The ABB 1SAX351001R1101 EF146-150 electronic overload relay is built to manage heavy electrical loads and protect high-amperage motors from thermal damage. Industrial overload units monitor current thresholds within motor control centers, disconnecting power automatically when overload conditions threaten the system. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Minimum Order Quantity: 1 piece
- Customs Tariff Number: 85364900
- Data Sheet, Technical Information: 2CDC107041D0201
- Instructions and Manuals: 2CDC107028M6803
- Instructions and Manuals (Part 2): 1SAC200017M0002
- Ex Operating Instructions: 2CDC107043M6801
- Time-Current Characteristic Curve: 1SAX100509F0002
- CAD Dimensional Drawing: 2CDC001079B0201
- Dimension Diagram: 1SAX300407F0001
- Product Net Width: 89.05 mm
- Product Net Height: 150.4 mm
- Product Net Depth / Length: 105.2 mm
- Product Net Weight: 0.879 kg
- Setting Range: 54 ... 150 A
- Rated Operational Voltage: Auxiliary Circuit 600 V AC/DC
- Rated Operational Current (I e ): 150 A
More info
▲| Ordering | |
|---|---|
| Minimum Order Quantity | 1 piece |
| Customs Tariff Number | 85364900 |
| Popular Downloads | |
| Data Sheet, Technical Information | 2CDC107041D0201 |
| Instructions and Manuals | 2CDC107028M6803 |
| Instructions and Manuals (Part 2) | 1SAC200017M0002 |
| Ex Operating Instructions | 2CDC107043M6801 |
| Time-Current Characteristic Curve | 1SAX100509F0002 |
| 1SAX100510F0001 | |
| CAD Dimensional Drawing | 2CDC001079B0201 |
| Dimension Diagram | 1SAX300407F0001 |
| Dimensions | |
| Product Net Width | 89.05 mm |
| Product Net Height | 150.4 mm |
| Product Net Depth / Length | 105.2 mm |
| Product Net Weight | 0.879 kg |
| Technical | |
| Setting Range | 54 ... 150 A |
| Rated Operational Voltage | Auxiliary Circuit 600 V AC/DC |
| Main Circuit 1000 V AC | |
| Rated Operational Current (Ie) | 150 A |
| Rated Frequency (f) | Auxiliary Circuit 50 Hz |
| Auxiliary Circuit 60 Hz | |
| Auxiliary Circuit DC | |
| Main Circuit 50 Hz | |
| Main Circuit 60 Hz | |
| Rated Impulse Withstand Voltage (Uimp) | Auxiliary Circuit 6 kV |
| Main Circuit 8 kV | |
| Rated Insulation Voltage (Ui) | 1000 V |
| Number of Poles | 3P |
| Number of Auxiliary Contacts NC | 1 |
| Number of Auxiliary Contacts NO | 1 |
| Number of Protected Poles | 3 |
| Conventional Free-air Thermal Current (Ith) | Auxiliary Circuit NC 6 A |
| Auxiliary Circuit NO 6 A | |
| Rated Operational Current AC-15 (Ie) | (240 V) NC 3 A |
| (240 V) NO 3 A | |
| (400 V) NC 1.1 A | |
| (400 V) NO 1.1 A | |
| (500 V) NC 0.75 A | |
| (500 V) NO 0.75 A | |
| Rated Operational Current DC-13 (Ie) | (125 V) NC 0.55 A |
| (125 V) NO 0.5 A | |
| (24 V) NC 1.5 A | |
| (24 V) NO 1.5 A | |
| (250 V) NC 0.27 A | |
| (250 V) NO 0.27 A | |
| (60 V) NC 0.55 A | |
| (60 V) NO 0.55 A | |
| Degree of Protection | Housing IP20 |
| Main Circuit Terminals IP10 | |
| Pollution Degree | 3 |
| Connecting Capacity Auxiliary Circuit | Flexible with Ferrule 1/2x 0.75 ... 2.5 mm² |
| Flexible with Insulated Ferrule 1/2x 0.75 ... 2.5 mm² | |
| Flexible 1/2x 0.75 ... 2.5 mm² | |
| Rigid 1/2x 1 ... 4 mm² | |
| Connecting Capacity Main Circuit | Flexible with Ferrule 1x 10 ... 70 mm² |
| Flexible with Ferrule 2x 10 ... 35 mm² | |
| Flexible with Insulated Ferrule 1x 10 ... 70 mm² | |
| Flexible with Insulated Ferrule 2x 2 ... 35 mm² | |
| Flexible 1x 10 ... 70 mm² | |
| Flexible 2x 10 ... 35 mm² | |
| Rigid 1x 10 ... 95 mm² | |
| Rigid 2x 10 ... 35 mm² | |
| Tightening Torque | Auxiliary Circuit 0.8 ... 1.2 N·m |
| Main Circuit 10 N·m | |
| Wire Stripping Length | Auxiliary Circuit 9 mm |
| Main Circuit 20 mm | |
| Recommended Screw Driver | Auxiliary Circuit Pozidriv 2 |
| Main Circuit Hexagon 4 | |
| Mounting Position | 1 ... 6 |
| Power Loss | at Rated Operating Conditions per Pole 0.204 ... 1.575 W |
| Suitable For | AF116 |
| AF140 | |
| AF146 | |
| Standards | IEC/EN 60947-1 |
| IEC/EN 60947-4-1 | |
| IEC/EN 60947-5-1 | |
| UL 60947-1 | |
| UL 60947-4-1 | |
| Technical UL/CSA | |
| Maximum Operating Voltage UL/CSA | Main Circuit 600 V AC |
| Contact Rating UL/CSA | (NC:) B600 |
| (NC:) Q600 | |
| (NO:) B600 | |
| (NO:) Q600 | |
| Connecting Capacity Main Circuit UL/CSA | Flexible 1x 6-00 AWG |
| Flexible 2x 6-2 AWG | |
| Stranded 2x 6-2 AWG | |
| Stranded 1x 6-00 AWG | |
| Connecting Capacity Auxiliary Circuit UL/CSA | Flexible 1/2x 18-10 AWG |
| Stranded 1/2x 18-10 AWG | |
| Tightening Torque UL/CSA | Auxiliary Circuit 7 ... 1 in·lb |
| Main Circuit 70 in·lb | |
| Environmental | |
| Ambient Air Temperature | Operation -25 ... +70 °C |
| Operation Compensated -25 ... +70 °C | |
| Storage -50 ... +85 °C | |
| Ambient Air Temperature Compensation | Yes |
| Maximum Operating Altitude Permissible | 2000 m |
| Resistance to Shock acc. to IEC 60068-2-27 | 11 ms Pulse 25g |
| Resistance to Vibrations | 5g 3 ... 150 Hz |
| RoHS Information | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
| Toxic Substances Control Act - TSCA | 2CMT2023-006525 |
| Material Compliance | |
| Conflict Minerals Reporting Template (CMRT) | 9AKK108467A5658 |
| REACH Declaration | 2CMT2021-006202 |
| RoHS Declaration | 1SVD981001-4401 |
| WEEE B2C / B2B | Business To Business |
| WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) |
| ABB EcoSolutions | |
| ABB EcoSolutions | Yes |
| ABB Site Meeting Group Waste To Landfill Target | UL 2799 Zero Waste To Landfill Validation available |
| End Of Life Disassembling Instructions | 1SAC200283H0001 |
| Environmental Information | 1SAC200100H0001 |
| Environmental Product Declaration - EPD | 1SAC200236H0001 |
| Certificates and Declarations | |
| ABS Certificate | 1SAA941002-0102 |
| ATEX Certificate | 1SAA941004-3901 |
| BV Certificate | 1SAA941002-0201 |
| CB Certificate | 1SAA964013-2001 |
| CCC Certificate | 2024010304636746 |
| CCS Certificate | 1SAA941001-0901 |
| CQC Certificate | CQC2013010309592132 |
| Declaration of Conformity - CCC | 2020980309000286 |
| Declaration of Conformity - CE | 1SAD101100-3601 |
| Declaration of Conformity - UKCA | 1SAD201100-3601 |
| DNV Certificate | 1SAA941003-0302 |
| EAC Certificate | 1SAA941003-2701 |
| IECEx Certificate | 1SAA941000-4001 |
| LR Certificate | 1SAA941002-0501 |
| RINA Certificate | RINA_ELE376813CS |
| RMRS Certificate | 1SAA941001-0701 |
| UL Certificate | E48139-19990512 |
| Container Information | |
| Package Level 1 Units | box 1 piece |
| Package Level 1 Width | 160 mm |
| Package Level 1 Height | 107 mm |
| Package Level 1 Depth / Length | 97 mm |
| Package Level 1 Gross Weight | 0.984 kg |
| Package Level 1 EAN | 4013614442230 |
| External Classifications and Standards | |
| Object Classification Code | F |
| ETIM 9 | EC001080 - Electronic overload relay |
| ETIM 10 | EC001080 - Electronic overload relay |
| eClass | V11.0 : 27371502 |
| UNSPSC | 39122330 |
| IDEA Granular Category Code (IGCC) | 5365 >> Electronic overload relay |
| E-Number (Finland) | 3706582 |
| E-Number (Norway) | 4116702 |
| E-Number (Sweden) | 3210247 |