ABB ESB20-11/230V ESB20-11/230V GHE3211302R0006 ABB ESB20-11 230V 50Hz / 264V 60Hz Installation Contactor View larger
Images are for illustrative purposes only. Please refer to data sheet for details

ESB20-11/230V GHE3211302R0006 ABB ESB20-11 230V 50Hz / 264V 60Hz Installation Contactor

ESB20-11/230V

GHE3211302R0006

ABB

1 Pcs.

ESB20-11 230V 50Hz / 264V 60Hz Installation Contactor Contact.ESB20-11/230V 1NA 1NC 20A 230V

Automation > Installation contactor for distribution board
ESB EN (FRCTLP)

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.

Request Quote

Product Overview

An Abb ESB20-11/230V installation contactor operates as an electromechanical control device designed for seamless integration into commercial switchgear, managing auxiliary circuits and lighting installations safely. Such components provide dependable remote switching performance.

Pricing, availability and lead time are confirmed per enquiry through an RFQ.

  • Ambient Air Temperature: Close to Contactor Fitted with Thermal O/L Relay (0.85 ... 1.1 Uc) -25 ... +55 °C
  • RoHS Status: Planned to follow EU Directive 2002/95/EC August 18, 2005 and amendment after 2006-07-01
  • Coil Operating Limits: (acc. to IEC 60947-4-1)0.85 ... 1.1 x Uc (at θ ≤ 55 °C) °C
  • Connecting terminals (delivered in open position) Main poles: M 4
  • Drop-out Voltage in % of Uc: Approximate 20 … 75 %
  • Electrical Durability: max. IeAC-3 0.15 million
  • IIT Publishing Status: Level 0 - Information enabled
  • Maximum Electrical Switching Frequency: AC-1 300 cycles per hour AC-3 600 cycles per hour
  • Mechanical Durability: 1 million
  • Minimum Switching Capacity: 17 / 200 volt per milliamp
  • Number of Main Contacts NC: 1
  • Number of Main Contacts NO: 1
  • Power Loss: 1 W
  • Product Main Type: ESB20
  • Product Name: Installation Contactor
  • Rated Frequency (f): 50 / 60 Hz

More info

▲

ESB20-11 230V 50Hz / 264V 60Hz Installation Contactor

Ordering

  • EAN:
    3471520263560
  • Minimum Order Quantity:
    10 piece
  • Customs Tariff Number:
    85369085

Dimensions

  • Product Net Width:
    17.5mm
  • Product Net Height:
    86mm
  • Product Net Depth:
    67mm
  • Product Net Weight:
    0.200kg

Container Information

  • Package Level 1 Units:
    10 piece
  • Package Level 1 Width:
    92 mm
  • Package Level 1 Height:
    76 mm
  • Package Level 1 Length:
    183 mm
  • Package Level 1 Gross Weight:
    1.3 kg
  • Package Level 1 EAN:
    3471520263560
  • Package Level 2 Units:
    120 piece
  • Package Level 3 Units:
    2160 piece

Environmental

  • Ambient Air Temperature:
    Close to Contactor Fitted with Thermal O/L Relay (0.85 ... 1.1 Uc) -25 ... +55 °C
  • RoHS Status:
    Planned to follow EU Directive 2002/95/EC August 18, 2005 and amendment after 2006-07-01

Additional Information

  • Coil Consumption:
    Average Holding Value 50 / 60 Hz 3.2 V·A
    Average Holding Value 50 / 60 Hz 1.2 W
    Average Pull-in Value 50 Hz 8 V·A
    Average Pull-in Value 60 Hz 10 V·A
  • Coil Operating Limits:
    (acc. to IEC 60947-4-1)0.85 ... 1.1 x Uc (at θ ≤ 55 °C) °C
  • Connecting terminals (delivered in open position) Coils terminals:
    M 3
  • Connecting terminals (delivered in open position) Main poles:
    M 4
  • Drop-out Voltage in % of Uc:
    Approximate 20 … 75 %
  • Electrical Durability:
    max. IeAC-3 0.15 million
  • IIT Publishing Status:
    Level 0 - Information enabled
  • Maximum Electrical Switching Frequency:
    AC-1 300 cycles per hour
    AC-3 600 cycles per hour
  • Mechanical Durability:
    1 million
  • Minimum Switching Capacity:
    17 / 200 volt per milliamp
  • Mounting on DIN Rail:
    TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715
    TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
  • Number of Main Contacts NC:
    1
  • Number of Main Contacts NO:
    1
  • Operate Time:
    Between Coil Energization and NO Contact Closing 12 ms
    Between Coil De-energization and NC Contact Closing 12 ms
  • Power Loss:
    1 W
  • Product Main Type:
    ESB20
  • Product Name:
    Installation Contactor
  • Rated Frequency (f):
    50 / 60 Hz
  • Rated Frequency Limits:
    50 … 60 Hz
  • Rated Insulation Voltage (Ui):
    acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 400 V
  • Rated Operational Current (Ie):
    9 A
  • Rated Operational Current AC-1 (Ie):
    for Air Temperature Near the Contactor = 55 °C 20 A
  • Rated Operational Power AC-1 (Pe):
    230 V Single Phase 4 kW
  • Rated Operational Voltage:
    Main Circuit 250 V
  • Rated Short-time Withstand Current (Icw):
    at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 72 A
  • Standards:
    Devices complying with international standards IEC 60 947-4-1 / IEC 1095 and European standards EN 60 947-4-1 / EN 61095.
  • Terminal Type:
    Screw Terminals

Certificates and Declarations (Document Number)

Classifications

  • E-nummer:
    3225014
  • ETIM 4:
    EC001653 - Installation contactor for distribution board
  • ETIM 5:
    EC001653 - Installation contactor for distribution board
  • Object Classification Code:
    Q
  • UNSPSC:
    39121529

Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.