View larger
SK827044-AF ABB EK1000-40-11 CONT. 4P BOB. 110V 50Hz
SK827044-AF
SK827044AF
ABB
1 Pcs.
Automation > Power contactor, AC switching
Contactors and overload relays
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Designed for heavy industrial environments, this ABB power contactor safely manages high-capacity electrical loads across large motor starter assemblies and power distribution panels. Multi-pole contactors are essential in heavy manufacturing applications where continuous duty cycles and robust current-carrying capabilities are required. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Minimum Order Quantity: 1 piece
- Customs Tariff Number: 85364900
- Data Sheet, Technical Information: 1SBC100214C0202
- Instructions and Manuals: 5309660-30
- Product Net Width: 270 mm
- Product Net Depth / Length: 225.5 mm
- Product Net Height: 272 mm
- Product Net Weight: 15.8 kg
- Number of Main Contacts NO: 4
- Number of Main Contacts NC: 0
- Number of Auxiliary Contacts NO: 1
- Number of Auxiliary Contacts NC: 1
- Number of Poles: 4P
- Rated Operational Voltage: Main Circuit 1000 V
- Conventional Free-air Thermal Current (I th ): acc. to IEC 60947-4-1, Open Contactors Θ = 40 °C 1000 A
- Rated Operational Current AC-1 (I e ): (1000 V) 40 °C 1000 A
More info
▲| Ordering | |
|---|---|
| Minimum Order Quantity | 1 piece |
| Customs Tariff Number | 85364900 |
| Popular Downloads | |
| Data Sheet, Technical Information | 1SBC100214C0202 |
| Instructions and Manuals | 5309660-30 |
| Dimensions | |
| Product Net Width | 270 mm |
| Product Net Depth / Length | 225.5 mm |
| Product Net Height | 272 mm |
| Product Net Weight | 15.8 kg |
| Technical | |
| Number of Main Contacts NO | 4 |
| Number of Main Contacts NC | 0 |
| Number of Auxiliary Contacts NO | 1 |
| Number of Auxiliary Contacts NC | 1 |
| Number of Poles | 4P |
| Rated Operational Voltage | Main Circuit 1000 V |
| Conventional Free-air Thermal Current (Ith) | acc. to IEC 60947-4-1, Open Contactors Θ = 40 °C 1000 A |
| Rated Operational Current AC-1 (Ie) | (1000 V) 40 °C 1000 A |
| (1000 V) 60 °C 800 A | |
| (1000 V) 70 °C 720 A | |
| (690 V) 40 °C 1000 A | |
| (690 V) 55 °C 800 A | |
| (690 V) 60 °C 800 A | |
| (690 V) 70 °C 720 A | |
| Rated Short-time Withstand Current Low Voltage (Icw) | at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 6400 A |
| at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 1200 A | |
| at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 3400 A | |
| at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 6800 A | |
| at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 4400 A | |
| Rated Insulation Voltage (Ui) | acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 1000 V |
| Rated Impulse Withstand Voltage (Uimp) | 8 kV |
| Maximum Electrical Switching Frequency | (AC-1) 300 cycles per hour |
| Mechanical Durability | 5 million |
| Maximum Mechanical Switching Frequency | 3600 cycles per hour |
| Coil Operating Limits | (acc. to IEC 60947-4-1) Uc (at θ ≤ 70 °C) |
| Rated Control Circuit Voltage (Uc) | 50 Hz 110 V |
| 60 Hz 120 V | |
| Coil Consumption | Holding at Max. Rated Control Circuit Voltage 50 Hz 125 V·A |
| Holding at Max. Rated Control Circuit Voltage 60 Hz 140 V·A | |
| Pull-in at Max. Rated Control Circuit Voltage 50 Hz 3500 V·A | |
| Pull-in at Max. Rated Control Circuit Voltage 60 Hz 4000 V·A | |
| Power Loss | at Rated Operating Conditions per Pole 80 W |
| Operate Time | Between Coil De-energization and NC Contact Closing 10 ... 20 ms |
| Between Coil De-energization and NO Contact Opening 13 ... 23 ms | |
| Between Coil Energization and NC Contact Opening 25 ... 55 ms | |
| Between Coil Energization and NO Contact Closing 30 ... 60 ms | |
| Degree of Protection | acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20 |
| Connecting Terminals (delivered in open position) Main Poles | Flat type c/w screws and bolts |
| Terminal Type | Main Circuit: Bars |
| Product Name | Block Contactor |
| Environmental | |
| Ambient Air Temperature | Close to Contactor Fitted with Thermal O/L Relay (0.85 ... 1.1 Uc) -25 ... 55 °C |
| Close to Contactor without Thermal O/L Relay (0.85 ... 1.1 Uc) -40 ... 70 °C | |
| Close to Contactor for Storage -50 ... 70 °C | |
| Maximum Operating Altitude Permissible | Without Derating 3000 m |
| Material Compliance | |
| Conflict Minerals Reporting Template (CMRT) | 9AKK108467A5658 |
| REACH Declaration | 2CMT2021-006202 |
| RoHS Declaration | 2CMT2021-006277 |
| Toxic Substances Control Act - TSCA | 2CMT2023-006525 |
| WEEE B2C / B2B | Business To Business |
| WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) |
| Certificates and Declarations | |
| CQC Certificate | CQC2003010304094983 |
| Declaration of Conformity - CCC | 2020980304001285 |
| Declaration of Conformity - CE | 2CMT2015-005442 |
| Container Information | |
| Package Level 1 Units | box 1 piece |
| Package Level 1 Width | 317 mm |
| Package Level 1 Depth / Length | 373 mm |
| Package Level 1 Height | 234 mm |
| Package Level 1 Gross Weight | 17.5 kg |
| Package Level 1 EAN | 7320500200667 |
| External Classifications and Standards | |
| Object Classification Code | Q |
| ETIM 7 | EC000066 - Power contactor, AC switching |
| ETIM 8 | EC000066 - Power contactor, AC switching |
| ETIM 9 | EC000066 - Power contactor, AC switching |
| eClass | V11.0 : 27371003 |
| UNSPSC | 39121529 |
| IDEA Granular Category Code (IGCC) | 4755 >> Contactors |