View larger
1SDA073376R1
073376
ABB
1 Pcs.
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
| ABB EcoSolutions | |
|---|---|
| ABB EcoSolutions | Yes |
| ABB Site Meeting Group Waste To Landfill Target | UL 2799 Zero Waste To Landfill Validation available |
| End Of Life Disassembling Instructions | 9AKK108468A2364 |
| Environmental Product Declaration - EPD | 9AKK108468A1905 |
| 9AKK108468A1913 | |
| Extended Product Lifetime | Lifetime Extension Services are Offered |
| Recyclability Rate of the Product acc. to EN45555 | Design for Closing Resource Loops - Standard EN45555 - 77 % |
| Material Compliance | |
| REACH Declaration | 9AKK108466A1425 |
| RoHS Declaration | 9AKK108466A1424 |
| RoHS Information | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
| Conflict Minerals Reporting Template (CMRT) | 9AKK108467A5658 |
| Toxic Substances Control Act - TSCA | 9AKK108467A8326 |
| SCIP | 77ba049f-10b5-4d2e-8c49-34038d34fd5f Italy |
| Simplified SCIP | 3e32310b-aa61-4422-9b6d-420cd270db5e Norway |
| 951f5456-07d3-41b4-bf90-0bc2b6d0541c Germany | |
| 0d95c4ce-6abb-48f9-874d-228a847b4957 Poland | |
| 96bdfada-6967-4ca0-bda4-672755574310 Belgium | |
| ab190791-edd3-4f4e-85a6-aaf869418489 Germany | |
| 0c52b1e0-0eb8-4eff-a781-d14aeb5d2a69 Sweden | |
| d1108afa-23fb-4f7d-95ce-0ebae45c32a8 Germany | |
| 16a45081-dcd3-411f-b245-f94d77806862 Hungary | |
| ae0a37a7-b635-4129-9c80-7e3bc85ed3bc Spain | |
| d46d0911-905c-415b-9494-a2a5490fa8ea France | |
| 56a902fc-ac5a-471d-9770-3b51f280bb69 Estonia | |
| 7be70dd9-a06d-43b5-b9f8-24fb22d9cfdb Greece | |
| eed15635-e0d2-4969-8e2d-e61a044138bc Netherlands | |
| 7c3a767c-4ced-441d-bc5f-e670703ddc1c Hungary | |
| 057cb5a5-c3d4-4752-b5d5-82ab6d113262 France | |
| c94b1b36-84d6-49a9-9f38-fb6997ab70bc Poland | |
| aa77c67d-f820-4a1a-b3de-0a2578b0a0f0 Sweden | |
| 0cc6a375-d2ed-4f7c-bddb-5395467983fb Bulgaria | |
| 3af2890b-c786-4668-a93e-58d96dbb9eae Portugal | |
| 06f6fadd-45a6-4be0-965a-4ad5bc9707c0 Czech Republic | |
| 49786eb9-11d8-4927-a191-61adb14fa340 Croatia | |
| cbb8d5fd-c436-4709-883b-0f3878480916 Germany | |
| 1e3df1e3-d80f-41d8-91db-fca503971141 Poland | |
| f50498ca-61a2-45ec-869e-848eea0dc376 Finland | |
| eaec9881-3129-4096-946c-e96b39e28694 Belgium | |
| 8044890b-fd51-4f70-a1c5-0b79e45a6ef3 Germany | |
| 162985e0-4533-452d-aeb2-ad9c1f5d18af Denmark | |
| Environmental | |
| Environmental Information | 9AKK108467A6707 |
| Ordering | |
| Order Code US and Canada | ZEVYETAF000A000000XX |
| EAN | 8015644772260 |
| Minimum Order Quantity | 1 piece |
| Customs Tariff Number | 85362090 |
| Dimensions | |
| Product Net Width | 1069 mm |
| Product Net Height | 425 mm |
| Product Net Depth / Length | 383 mm |
| Product Net Weight | 148 kg |
| Container Information | |
| Package Level 1 Units | box 1 piece |
| Package Level 1 Width | 515 mm |
| Package Level 1 Height | 610 mm |
| Package Level 1 Depth / Length | 1257 mm |
| Package Level 1 Gross Weight | 159 kg |
| Package Level 1 EAN | 8015644772260 |
| Additional Information | |
| Product Main Type | SACE Emax 2 |
| Product Name | Air Circuit Breaker |
| Product Type | Air Circuit Breaker |
| Version | W |
| CAD Dimensional Drawing | 1SDH001252R0264 |
| Technical | |
| Connecting Capacity | 6000 mm² |
| Current Type | AC |
| Electrical Durability | Ue =< 440 V 2000 cycle |
| Ue = 500 ... 690 V 2000 cycle | |
| 10 cycles per hour | |
| Mechanical Durability | 12000 cycle |
| 60 cycles per hour | |
| Neutral Pole Current ([%Iu]) | 100 % |
| Number of Poles | 4 / f |
| Power Loss | 1550 W |
| Rated Current (In) | 6300 A |
| Rated Impulse Withstand Voltage (Uimp) | acc. to IEC 60947-2 12 kV |
| Rated Insulation Voltage (Ui) | AC 1000 V |
| Rated Operational Voltage | 690 V AC |
| Rated Service Short-Circuit Breaking Capacity (Ics) | (220 V AC) 150 kA |
| (230 V AC) 150 kA | |
| (380 V AC) 150 kA | |
| (400 V AC) 150 kA | |
| (415 V AC) 150 kA | |
| (440 V AC) 150 kA | |
| (500 V AC) 130 kA | |
| (660 V AC) 100 kA | |
| (690 V AC) 100 kA | |
| Rated Service Short-Circuit Breaking Capacity, in % of Icu (Ics) | 100 % |
| Rated Short-time Withstand Current Low Voltage (Icw) | for 1 s 100 kA |
| for 3 s 100 kA | |
| Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (400 V AC) 150 kA |
| (415 V AC) 150 kA | |
| (440 V AC) 150 kA | |
| (500 V AC) 130 kA | |
| (525 V AC) 130 kA | |
| (690 V AC) 100 kA | |
| Rated Uninterrupted Current (Iu) | 6300 A |
| Rated Voltage (Ur) | 690 V |
| Recommended Screw Driver | M12 |
| Release | Ekip Touch LSIG |
| Release Type | EL |
| Short-Circuit Performance Level | V |
| Standards | IEC |
| Sub-type | E6.2 |
| Suitable for IT Networks | Yes, 690V |
| Certificates and Declarations | |
| ATEX Certificate | No certification needed |
| CSA Certificate | No certification needed |
| CSA Certificate (Intrinsic Safe) | No certification needed |
| Data Sheet, Technical Information | 1SDC200023D0209 |
| Declaration of Conformity - CE | 9AKK106713A5544 |
| EU Data Act Compliance Declaration | 1SDH002560A1001 |
| UL Certificate | No certification needed |
| VDE Certificate | No certification needed |
| Mechanical Drawings | 1SDH001060R0107 |
| Wiring Diagram | 1SDM000091R0001 |
| Instructions and Manuals | 1SDH001000R0002 |
| Instructions and Manuals (Part 2) | 1SDH001316R1002 |
| External Classifications and Standards | |
| ETIM 9 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
| ETIM 10 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
| Object Classification Code | Q |
| WEEE Category | 4. Large Equipment (Any External Dimension More Than 50 cm) |
| eClass | V11.1 : 27370409 |
| Feature Name | Feature Value |
|---|---|
| Rated permanent current Iu (EF001389) | 6300 A |
| Rated voltage (EF003977) | 690 V |
| Rated short-circuit breaking capacity Icu at 400 V, 50 Hz (EF007048) | 150 kA |
| Overload release current setting (EF002336) | 2520.0 A |
| Adjustment range short-term delayed short-circuit release (EF007129) | 3780.0 A |
| Adjustment range undelayed short-circuit release (EF007131) | 9450.0 A |
| Integrated earth fault protection (EF007296) | Yes |
| Type of electrical connection of main circuit (EF006819) | Connection at separate chassis part |
| Device construction (EF008240) | Built-in device slide-in technique (withdrawable) |
| Suitable for DIN rail (top hat rail) mounting (EF007250) | No |
| DIN rail (top hat rail) mounting optional (EF008904) | No |
| Number of auxiliary contacts as normally closed contact (EF001377) | 0 |
| Number of auxiliary contacts as normally open contact (EF001376) | 0 |
| Number of auxiliary contacts as change-over contact (EF003531) | 4 |
| With switched-off indicator (EF007006) | Yes |
| With integrated under voltage release (EF001390) | No |
| Number of poles (EF001391) | 4 |
| Position of connection for main current circuit (EF006671) | Connection at separate chassis part |
| Type of control element (EF006976) | Push button |
| Complete device with protection unit (EF008906) | Yes |
| Motor drive integrated (EF006697) | No |
| Motor drive optional (EF007386) | Yes |
| Degree of protection (IP) (EF005474) | IP30 |