ABB SK827041-AF SK827041-AF ABB EK550-40-11 CONT. 4P 800A AC1 BOB. 110Va View larger
Images are for illustrative purposes only. Please refer to data sheet for details

SK827041-AF ABB EK550-40-11 CONT. 4P 800A AC1 BOB. 110Va

SK827041-AF

SK827041AF

ABB

1 Pcs.

EK550-40-11 CONT. 4P 800A AC1 BOB. 110Va EK550-40-11 110V 50Hz/120V 60Hz Contactor

Automation > Power contactor, AC switching
Contactors and overload relays

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Add your required quantity to begin.

No account, online checkout or payment is required.

More info

classification
Minimum order quantity1 piece
Tariff code85364900
Popular Downloads
Technical data, technical information1SBC100214C0202
Instructions and manuals5309660-30
Dimensions
Product Width270 mm
Product length225.5 mm
Product height272 mm
Product Weight15.5 kg
Technique
Number of primary contacts NO4
Number of NC Primary Contacts0
Number of auxiliary contacts NO1
Number of NC auxiliary contacts1
Number of poles4P
Nominal operating voltageMain Circuit 1000 V
Conventional free-air thermal current (ITh)according to IEC 60947-4-1, open contactors θ = 40 °C 800 A
Rated Operating Current AC-1 (Iand)(1000 V) 40 °C 800 A
(1000 V) 60 °C 650 A
(1000 V) 70 °C 575 A
(690 V) 40°C 800 A
(690 V) 55°C 650 A
(690 V) 60 °C 650 A
(690 V) 70 °C 575 A
Rated operating current AC-3 (Iand)(440 V) 55°C 550 A
(500 V) 55°C 550 A
(690 V) 55°C 550 A
(1000 V) 55 °C 175 A
(380 / 400 V) 55 °C 550 A
(220 / 230 / 240 V) 55°C 550 A
Rated operating power AC-3 (Pand)(415 V) 315 kW
(440 V) 315 kW
(500 V) 400 kW
(690 V) 500 kW
(1000 V) 35 kW
(380 / 400 V) 280 kW
(220 / 230 / 240 V) 160 kW
Rated Breaking Capacity AC-38 x Ie AC-3
Rated Manufacturing Capacity AC-310 x Ie AC-3
Short circuit protection devicesgG Type Fuses 1.5 ... 1.8 In A
Short-term rated current Low voltage (ICw)at 40 °C ambient temperature, in open air, from a cold state of 10 s 5300 A
at 40 °C ambient temperature, in open air, from a cold state of 15 min 1000 A
at 40 °C ambient temperature, outdoors, from a cold state 1 min 3000 A
at 40 °C ambient temperature, in open air, from a cold state of 1 s 5500 A
at 40 °C ambient temperature, in open air, from a cold state of 30 s 3700 A
Rated insulation voltage (Ui)according to IEC 60947-4-1 and VDE 0110 (Gr. C) 1000 V
to UL/CSA 600 V
Nominal impulse-supported voltage (Uimp)8 kV
Maximum electrical switching frequency(AC-1) 300 cycles per hour
(AC-2 / AC-4) 120 cycles per hour
(AC-3) 300 cycles per hour
Mechanical durability5 million
Maximum mechanical switching frequency3600 cycles per hour
Coil Operating Limits(acc. to IEC 60947-4-1) Uc (at θ ≤ 70 °C)
Control circuit voltage rating (Uc)50 Hz 110 V
60 Hz 120 V
Coil consumptionMaintenance at the maximum nominal voltage of the control circuit 50 Hz 125 V·A
Maintenance at the maximum nominal voltage of the control circuit 60 Hz 140 V·A
Pull-in at the maximum voltage rating of the control circuit 50 Hz 3500 V·A
Pull-in at the maximum nominal voltage of the control circuit 60 Hz 4000 V·A
Power lossunder nominal operating conditions per pole 60 W
Operating TimeBetween coil de-energization and NC 10 contact closure... 20 ms
Between coil de-energization and non-contact opening 13 ... 23 ms
Between coil energization and NC 25 contact opening, NC 25 ... 55 ms
Between coil energization and non-contact shut-off 30 ... 60 ms
Degree of protectionAcc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20
Terminal blocks (supplied in the open position) Main polesFlat type c/w screws and bolts
Terminal TypeMain Circuit: Bars
Product NameBlock Contactor
UL/CSA Technique
UL/CSA General Purpose Rating(600 V AC) 540 A
Environment
Ambient TemperatureClose to Contactor Fitted with Thermal O/L Relay (0.85 ... 1.1 Uc) -25 ... 55 °C
Close to Contactor without Thermal O/L Relay (0.85 ... 1.1 Uc) -40 ... 70 °C
Close to Contactor for Storage -50 ... 70 °C
Maximum permissible operating altitudeNo power reduction 3000 m
Material Compliance
Conflict Minerals Notification Template (CMRT)9AKK108467A5658
REACH Declaration2CMT2021-006202
RoHS Information2CMT2021-006277
RoHS StatusNo declaration needed
Toxic Substances Control Act - TSCA2CMT2023-006525
WEEE B2C / B2BFrom company to company
WEEE Category5. Small equipment (no external dimension more than 50cm)
Certificates and Declarations (Document Number)
CQC CertificateCQC2003010304094982
Declaration of Conformity - CCC2020980304001264
Declaration of Conformity - CE2CMT2015-005442
UL Certified20161201-E36588
Packaging Information
Packaging Level 1 UnitsBox 1 piece
Packaging Level 1 Width317 mm
Level 1 Long Packaging373 mm
Packaging Level 1 High234 mm
Packaging Level 1 Weight17.2 kg
EAN Level 1 Packaging7320500040386
External Classifications and Standards
Object Classification CodeQ
ETIM 7EC000066 - Power contactor, AC switching
ETIM 8EC000066 - Power contactor, AC switching
ETIM 9EC000066 - Power contactor, AC switching
E-classV11.0 : 27371003
UNSPSC39121529
IDEA Granular Category Code (IGCC)4755 >> Contactors

ETIM for SK827041-AF Low-voltage industrial controls and switchgear (EC000066)
Feature Name Feature Value
Rated control supply voltage AC 50 Hz (EF003978) 110 V
Rated control supply voltage AC 60 Hz (EF003979) 120 V
Voltage type for actuating (EF008242) AC
Rated operation current Ie at AC-1, 400 V (EF001393) 800 A
Rated operation current Ie at AC-3, 400 V (EF001392) 550 A
Rated operation power at AC-3, 400 V (EF001364) 280 kW
Modular version (EF001126) No
Number of auxiliary contacts as normally open contact (EF001376) 1
Number of auxiliary contacts as normally closed contact (EF001377) 1
Type of electrical connection of main circuit (EF006819) Rail connection
Number of normally closed contacts as main contact (EF001375) 0
Number of normally open contacts as main contact (EF001374) 4

Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.