Abb residual current device registered under part number 2CSF202001R2900. Devices in this category are standard safety components utilized to safeguard electrical installations against earth faults and insulation breakdowns. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Number of poles: 2
- Rated voltage: 230 V
- Rated current: 100 A
- Rated insulation voltage Ui: 500 V
- Rated impulse withstand voltage Uimp: 4 kV
- Mounting method: DIN rail
- Leakage current type: AC
- Selective protection: No
- Short-time delayed tripping: No
- Surge current capacity: 0.25 kA
- With interlocking device: Yes
- Additional equipment possible: Yes
- Degree of protection (IP): IP20
- Width in number of modular spacings: 2
- Built-in depth: 69 mm
- Ambient temperature during operating: -25 °C
More info
▲The RCCBs F200 series assures protection to people and installations against fault current to earth. A large offer for standard instantaneous and selective AC and A types is completed with some configurations for special applications.
Ordering
- EAN:
- 8012542914501
- Minimum Order Quantity:
- 1 piece
- Customs Tariff Number:
- 85363030
Dimensions
- Product Net Width:
- 0.035m
- Product Net Height:
- 0.085m
- Product Net Depth:
- 0.069m
- Product Net Weight:
- 0.200kg
Container Information
- Package Level 1 Units:
- 1 piece
- Package Level 1 Width:
- 0.041 m
- Package Level 1 Height:
- 0.078 m
- Package Level 1 Length:
- 0.096 m
- Package Level 1 Gross Weight:
- 0.225 kg
- Package Level 1 EAN:
- 8012542914501
Technical
- Standards:
- EN 61008
UL 1053
- Operating Characteristic:
- Instantaneous
- Type of Residual Current:
- AC type
- Rated Residual Current:
- 100 mA
- Rated Current (In):
- 100 A
- Number of Poles:
- 2
- Power Loss:
- at Rated Operating Conditions per Pole 6.5 W
Environmental
- RoHS Status:
- Planned to follow EU Directive 2002/95/EC August 18, 2005 and amendment after 2007 Q3
Certificates and Declarations (Document Number)
- Declaration of Conformity - CE:
- ITSCE116F200
- RoHS Information:
- 2CSC423001K0201
Classifications
- Object Classification Code:
- Q
- ETIM 4:
- EC000003 - Residual current circuit breaker (RCCB)
- ETIM 5:
- EC000003 - Residual current circuit breaker (RCCB)