View larger
ESB40-20/230V GHE3491402R0006 ABB ESB40-20-230AC/DC Installation Contactor
ESB40-20/230V
GHE3491402R0006
ABB
1 Pcs.
Automation > Installation contactor for distribution board
ESB EN (DESTO)
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Providing dependable power switching in electrical distribution architectures, the ESB40-20/230V GHE3491402R0006 ABB ESB40-20-230AC/DC Installation Contactor functions as an installation contactor for managing medium-to-high current equipment. Engineers integrate such contactors to interface control systems with heavy-duty loads like industrial lighting arrays and heating banks. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Ambient Air Temperature: Operation -25 ... +55 °C Storage -40 ... +80 °C
- Maximum Operating Altitude Permissible: 2000 m
- Resistance to Shock acc. to IEC 60068-2-27: 11 ms Pulse 15g
- Resistance to Vibrations acc. to IEC 60068-2-6: 5g / 3 … 150 Hz
- RoHS Status: Following EU Directive 2002/95/EC August 18, 2005 and amendment
- Maximum Operating Voltage UL/CSA: Main Circuit 480 V AC
- Ampere Rating UL/CSA: 21 A
- Horsepower Rating UL/CSA: (220 ... 240 V AC) Single Phase 7.5 Hp (440 ... 480 V AC) Three Phase 15 Hp
- General Use Rating UL/CSA: (acc. to UL 480 V) 40 A
- Connecting Capacity Main Circuit UL/CSA: Stranded 16 ... 4 AWG
- Tightening Torque UL/CSA: Control Circuit 8 in·lb Main Circuit 20 in·lb
- Connecting Capacity Control Circuit UL/CSA: Stranded 16 ... 10 AWG
- Coil Consumption: Average Holding Value 50 Hz 5 V·A Average Pull-in Value 50 Hz 5 V·A
- Coil Operating Limits: (acc. to IEC 60947-4-1)0.85 ... 1.1 x Uc (at θ ≤ 55 °C)
- Connecting Capacity-Control Circuit: Rigid 1/2x 1 ... 4 mm² Rigid 2x 2.5 mm²
- Degree of Protection: IP20
More info
▲The ESB40 installation contactor is a 2 pole contactor suitable for modular switchboards. They are specially designed fitting to modular DIN rail products and for applications where customers want to use the panel design with high finger protection. Installation contactors are used in residential, commercial and industrial applications for the control of single or three-phase loads up to 40 A or switching of control signals. Further features are the noiseless and hum-free DC coil, the integrated overvoltage protection up to 5 kV and a switch position indication. Auxiliary contacts, distance pieces and sealing cover for protection against unauthorized changes are available as accessory.
Ordering
- EAN:
- 4013614085314
- Minimum Order Quantity:
- 1 piece
- Customs Tariff Number:
- 85365080
Dimensions
- Product Net Width:
- 54mm
- Product Net Height:
- 85mm
- Product Net Depth:
- 65mm
- Product Net Weight:
- 0.37kg
Container Information
- Package Level 1 Units:
- 3 piece
- Package Level 1 Width:
- 89 mm
- Package Level 1 Height:
- 69 mm
- Package Level 1 Length:
- 165 mm
- Package Level 1 Gross Weight:
- 1.155 kg
- Package Level 1 EAN:
- 4013614421204
Environmental
- Ambient Air Temperature:
- Operation -25 ... +55 °C
Storage -40 ... +80 °C
- Maximum Operating Altitude Permissible:
- 2000 m
- Resistance to Shock acc. to IEC 60068-2-27:
- 11 ms Pulse 15g
- Resistance to Vibrations acc. to IEC 60068-2-6:
- 5g / 3 … 150 Hz
- RoHS Status:
- Following EU Directive 2002/95/EC August 18, 2005 and amendment
Technical UL/CSA
- Maximum Operating Voltage UL/CSA:
- Main Circuit 480 V AC
- Ampere Rating UL/CSA:
- 21 A
- Horsepower Rating UL/CSA:
- (220 ... 240 V AC) Single Phase 7.5 Hp
(440 ... 480 V AC) Three Phase 15 Hp
- General Use Rating UL/CSA:
- (acc. to UL 480 V) 40 A
- Connecting Capacity Main Circuit UL/CSA:
- Stranded 16 ... 4 AWG
- Tightening Torque UL/CSA:
- Control Circuit 8 in·lb
Main Circuit 20 in·lb
- Connecting Capacity Control Circuit UL/CSA:
- Stranded 16 ... 10 AWG
Additional Information
- Coil Consumption:
- Average Holding Value 50 Hz 5 V·A
Average Pull-in Value 50 Hz 5 V·A
- Coil Operating Limits:
- (acc. to IEC 60947-4-1)0.85 ... 1.1 x Uc (at θ ≤ 55 °C)
- Connecting Capacity-Control Circuit:
- Rigid 1/2x 1 ... 4 mm²
Rigid 2x 2.5 mm²
- Connecting Capacity-Main Circuit:
- Flexible with Ferrule 1x 1.5 ... 16 mm²
Flexible with Insulated Ferrule 1x 1.5 ... 16 mm²
Flexible 1x 1.5 ... 16 mm²
Rigid 1x 1.5 ... 25 mm²
Rigid 2x 10 mm²
- Degree of Protection:
- IP20
- Drop-out Voltage in % of Uc:
- 10 ... 75
- Electrical Durability:
- AC-1 150000 cycle
AC-3 170000 cycle
AC-7a 150000 cycle
AC-7b 170000 cycle
- Frequency (f):
- 40 ... 450 Hz
- Fuse Type:
- Class K5 - 40 A
- IIT Publishing Status:
- Level 0 - Information enabled
- Maximum Electrical Switching Frequency:
- AC-1 300 cycles per hour
AC-3 600 cycles per hour
AC-7a 300 cycles per hour
AC-7b 600 cycles per hour
- Mechanical Durability:
- 1000000 cycle
- Mounting on DIN Rail:
- TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715
- Mounting Position:
- Position 1 to 5
- Number of Main Contacts NC:
- 0
- Number of Main Contacts NO:
- 2
- Number of Poles:
- 2
- Pollution Degree:
- 3
- Power Loss:
- at Rated Operating Conditions per Pole 4 W
- Product Main Type:
- ESB40
- Product Name:
- Installation Contactor
- Rated Breaking Capacity AC-3 acc. to IEC 60947-4-1:
- 8 x Ie / AC-3
- Rated Control Circuit Voltage (Uc):
- 230 V
- Rated Frequency (f):
- Control Circuit DC
Control Circuit 50 Hz
Control Circuit 60 Hz
Control Circuit 400 Hz
Main Circuit DC
Main Circuit 50 Hz
Main Circuit 60 Hz
- Rated Impulse Withstand Voltage (Uimp):
- 6 kV
- Rated Insulation Voltage (Ui):
- acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 500 V
acc. to UL/CSA 600 V
- Rated Making Capacity AC-3 acc. to IEC 60947-4-1:
- 10 x Ie / AC-3
- Rated Operational Current AC-1 (Ie):
- (NC) 30 A
(NO) 40 A
- Rated Operational Current AC-3 (Ie):
- (230 V) Single Phase 22 A
(400 V) Three Phase 22 A
- Rated Operational Current AC-7b (Ie):
- (230 V) Single Phase 22 A
(400 V) Three Phase 22 A
- Rated Operational Power AC-1 (Pe):
- 230 V Single Phase 9.2 kW
400 V Three Phase 26 kW
- Rated Operational Power AC-3 (Pe):
- (230 V) Single Phase 3.7 kW
(400 V) Three Phase 11 kW
- Rated Operational Power AC-7a (Pe):
- (230 V) Single Phase 9.2 kW
(400 V) Three Phase 26 kW
- Rated Operational Voltage:
- Main Circuit 220 V DC
Main Circuit 400 V AC
- Rated Short-time Withstand Current (Icw):
- at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 176 kA
- Recommended Screw Driver:
- Control Circuit Pozidriv 1
Main Circuit Pozidriv 2
- RoHS Date:
- 0456
- Standards:
- IEC/EN 60947-1
IEC/EN 60947-4-1
IEC/EN 60947-5-1
IEC/EN 61095
UL 60947-1
UL 60947-4-1
- Terminal Type:
- Screw Terminals
- Tightening Torque:
- Control Circuit 0.9 N·m
Main Circuit 2.5 N·m
- Wire Stripping Length:
- Control Circuit 7 mm
Main Circuit 13 mm
Certificates and Declarations (Document Number)
- BV Certificate:
- 1SAA920000-0203
- CB Certificate:
- 1SAA920001-2003
- CCC Certificate:
- 1SAA920000-3804
- CEBEC Certificate:
- 1SAA920001-2001
- cUL Certificate:
- 1SAA920000-1701
- Data Sheet, Technical Information:
- 1SAC101101D0201
- Declaration of Conformity - CE:
- 1SAD938508-0007
- DNV Certificate:
- 1SAA920000-0305
- EAC Certificate:
- 1SAA920000-2702
- GL Certificate:
- 1SAA920000-0403
- RMRS Certificate:
- 1SAA920000-0703
- RoHS Information:
- 1SAA920005-4401
- UL Certificate:
- 1SAA920000-1603
Classifications
- eClass:
- 7.0 27142308
- ETIM 4:
- EC001653 - Installation contactor for distribution board
- ETIM 5:
- EC001653 - Installation contactor for distribution board
- Object Classification Code:
- Q