View larger
1SDA072013R1
072013
ABB
1 Pcs.
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
| ABB EcoSolutions | |
|---|---|
| ABB EcoSolutions | Yes |
| ABB Site Meeting Group Waste To Landfill Target | UL 2799 Zero Waste To Landfill Validation available |
| End Of Life Disassembling Instructions | 9AKK108468A2364 |
| Environmental Product Declaration - EPD | 9AKK108468A1905 |
| 9AKK108468A1913 | |
| Extended Product Lifetime | Lifetime Extension Services are Offered |
| Recyclability Rate of the Product acc. to EN45555 | Design for Closing Resource Loops - Standard EN45555 - 77 % |
| Material Compliance | |
| REACH Declaration | 9AKK108466A1425 |
| RoHS Declaration | 9AKK108466A1424 |
| RoHS Information | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
| Conflict Minerals Reporting Template (CMRT) | 9AKK108467A5658 |
| Toxic Substances Control Act - TSCA | 9AKK108467A8326 |
| SCIP | 28531790-77e7-4890-a207-df820df71a97 Italy |
| Simplified SCIP | 61288aa1-04d7-47c0-8989-17bd2c192ffd Germany |
| d33b860f-d6af-40d3-bef6-f0a93ba0f558 Estonia | |
| 5348fc7e-dcc1-4053-b100-63db12ef109b Portugal | |
| 07dc02e9-a15f-4d46-9f5f-4bba0dc72eb2 Greece | |
| 50d35fa0-0d2d-4389-b24b-fb7dc2260f0b Bulgaria | |
| 6a722696-e38d-4e34-a681-47a3c1a8d297 Denmark | |
| e328bfd0-a998-490b-8f45-31cad1cef2e9 Sweden | |
| 9c4c3e1d-5fa2-4d08-867c-346fb308a28d Hungary | |
| fe2a9491-8242-48fa-9e92-d84bbbb30668 Croatia | |
| cf010c20-846e-47a0-838d-f302c7c86f8a Norway | |
| 749cd6b0-7a40-4dec-b514-efcef753422e Poland | |
| 112126f2-9fb5-450b-aeff-9182bd47699b Poland | |
| b130ece8-ba0d-4dd6-8bf0-4cbaffc2bd84 Germany | |
| 570a948e-5415-42aa-8171-1a288889c1d9 Belgium | |
| 0e8a6f37-e147-419f-a8ff-6ad5cf30b34f Spain | |
| 532814f0-cfd3-4606-8b79-0cdff7db30ef Netherlands | |
| 1d0c2fd6-9238-4e75-ab3e-e6b66b900e8f Poland | |
| f63192a9-c318-4ab8-9793-aa9189dcbaad France | |
| a20edafc-d67d-4715-b6fe-611347e62e4a Hungary | |
| 0430bfa8-2a7e-4eca-9edb-f45808046e88 Germany | |
| 79faef03-ef0f-4cd5-96f5-7ce592c6059f Germany | |
| b19ef202-11c0-4925-b8b2-5313f89b5b7d Germany | |
| 311ef112-30d1-46b1-90bd-f845e6807279 Belgium | |
| d6669569-09db-432f-84c7-271cc317a5fa Czech Republic | |
| d91330c3-0907-4d38-83c0-37de6639eb4f Finland | |
| baa64022-43c8-461b-b581-749a64477224 France | |
| 4d4a6d6b-8b81-415f-a60e-0c0e2669d1a0 Sweden | |
| Environmental | |
| Environmental Information | 9AKK108467A6707 |
| Ordering | |
| Order Code US and Canada | ZEHYETBC000A000000XX |
| EAN | 8015644758639 |
| Minimum Order Quantity | 1 piece |
| Customs Tariff Number | 85362090 |
| Dimensions | |
| Product Net Width | 1014 mm |
| Product Net Height | 371 mm |
| Product Net Depth / Length | 270 mm |
| Product Net Weight | 140 kg |
| Container Information | |
| Package Level 1 Units | box 1 piece |
| Package Level 1 Width | 515 mm |
| Package Level 1 Height | 610 mm |
| Package Level 1 Depth / Length | 1257 mm |
| Package Level 1 Gross Weight | 151 kg |
| Package Level 1 EAN | 8015644758639 |
| Additional Information | |
| Product Main Type | SACE Emax 2 |
| Product Name | Air Circuit Breaker |
| Product Type | Air Circuit Breaker |
| Version | F |
| CAD Dimensional Drawing | 1SDH001252R0250 |
| Technical | |
| Connecting Capacity | 6000 mm² |
| Current Type | AC |
| Electrical Durability | Ue =< 440 V 2000 cycle |
| Ue = 500 ... 690 V 2000 cycle | |
| 10 cycles per hour | |
| Mechanical Durability | 12000 cycle |
| 60 cycles per hour | |
| Neutral Pole Current ([%Iu]) | 100 % |
| Number of Poles | 4 / f |
| Power Loss | 767 W |
| Rated Current (In) | 6300 A |
| Rated Impulse Withstand Voltage (Uimp) | acc. to IEC 60947-2 12 kV |
| Rated Insulation Voltage (Ui) | AC 1000 V |
| Rated Operational Voltage | 690 V AC |
| Rated Service Short-Circuit Breaking Capacity (Ics) | (220 V AC) 100 kA |
| (230 V AC) 100 kA | |
| (380 V AC) 100 kA | |
| (400 V AC) 100 kA | |
| (415 V AC) 100 kA | |
| (440 V AC) 100 kA | |
| (500 V AC) 100 kA | |
| (660 V AC) 100 kA | |
| (690 V AC) 100 kA | |
| Rated Service Short-Circuit Breaking Capacity, in % of Icu (Ics) | 100 % |
| Rated Short-time Withstand Current Low Voltage (Icw) | for 1 s 100 kA |
| for 3 s 100 kA | |
| Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (400 V AC) 100 kA |
| (415 V AC) 100 kA | |
| (440 V AC) 100 kA | |
| (500 V AC) 100 kA | |
| (525 V AC) 100 kA | |
| (690 V AC) 100 kA | |
| Rated Uninterrupted Current (Iu) | 6300 A |
| Rated Voltage (Ur) | 690 V |
| Recommended Screw Driver | M12 |
| Release | Ekip Dip LSIG |
| Release Type | EL |
| Short-Circuit Performance Level | H |
| Standards | IEC |
| Sub-type | E6.2 |
| Suitable for IT Networks | Yes, 690V |
| Terminal Connection Type | Rear flat Horizontal |
| Terminal Type | Bolt |
| Tightening Torque | 70 N·m |
| Certificates and Declarations | |
| ATEX Certificate | No certification needed |
| CSA Certificate | No certification needed |
| CSA Certificate (Intrinsic Safe) | No certification needed |
| Data Sheet, Technical Information | 1SDC200023D0209 |
| Declaration of Conformity - CE | 9AKK106713A5544 |
| EU Data Act Compliance Declaration | 1SDH002560A1001 |
| UL Certificate | No certification needed |
| VDE Certificate | No certification needed |
| Mechanical Drawings | 1SDH001060R0102 |
| Wiring Diagram | 1SDM000091R0001 |
| Instructions and Manuals | 1SDH001000R0002 |
| External Classifications and Standards | |
| ETIM 9 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
| ETIM 10 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
| Object Classification Code | Q |
| WEEE Category | 4. Large Equipment (Any External Dimension More Than 50 cm) |
| eClass | V11.1 : 27370409 |
| Feature Name | Feature Value |
|---|---|
| Rated permanent current Iu (EF001389) | 6300 A |
| Rated voltage (EF003977) | 690 V |
| Rated short-circuit breaking capacity Icu at 400 V, 50 Hz (EF007048) | 100 kA |
| Overload release current setting (EF002336) | 2520.0 A |
| Adjustment range short-term delayed short-circuit release (EF007129) | 3780.0 A |
| Adjustment range undelayed short-circuit release (EF007131) | 9450.0 A |
| Integrated earth fault protection (EF007296) | Yes |
| Type of electrical connection of main circuit (EF006819) | Bolt connection |
| Device construction (EF008240) | Built-in device fixed built-in technique |
| Suitable for DIN rail (top hat rail) mounting (EF007250) | No |
| DIN rail (top hat rail) mounting optional (EF008904) | No |
| Number of auxiliary contacts as normally closed contact (EF001377) | 0 |
| Number of auxiliary contacts as normally open contact (EF001376) | 0 |
| Number of auxiliary contacts as change-over contact (EF003531) | 4 |
| With switched-off indicator (EF007006) | Yes |
| With integrated under voltage release (EF001390) | No |
| Number of poles (EF001391) | 4 |
| Position of connection for main current circuit (EF006671) | Back |
| Type of control element (EF006976) | Push button |
| Complete device with protection unit (EF008906) | Yes |
| Motor drive integrated (EF006697) | No |
| Motor drive optional (EF007386) | Yes |
| Degree of protection (IP) (EF005474) | IP30 |