View larger
1SDA073260R1 ABB E6.2V 5000 Ekip G Hi-Touch LSIG 4p WMP
1SDA073260R1
073260
ABB
1 Pcs.
Automation > Power circuit-breaker for trafo/generator/installation protection
E6.2
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Abb 1SDA073260R1 circuit-breaker is a high-performance air circuit breaker featuring advanced digital tripping intelligence for critical industrial electrical networks. Premium circuit breakers of this type ensure precise protection coordination, energy monitoring, and reliable interruption of extreme fault currents. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- ABB EcoSolutions: Yes
- ABB Site Meeting Group Waste To Landfill Target: UL 2799 Zero Waste To Landfill Validation available
- End Of Life Disassembling Instructions: 9AKK108468A2364
- Environmental Product Declaration - EPD: 9AKK108468A1905
- Recyclability Rate of the Product acc. to EN45555: Design for Closing Resource Loops - Standard EN45555 - 77 %
- REACH Declaration: 9AKK108466A1425
- RoHS Declaration: 9AKK108466A1424
- RoHS Information: Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
- Conflict Minerals Reporting Template (CMRT): 9AKK108467A5658
- Toxic Substances Control Act - TSCA: 9AKK108467A8326
- Environmental Information: 9AKK108467A6707
- Order Code US and Canada: ZDVXESAQ200A000000XX
- EAN: 8015644771102
- Minimum Order Quantity: 1 piece
- Customs Tariff Number: 85362090
- Product Net Width: 929 mm
More info
▲| ABB EcoSolutions | |
|---|---|
| ABB EcoSolutions | Yes |
| ABB Site Meeting Group Waste To Landfill Target | UL 2799 Zero Waste To Landfill Validation available |
| End Of Life Disassembling Instructions | 9AKK108468A2364 |
| Environmental Product Declaration - EPD | 9AKK108468A1905 |
| 9AKK108468A1913 | |
| Recyclability Rate of the Product acc. to EN45555 | Design for Closing Resource Loops - Standard EN45555 - 77 % |
| Material Compliance | |
| REACH Declaration | 9AKK108466A1425 |
| RoHS Declaration | 9AKK108466A1424 |
| RoHS Information | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
| Conflict Minerals Reporting Template (CMRT) | 9AKK108467A5658 |
| Toxic Substances Control Act - TSCA | 9AKK108467A8326 |
| Environmental | |
| Environmental Information | 9AKK108467A6707 |
| Ordering | |
| Order Code US and Canada | ZDVXESAQ200A000000XX |
| EAN | 8015644771102 |
| Minimum Order Quantity | 1 piece |
| Customs Tariff Number | 85362090 |
| Dimensions | |
| Product Net Width | 929 mm |
| Product Net Height | 425 mm |
| Product Net Depth / Length | 383 mm |
| Product Net Weight | 134 kg |
| Container Information | |
| Package Level 1 Units | box 1 piece |
| Package Level 1 Width | 515 mm |
| Package Level 1 Height | 610 mm |
| Package Level 1 Depth / Length | 1127 mm |
| Package Level 1 Gross Weight | 143 kg |
| Package Level 1 EAN | 8015644771102 |
| Additional Information | |
| Product Main Type | SACE Emax 2 |
| Product Name | Air Circuit Breaker |
| Product Type | Air Circuit Breaker |
| Version | W |
| Technical | |
| Current Type | AC |
| Electrical Durability | Ue =< 440 V 3000 cycle |
| Ue = 500 ... 690 V 2000 cycle | |
| 10 cycles per hour | |
| Mechanical Durability | 12000 cycle |
| 60 cycles per hour | |
| Neutral Pole Current ([%Iu]) | 50 % |
| Number of Poles | 4P |
| Power Loss | 850 W |
| Rated Current (In) | 5000 A |
| Rated Impulse Withstand Voltage (Uimp) | acc. to IEC 60947-2 12 kV |
| Rated Insulation Voltage (Ui) | AC 1000 V |
| Rated Operational Voltage | 690 V AC |
| Rated Service Short-Circuit Breaking Capacity (Ics) | (220 V AC) 150 kA |
| (230 V AC) 150 kA | |
| (380 V AC) 150 kA | |
| (400 V AC) 150 kA | |
| (415 V AC) 150 kA | |
| (440 V AC) 150 kA | |
| (500 V AC) 130 kA | |
| (660 V AC) 100 kA | |
| (690 V AC) 100 kA | |
| Rated Service Short-Circuit Breaking Capacity, in % of Icu (Ics) | 100 % |
| Rated Short-time Withstand Current Low Voltage (Icw) | for 1 s 100 kA |
| for 3 s 100 kA | |
| Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (400 V AC) 150 kA |
| (415 V AC) 150 kA | |
| (440 V AC) 150 kA | |
| (500 V AC) 130 kA | |
| (525 V AC) 130 kA | |
| (690 V AC) 100 kA | |
| Rated Uninterrupted Current (Iu) | 5000 A |
| Rated Voltage (Ur) | 690 V |
| Release | Ekip G Hi-Touch LSIG |
| Release Type | EL |
| Short-Circuit Performance Level | V |
| Standards | IEC |
| Sub-type | E6.2 |
| Suitable for IT Networks | Yes, 690V |
| Certificates and Declarations | |
| Data Sheet, Technical Information | 1SDC200023D0209 |
| Declaration of Conformity - CE | 9AKK106713A5544 |
| Instructions and Manuals | 1SDH001000R0002 |
| Instructions and Manuals (Part 2) | 1SDH001316R1002 |
| External Classifications and Standards | |
| ETIM 9 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
| ETIM 10 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
| Object Classification Code | Q |
| WEEE Category | 4. Large Equipment (Any External Dimension More Than 50 cm) |
| eClass | V11.1 : 27370409 |