View larger
1SDA073255R1
073255
ABB
1 Pcs.
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
| ABB EcoSolutions | |
|---|---|
| ABB EcoSolutions | Yes |
| ABB Site Meeting Group Waste To Landfill Target | UL 2799 Zero Waste To Landfill Validation available |
| End Of Life Disassembling Instructions | 9AKK108468A2364 |
| Environmental Product Declaration - EPD | 9AKK108468A1905 |
| 9AKK108468A1913 | |
| Extended Product Lifetime | Lifetime Extension Services are Offered |
| Recyclability Rate of the Product acc. to EN45555 | Design for Closing Resource Loops - Standard EN45555 - 77 % |
| Material Compliance | |
| REACH Declaration | 9AKK108466A1425 |
| RoHS Declaration | 9AKK108466A1424 |
| RoHS Information | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
| Conflict Minerals Reporting Template (CMRT) | 9AKK108467A5658 |
| Toxic Substances Control Act - TSCA | 9AKK108467A8326 |
| SCIP | 0baf0357-28ab-4b14-be56-88d91eb451a5 China |
| Simplified SCIP | eb5a73cb-42b4-4be8-85a2-d070cc4e1366 Sweden |
| c58ea548-522f-4914-a039-582b593b1797 Spain | |
| 27ab87dc-80eb-41e2-9cd7-818429cb0d74 France | |
| 6a230a44-f3a5-4d82-a2ca-de3bd3d56cf0 Germany | |
| e6128afd-4192-4e19-a06d-d5cd7943d145 Finland | |
| 0e79e07e-6584-44d0-8b38-ece8613a4cd0 Germany | |
| 6e6d3153-be6f-4754-b681-9752386ce23a France | |
| 9a5504fa-b7ef-47f0-9ac5-1a7f721b3a2d Belgium | |
| 23eea5a2-b6f0-4019-be39-30a7f71636ec Germany | |
| d6014b0e-d190-486a-a2af-6d8404e8d648 Sweden | |
| af5dd2c3-696e-41d9-8590-f6c77c40f87b Estonia | |
| 2caf1309-aa9c-4253-b229-0d52f2974335 Portugal | |
| e0210a14-6d10-46cc-9f55-89679a3a2858 Hungary | |
| 93828b0e-7ac7-4344-a568-dda3144a891e Bulgaria | |
| 68e231d7-6bd2-4cfb-9223-3444c54ff394 Poland | |
| 98d88803-1b5d-4dfe-9a5c-0c0232200c9d Hungary | |
| dcbf106a-11b9-426a-8d7c-7843aea7afda Croatia | |
| bb2402ba-ced2-45fc-b0f2-3ec937625756 Poland | |
| 92fcada8-8e58-4692-b0fe-971a3b07a4e2 Belgium | |
| 1c88dd15-83f2-490f-a7de-3fae8143e260 Greece | |
| 87322091-5bb1-4315-a3dd-8749f3af16ad Germany | |
| 633479af-86fa-4501-9dd5-76aadc345606 Norway | |
| a48e252c-e80a-4310-b8e8-c31f2d337c6a Denmark | |
| 7f4ad097-94a3-4520-b0cf-d9bb26ac9b92 Netherlands | |
| 667f8766-e721-46a9-aecf-542da7daed5a Poland | |
| c0430cf2-93ec-439a-a663-79b2a8afbdf5 Czech Republic | |
| 7ebf296a-6e6f-485a-903e-1e4541ee0b8d Germany | |
| Environmental | |
| Environmental Information | 9AKK108467A6707 |
| Ordering | |
| Order Code US and Canada | ZDVXESAE000A000000XX |
| EAN | 8015644771058 |
| Minimum Order Quantity | 1 piece |
| Customs Tariff Number | 85362090 |
| Dimensions | |
| Product Net Width | 929 mm |
| Product Net Height | 425 mm |
| Product Net Depth / Length | 383 mm |
| Product Net Weight | 134 kg |
| Container Information | |
| Package Level 1 Units | box 1 piece |
| Package Level 1 Width | 515 mm |
| Package Level 1 Height | 610 mm |
| Package Level 1 Depth / Length | 1127 mm |
| Package Level 1 Gross Weight | 143 kg |
| Package Level 1 EAN | 8015644771058 |
| Additional Information | |
| Product Main Type | SACE Emax 2 |
| Product Name | Air Circuit Breaker |
| Product Type | Air Circuit Breaker |
| Version | W |
| CAD Dimensional Drawing | 1SDH001252R0289 |
| Technical | |
| Connecting Capacity | 5000 mm² |
| Current Type | AC |
| Electrical Durability | Ue =< 440 V 3000 cycle |
| Ue = 500 ... 690 V 2000 cycle | |
| 10 cycles per hour | |
| Mechanical Durability | 12000 cycle |
| 60 cycles per hour | |
| Neutral Pole Current ([%Iu]) | 50 % |
| Number of Poles | 4P |
| Power Loss | 850 W |
| Rated Current (In) | 5000 A |
| Rated Impulse Withstand Voltage (Uimp) | acc. to IEC 60947-2 12 kV |
| Rated Insulation Voltage (Ui) | AC 1000 V |
| Rated Operational Voltage | 690 V AC |
| Rated Service Short-Circuit Breaking Capacity (Ics) | (220 V AC) 150 kA |
| (230 V AC) 150 kA | |
| (380 V AC) 150 kA | |
| (400 V AC) 150 kA | |
| (415 V AC) 150 kA | |
| (440 V AC) 150 kA | |
| (500 V AC) 130 kA | |
| (660 V AC) 100 kA | |
| (690 V AC) 100 kA | |
| Rated Service Short-Circuit Breaking Capacity, in % of Icu (Ics) | 100 % |
| Rated Short-time Withstand Current Low Voltage (Icw) | for 1 s 100 kA |
| for 3 s 100 kA | |
| Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (400 V AC) 150 kA |
| (415 V AC) 150 kA | |
| (440 V AC) 150 kA | |
| (500 V AC) 130 kA | |
| (525 V AC) 130 kA | |
| (690 V AC) 100 kA | |
| Rated Uninterrupted Current (Iu) | 5000 A |
| Rated Voltage (Ur) | 690 V |
| Recommended Screw Driver | M12 |
| Release | Ekip Touch LSI |
| Release Type | EL |
| Short-Circuit Performance Level | V |
| Standards | IEC |
| Sub-type | E6.2 |
| Suitable for IT Networks | Yes, 690V |
| Certificates and Declarations | |
| ATEX Certificate | No certification needed |
| CSA Certificate | No certification needed |
| CSA Certificate (Intrinsic Safe) | No certification needed |
| Data Sheet, Technical Information | 1SDC200023D0209 |
| Declaration of Conformity - CE | 9AKK106713A5544 |
| EU Data Act Compliance Declaration | 1SDH002560A1001 |
| UL Certificate | No certification needed |
| VDE Certificate | No certification needed |
| Mechanical Drawings | 1SDH001060R0105 |
| Wiring Diagram | 1SDM000091R0001 |
| Instructions and Manuals | 1SDH001000R0002 |
| Instructions and Manuals (Part 2) | 1SDH001316R1002 |
| External Classifications and Standards | |
| ETIM 9 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
| ETIM 10 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
| Object Classification Code | Q |
| WEEE Category | 4. Large Equipment (Any External Dimension More Than 50 cm) |
| eClass | V11.1 : 27370409 |
| Feature Name | Feature Value |
|---|---|
| Rated permanent current Iu (EF001389) | 5000 A |
| Rated voltage (EF003977) | 690 V |
| Rated short-circuit breaking capacity Icu at 400 V, 50 Hz (EF007048) | 150 kA |
| Overload release current setting (EF002336) | 2000.0 A |
| Adjustment range short-term delayed short-circuit release (EF007129) | 3000.0 A |
| Adjustment range undelayed short-circuit release (EF007131) | 7500.0 A |
| Integrated earth fault protection (EF007296) | No |
| Type of electrical connection of main circuit (EF006819) | Connection at separate chassis part |
| Device construction (EF008240) | Built-in device slide-in technique (withdrawable) |
| Suitable for DIN rail (top hat rail) mounting (EF007250) | No |
| DIN rail (top hat rail) mounting optional (EF008904) | No |
| Number of auxiliary contacts as normally closed contact (EF001377) | 0 |
| Number of auxiliary contacts as normally open contact (EF001376) | 0 |
| Number of auxiliary contacts as change-over contact (EF003531) | 4 |
| With switched-off indicator (EF007006) | Yes |
| With integrated under voltage release (EF001390) | No |
| Number of poles (EF001391) | 4 |
| Position of connection for main current circuit (EF006671) | Connection at separate chassis part |
| Type of control element (EF006976) | Push button |
| Complete device with protection unit (EF008906) | Yes |
| Motor drive integrated (EF006697) | No |
| Motor drive optional (EF007386) | Yes |
| Degree of protection (IP) (EF005474) | IP30 |