View larger
1SDA071232R1
071232
ABB
1 Pcs.
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
| ABB EcoSolutions | |
|---|---|
| ABB EcoSolutions | Yes |
| ABB Site Meeting Group Waste To Landfill Target | UL 2799 Zero Waste To Landfill Validation available |
| End Of Life Disassembling Instructions | 9AKK108468A2364 |
| Environmental Product Declaration - EPD | 9AKK108468A1905 |
| 9AKK108468A1913 | |
| Extended Product Lifetime | Lifetime Extension Services are Offered |
| Recyclability Rate of the Product acc. to EN45555 | Design for Closing Resource Loops - Standard EN45555 - 77 % |
| Material Compliance | |
| REACH Declaration | 9AKK108466A1425 |
| RoHS Declaration | 9AKK108466A1424 |
| RoHS Information | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
| Conflict Minerals Reporting Template (CMRT) | 9AKK108467A5658 |
| Toxic Substances Control Act - TSCA | 9AKK108467A8326 |
| SCIP | d4b5bee0-bab4-471b-b9e8-051924f12b84 Italy |
| Simplified SCIP | 1f414b97-1c37-4c25-ab44-e73979ccf53d Germany |
| e2179a60-2260-4da4-9dc0-8f716e003cc0 Hungary | |
| 40de4732-6e24-46ab-a832-c4566f71dae6 Belgium | |
| d635757d-b306-4956-b6e7-5ac0dc93021d Spain | |
| f00eb3ab-dc45-4ab3-a7aa-0afff70714e8 Hungary | |
| 848153f5-7be5-4cef-96db-0a4d6ee70858 Norway | |
| c4ece108-a8f4-4c4f-8a6e-49438238ff8f Poland | |
| 4e718dc2-175e-4241-abbe-008c998bc095 Netherlands | |
| ab53797e-b6e3-44a6-8012-2efa88245139 Finland | |
| e2421c7b-45e1-4a26-82c0-bced7ba58acb France | |
| d2945fc2-a21c-403e-b485-14fd5a56d518 Greece | |
| fb30cd32-04da-456e-9ecc-c258d343d70d Estonia | |
| aeaabd89-3088-4c8f-ace2-80a491cfb813 Sweden | |
| 224d2bfd-62a4-45d1-8759-afbc4f6e560d Bulgaria | |
| 64cc669c-a989-415f-ac1b-43f85ad8bfea Belgium | |
| e94e13de-0c65-4137-b5bf-4deb339624f1 Germany | |
| d8e31e5a-38d8-42a8-87a0-3b58fb396bb5 Germany | |
| 973cfe40-f71a-406e-9caa-2687b0f68180 Denmark | |
| bf364294-ea83-43aa-82cf-67f999ea569c Germany | |
| bdd1e786-ac5e-40d9-bbf4-0352038754ff Germany | |
| e5109047-1291-4ede-999b-378131dcd1f9 Croatia | |
| e7abfa83-550d-4aed-a747-860fe636ec66 France | |
| b17eb08c-c7d0-4cf4-a7e4-8f3495e32774 Portugal | |
| 63834391-83e0-4c2d-bc53-cabf79b03029 Sweden | |
| ae63b4b8-0fae-4626-ab49-dd4d25d9bb27 Poland | |
| c51e6316-300a-4b4a-ba6d-eb138939bc46 Poland | |
| 06ebf9d1-d958-4fe1-ad9c-36c15bdc9bb0 Czech Republic | |
| Environmental | |
| Environmental Information | 9AKK108467A6707 |
| Ordering | |
| Order Code US and Canada | Z6HWERBB000A000000XX |
| EAN | 8015644750824 |
| Minimum Order Quantity | 1 piece |
| Customs Tariff Number | 85362090 |
| Dimensions | |
| Product Net Width | 762 mm |
| Product Net Height | 371 mm |
| Product Net Depth / Length | 270 mm |
| Product Net Weight | 109 kg |
| Container Information | |
| Package Level 1 Units | box 1 piece |
| Package Level 1 Width | 515 mm |
| Package Level 1 Height | 610 mm |
| Package Level 1 Depth / Length | 1000 mm |
| Package Level 1 Gross Weight | 118 kg |
| Package Level 1 EAN | 8015644750824 |
| Additional Information | |
| Product Main Type | SACE Emax 2 |
| Product Name | Air Circuit Breaker |
| Product Type | Air Circuit Breaker |
| Version | F |
| CAD Dimensional Drawing | 1SDH001252R0223 |
| Technical | |
| Connecting Capacity | 4000 mm² |
| Current Type | AC |
| Electrical Durability | Ue =< 440 V 4000 cycle |
| Ue = 500 ... 690 V 4000 cycle | |
| 10 cycles per hour | |
| Mechanical Durability | 12000 cycle |
| 60 cycles per hour | |
| Number of Poles | 3P |
| Power Loss | 309 W |
| Rated Current (In) | 4000 A |
| Rated Impulse Withstand Voltage (Uimp) | acc. to IEC 60947-2 12 kV |
| Rated Insulation Voltage (Ui) | AC 1000 V |
| Rated Operational Voltage | 690 V AC |
| Rated Service Short-Circuit Breaking Capacity (Ics) | (220 V AC) 100 kA |
| (230 V AC) 100 kA | |
| (380 V AC) 100 kA | |
| (400 V AC) 100 kA | |
| (415 V AC) 100 kA | |
| (440 V AC) 100 kA | |
| (500 V AC) 100 kA | |
| (660 V AC) 100 kA | |
| (690 V AC) 100 kA | |
| Rated Service Short-Circuit Breaking Capacity, in % of Icu (Ics) | 100 % |
| Rated Short-time Withstand Current Low Voltage (Icw) | for 1 s 100 kA |
| for 3 s 100 kA | |
| Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (400 V AC) 100 kA |
| (415 V AC) 100 kA | |
| (440 V AC) 100 kA | |
| (500 V AC) 100 kA | |
| (525 V AC) 100 kA | |
| (690 V AC) 100 kA | |
| Rated Uninterrupted Current (Iu) | 4000 A |
| Rated Voltage (Ur) | 690 V |
| Recommended Screw Driver | M12 |
| Release | Ekip Dip LSI |
| Release Type | EL |
| Short-Circuit Performance Level | H |
| Standards | IEC |
| Sub-type | E6.2 |
| Suitable for IT Networks | Yes, 690V |
| Terminal Connection Type | Rear flat Horizontal |
| Terminal Type | Bolt |
| Tightening Torque | 70 N·m |
| Certificates and Declarations | |
| ATEX Certificate | No certification needed |
| CSA Certificate | No certification needed |
| CSA Certificate (Intrinsic Safe) | No certification needed |
| Data Sheet, Technical Information | 1SDC200023D0209 |
| Declaration of Conformity - CE | 9AKK106713A5544 |
| EU Data Act Compliance Declaration | 1SDH002560A1001 |
| UL Certificate | No certification needed |
| VDE Certificate | No certification needed |
| Mechanical Drawings | 1SDH001060R0100 |
| Wiring Diagram | 1SDM000091R0001 |
| Instructions and Manuals | 1SDH001000R0002 |
| External Classifications and Standards | |
| ETIM 9 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
| ETIM 10 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
| IDEA Granular Category Code (IGCC) | 4926 >> Air circuit breakers |
| Object Classification Code | Q |
| UNSPSC | 39121615 |
| WEEE Category | 4. Large Equipment (Any External Dimension More Than 50 cm) |
| eClass | V11.1 : 27370409 |
| Feature Name | Feature Value |
|---|---|
| Rated permanent current Iu (EF001389) | 4000 A |
| Rated voltage (EF003977) | 690 V |
| Rated short-circuit breaking capacity Icu at 400 V, 50 Hz (EF007048) | 100 kA |
| Overload release current setting (EF002336) | 1600.0 A |
| Adjustment range short-term delayed short-circuit release (EF007129) | 2400.0 A |
| Adjustment range undelayed short-circuit release (EF007131) | 6000.0 A |
| Integrated earth fault protection (EF007296) | No |
| Type of electrical connection of main circuit (EF006819) | Bolt connection |
| Device construction (EF008240) | Built-in device fixed built-in technique |
| Suitable for DIN rail (top hat rail) mounting (EF007250) | No |
| DIN rail (top hat rail) mounting optional (EF008904) | No |
| Number of auxiliary contacts as normally closed contact (EF001377) | 0 |
| Number of auxiliary contacts as normally open contact (EF001376) | 0 |
| Number of auxiliary contacts as change-over contact (EF003531) | 4 |
| With switched-off indicator (EF007006) | Yes |
| With integrated under voltage release (EF001390) | No |
| Number of poles (EF001391) | 3 |
| Position of connection for main current circuit (EF006671) | Back |
| Type of control element (EF006976) | Push button |
| Complete device with protection unit (EF008906) | Yes |
| Motor drive integrated (EF006697) | No |
| Motor drive optional (EF007386) | Yes |
| Degree of protection (IP) (EF005474) | IP30 |