b8311e-47e3-4a9c-bc31-a2d09986d074 Italy |
| WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) |
| WEEE B2C / B2B | Business To Consumer |
| Environmental | |
| Ambient Air Temperature | Operation -25...+65 °C |
| Storage -40…+70 °C | |
| Degree of Protection | Terminals IP20 |
| Housing IP40 | |
| Pollution Degree | 2 |
| Environmental Conditions | 28 cycle |
| with 55 °C / 90-96 % | |
| and 25 °C / 95-100 % | |
| Resistance to Vibrations | 20 Cycles with Load 0.8 In: 1g or 1mm 50 … 150 … 5 Hz |
| Resistance to Shock acc. to IEC 60068-2-27 | 25g 2 shocks 13 ms |
| Environmental Information | Refer to RoHS |
| Dimensions | |
| Width in Number of Modular Spacings | 4 |
| Product Net Width | 70 mm |
| Product Net Height | 85 mm |
| Product Net Depth / Length | 69 mm |
| Product Net Weight | 380 g |
| Built-In Depth (t2) | 69 mm |
| Dimension Diagram | 9AKK106354A0759 |
| Engineering | |
| EPLAN Data | 9AAF619163_EPLAN |
| Ordering | |
| Package Level 1 Units | box 1 piece |
| Package Level 1 Gross Weight | 0.415 kg |
| E-Number (Finland) | 3210603 |
| E-Number (Norway) | 1683080 |
| Certificates and Declarations | |
| Declaration of Conformity - CE | 9AKK106713A5610 |
| Installation | |
| Instructions and Manuals | 9AKK107992A0195 |
| Mounting Type | DIN-Rail |
| Mounting Position | Any |
| Popular Downloads | |
| Data Sheet, Technical Information | 9AKK107991A7569 |
| External Classifications and Standards | |
| ETIM 9 | EC000003 - Residual current circuit breaker (RCCB) |
| ETIM 10 | EC000003 - Residual current circuit breaker (RCCB) |
| UNSPSC | 39121601 |
| eClass | V11.0 : 27142201 |
| IDEA Granular Category Code (IGCC) | 4875 >> Residual current circuit breaker (RCCB) |
| Object Classification Code | F |
| Standards | IEC/EN 61008-1, IEC/EN 61008-2-1, IEC/EN 62423 |