View larger
1SDA071298R1
071298
ABB
1 Pcs.
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
| ABB EcoSolutions | |
|---|---|
| ABB EcoSolutions | Yes |
| ABB Site Meeting Group Waste To Landfill Target | UL 2799 Zero Waste To Landfill Validation available |
| End Of Life Disassembling Instructions | 9AKK108468A2364 |
| Environmental Product Declaration - EPD | 9AKK108468A1905 |
| 9AKK108468A1913 | |
| Extended Product Lifetime | Lifetime Extension Services are Offered |
| Recyclability Rate of the Product acc. to EN45555 | Design for Closing Resource Loops - Standard EN45555 - 77 % |
| Material Compliance | |
| REACH Declaration | 9AKK108466A1425 |
| RoHS Declaration | 9AKK108466A1424 |
| RoHS Information | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
| Conflict Minerals Reporting Template (CMRT) | 9AKK108467A5658 |
| Toxic Substances Control Act - TSCA | 9AKK108467A8326 |
| SCIP | fa293613-5289-4323-992b-fc179ece25bc Italy |
| Simplified SCIP | 24f3e458-292b-4b28-abba-229e3b698125 Germany |
| 4a35c4d8-f0cb-4873-a676-f035505cfcc3 Hungary | |
| a0af51c8-04ee-4160-a8d5-dd21c760d2ae Belgium | |
| 8f6a7baf-1f58-40b6-b1d7-dec57f860ec9 Spain | |
| eb8d5c5e-7643-4601-b4a8-b3344a28af41 Germany | |
| ae2c524a-98a7-4405-9816-76b6aa467c38 Germany | |
| 5478c353-f26e-4ff9-a3f8-4cff847640ef Croatia | |
| 9a5c5a5c-cad0-41fe-a749-48a5c983efaa Bulgaria | |
| ad6fb889-5f29-4611-9d43-edc609981dcd France | |
| a38dd5b6-6049-4f83-b68e-fd067679613b Sweden | |
| deb5017d-cd9d-4706-9156-c0b0a456c62d Belgium | |
| 26287913-5cc1-4e91-b8dd-ee80a4d32d96 Estonia | |
| aec9a7e7-b78c-42ce-99cc-d1ef57532cd7 Netherlands | |
| 6530e613-8151-4076-acc9-03040dbc6c81 Finland | |
| 379383bd-ec0d-4ab7-b5eb-eeea3398f209 France | |
| 4910da71-fb49-41f2-83a7-83b81f54325d Greece | |
| b69134df-cc20-4e66-84df-8f06eb09370a Germany | |
| e0631034-64a1-4bb0-8227-8b69b757fddd Denmark | |
| 52744f5d-44ee-49a1-a017-763d2ce2a90a Germany | |
| 2e55ddb1-0760-467f-bb93-bdcbb9fd122e Hungary | |
| 03bcc6ac-df4c-4980-a56d-f919cc63a7aa Poland | |
| c4810516-40d5-4860-91c1-f9c583883500 Norway | |
| d6b1e513-0939-4e0e-8245-45882a820f5b Poland | |
| bc597603-a7ef-4463-8711-b906ffc2dfde Poland | |
| 75645da3-15d8-4e7e-abbf-94d2d00bf177 Czech Republic | |
| 6c5f903b-ef1d-4913-b7d0-d9740977e879 Portugal | |
| 371ca3d8-ce3b-404c-ae49-55c6db710fa3 Sweden | |
| Environmental | |
| Environmental Information | 9AKK108467A6707 |
| Ordering | |
| Order Code US and Canada | Z6HYETBJ200A000000XX |
| EAN | 8015644751487 |
| Minimum Order Quantity | 1 piece |
| Customs Tariff Number | 85362090 |
| Dimensions | |
| Product Net Width | 762 mm |
| Product Net Height | 371 mm |
| Product Net Depth / Length | 270 mm |
| Product Net Weight | 109 kg |
| Container Information | |
| Package Level 1 Units | box 1 piece |
| Package Level 1 Width | 515 mm |
| Package Level 1 Height | 610 mm |
| Package Level 1 Depth / Length | 1000 mm |
| Package Level 1 Gross Weight | 118 kg |
| Package Level 1 EAN | 8015644751487 |
| Additional Information | |
| Product Main Type | SACE Emax 2 |
| Product Name | Air Circuit Breaker |
| Product Type | Air Circuit Breaker |
| Version | F |
| CAD Dimensional Drawing | 1SDH001252R0223 |
| Technical | |
| Connecting Capacity | 6000 mm² |
| Current Type | AC |
| Electrical Durability | Ue =< 440 V 2000 cycle |
| Ue = 500 ... 690 V 2000 cycle | |
| 10 cycles per hour | |
| Mechanical Durability | 12000 cycle |
| 60 cycles per hour | |
| Number of Poles | 3P |
| Power Loss | 767 W |
| Rated Current (In) | 6300 A |
| Rated Impulse Withstand Voltage (Uimp) | acc. to IEC 60947-2 12 kV |
| Rated Insulation Voltage (Ui) | AC 1000 V |
| Rated Operational Voltage | 690 V AC |
| Rated Service Short-Circuit Breaking Capacity (Ics) | (220 V AC) 100 kA |
| (230 V AC) 100 kA | |
| (380 V AC) 100 kA | |
| (400 V AC) 100 kA | |
| (415 V AC) 100 kA | |
| (440 V AC) 100 kA | |
| (500 V AC) 100 kA | |
| (660 V AC) 100 kA | |
| (690 V AC) 100 kA | |
| Rated Service Short-Circuit Breaking Capacity, in % of Icu (Ics) | 100 % |
| Rated Short-time Withstand Current Low Voltage (Icw) | for 1 s 100 kA |
| for 3 s 100 kA | |
| Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (400 V AC) 100 kA |
| (415 V AC) 100 kA | |
| (440 V AC) 100 kA | |
| (500 V AC) 100 kA | |
| (525 V AC) 100 kA | |
| (690 V AC) 100 kA | |
| Rated Uninterrupted Current (Iu) | 6300 A |
| Rated Voltage (Ur) | 690 V |
| Recommended Screw Driver | M12 |
| Release | Ekip Hi-Touch LSI |
| Release Type | EL |
| Short-Circuit Performance Level | H |
| Standards | IEC |
| Sub-type | E6.2 |
| Suitable for IT Networks | Yes, 690V |
| Terminal Connection Type | Rear flat Horizontal |
| Terminal Type | Bolt |
| Tightening Torque | 70 N·m |
| Certificates and Declarations | |
| ATEX Certificate | No certification needed |
| CSA Certificate | No certification needed |
| CSA Certificate (Intrinsic Safe) | No certification needed |
| Data Sheet, Technical Information | 1SDC200023D0209 |
| Declaration of Conformity - CE | 9AKK106713A5544 |
| EU Data Act Compliance Declaration | 1SDH002560A1001 |
| UL Certificate | No certification needed |
| VDE Certificate | No certification needed |
| Mechanical Drawings | 1SDH001060R0100 |
| Wiring Diagram | 1SDM000091R0001 |
| Instructions and Manuals | 1SDH001000R0002 |
| Instructions and Manuals (Part 2) | 1SDH001316R1002 |
| External Classifications and Standards | |
| ETIM 9 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
| ETIM 10 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
| IDEA Granular Category Code (IGCC) | 4926 >> Air circuit breakers |
| Object Classification Code | Q |
| UNSPSC | 39121615 |
| WEEE Category | 4. Large Equipment (Any External Dimension More Than 50 cm) |
| eClass | V11.1 : 27370409 |
| Feature Name | Feature Value |
|---|---|
| Rated permanent current Iu (EF001389) | 6300 A |
| Rated voltage (EF003977) | 690 V |
| Rated short-circuit breaking capacity Icu at 400 V, 50 Hz (EF007048) | 100 kA |
| Overload release current setting (EF002336) | 2520.0 A |
| Adjustment range short-term delayed short-circuit release (EF007129) | 3780.0 A |
| Adjustment range undelayed short-circuit release (EF007131) | 9450.0 A |
| Integrated earth fault protection (EF007296) | No |
| Type of electrical connection of main circuit (EF006819) | Bolt connection |
| Device construction (EF008240) | Built-in device fixed built-in technique |
| Suitable for DIN rail (top hat rail) mounting (EF007250) | No |
| DIN rail (top hat rail) mounting optional (EF008904) | No |
| Number of auxiliary contacts as normally closed contact (EF001377) | 0 |
| Number of auxiliary contacts as normally open contact (EF001376) | 0 |
| Number of auxiliary contacts as change-over contact (EF003531) | 4 |
| With switched-off indicator (EF007006) | Yes |
| With integrated under voltage release (EF001390) | No |
| Number of poles (EF001391) | 3 |
| Position of connection for main current circuit (EF006671) | Back |
| Type of control element (EF006976) | Push button |
| Complete device with protection unit (EF008906) | Yes |
| Motor drive integrated (EF006697) | No |
| Motor drive optional (EF007386) | Yes |
| Degree of protection (IP) (EF005474) | IP30 |