View larger
1SDA073201R1
073201
ABB
1 Pcs.
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
| ABB EcoSolutions | |
|---|---|
| ABB EcoSolutions | Yes |
| ABB Site Meeting Group Waste To Landfill Target | UL 2799 Zero Waste To Landfill Validation available |
| End Of Life Disassembling Instructions | 9AKK108468A2363 |
| Environmental Product Declaration - EPD | 9AKK108468A1904 |
| 9AKK108468A1910 | |
| Extended Product Lifetime | Lifetime Extension Services are Offered |
| Recyclability Rate of the Product acc. to EN45555 | Design for Closing Resource Loops - Standard EN45555 - 79.3 % |
| Material Compliance | |
| REACH Declaration | 9AKK108466A1425 |
| RoHS Declaration | 9AKK108466A1424 |
| RoHS Information | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
| Conflict Minerals Reporting Template (CMRT) | 9AKK108467A5658 |
| Toxic Substances Control Act - TSCA | 9AKK108467A8326 |
| SCIP | c7188295-c5cf-42e7-9494-322e70922654 Italy |
| Simplified SCIP | 8cc6fe3c-54a0-46cf-b4e7-719fb4d0b1d8 Germany |
| 133b4de2-990f-456d-9303-50f8ce48aa96 Estonia | |
| eaa4aad7-01bf-4e71-b8f8-d39020d3ccc0 Greece | |
| 318c3f11-79e3-45b8-aaa3-e5ab11ce9ef2 Portugal | |
| 9f6412eb-0078-445f-8158-941fb91e49f1 Sweden | |
| 65e37805-54fd-42fd-9ee6-3b4fa66ae0e7 Bulgaria | |
| a956b689-6d41-4c5e-9043-8c18a092a7e0 Denmark | |
| ced163b2-1e57-402b-9c0f-0ea683c50aea Hungary | |
| b8962315-f1eb-4780-8dd8-dbdb04b5688b Croatia | |
| c9c6da2a-d185-4a1c-bfec-40af5d77e51d Norway | |
| 9c2bc9a5-8012-47a9-9160-3baef7d47af8 Germany | |
| 5e496ac8-9b35-485f-a889-c306eace62b4 Poland | |
| 743570a9-92a6-4937-8d33-7223bfc40fe5 France | |
| 4318bbab-1f2a-4b87-af5c-9b506c96cecd Poland | |
| 1893db46-1ffb-4608-82fc-cb58b7a6ca8b Spain | |
| f2a0cfcd-2ed9-4aa7-9c44-86c111a4ebef Belgium | |
| 30b17da3-c335-4567-8264-41bf8c4782f2 Poland | |
| edd4189e-20d7-4a58-8eee-8cb5ac3f3c98 Netherlands | |
| bd74afd8-773c-49c9-9880-a0155acd4e13 France | |
| 3a6e4619-bb15-481a-b851-c65420916c07 Hungary | |
| a5ea2c5c-a382-4f42-a65e-08c164b88c86 Germany | |
| 34d2d340-c4a2-4e22-9030-e982d6656a04 Germany | |
| 0863ca59-ca84-4a5f-869f-38c1aa4f314a Germany | |
| b9025b73-a12a-437f-982c-b5c04f4afd1e Sweden | |
| b4541c0d-18e8-4d05-96a4-c8d366f37aaf Finland | |
| 3a6b9b31-fca2-45f7-b165-eea61a1953fe Belgium | |
| fa348c31-52bd-4b17-bdf2-4a4d9cf5403b Czech Republic | |
| Environmental | |
| Environmental Information | 9AKK108467A6707 |
| Ordering | |
| Order Code US and Canada | ZCVWERAA000A000000XX |
| EAN | 8015644770518 |
| Minimum Order Quantity | 1 piece |
| Customs Tariff Number | 85362090 |
| Dimensions | |
| Product Net Width | 551 mm |
| Product Net Height | 425 mm |
| Product Net Depth / Length | 383 mm |
| Product Net Weight | 74 kg |
| Container Information | |
| Package Level 1 Units | box 1 piece |
| Package Level 1 Width | 515 mm |
| Package Level 1 Height | 610 mm |
| Package Level 1 Depth / Length | 785 mm |
| Package Level 1 Gross Weight | 81 kg |
| Package Level 1 EAN | 8015644770518 |
| Additional Information | |
| Product Main Type | SACE Emax 2 |
| Product Name | Air Circuit Breaker |
| Product Type | Air Circuit Breaker |
| Version | W |
| CAD Dimensional Drawing | 1SDH001252R0434 |
| Technical | |
| Connecting Capacity | 4000 mm² |
| Current Type | AC |
| Electrical Durability | Ue =< 440 V 5000 cycle |
| Ue = 500 ... 690 V 4000 cycle | |
| 20 cycles per hour | |
| Mechanical Durability | 15000 cycle |
| 60 cycles per hour | |
| Neutral Pole Current ([%Iu]) | 100 % |
| Number of Poles | 4P |
| Power Loss | 900 W |
| Rated Current (In) | 4000 A |
| Rated Impulse Withstand Voltage (Uimp) | acc. to IEC 60947-2 12 kV |
| Rated Insulation Voltage (Ui) | AC 1000 V |
| Rated Operational Voltage | 690 V AC |
| Rated Service Short-Circuit Breaking Capacity (Ics) | (220 V AC) 150 kA |
| (230 V AC) 150 kA | |
| (380 V AC) 150 kA | |
| (400 V AC) 150 kA | |
| (415 V AC) 150 kA | |
| (440 V AC) 150 kA | |
| (500 V AC) 100 kA | |
| (660 V AC) 100 kA | |
| (690 V AC) 100 kA | |
| Rated Service Short-Circuit Breaking Capacity, in % of Icu (Ics) | 100 % |
| Rated Short-time Withstand Current Low Voltage (Icw) | for 1 s 100 kA |
| for 3 s 75 kA | |
| Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (400 V AC) 150 kA |
| (415 V AC) 150 kA | |
| (440 V AC) 150 kA | |
| (500 V AC) 100 kA | |
| (525 V AC) 100 kA | |
| (690 V AC) 100 kA | |
| Rated Uninterrupted Current (Iu) | 4000 A |
| Rated Voltage (Ur) | 690 V |
| Recommended Screw Driver | M12 |
| Release | Ekip Dip LI |
| Release Type | EL |
| Short-Circuit Performance Level | V |
| Standards | IEC |
| Sub-type | E4.2 |
| Suitable for IT Networks | Yes, 690V |
| Certificates and Declarations | |
| ATEX Certificate | No certification needed |
| CSA Certificate | No certification needed |
| CSA Certificate (Intrinsic Safe) | No certification needed |
| Data Sheet, Technical Information | 1SDC200023D0209 |
| Declaration of Conformity - CE | 9AKK106713A5545 |
| EU Data Act Compliance Declaration | 1SDH002560A1001 |
| UL Certificate | No certification needed |
| VDE Certificate | No certification needed |
| Mechanical Drawings | 1SDH001001R0102 |
| Wiring Diagram | 1SDM000091R0001 |
| Instructions and Manuals | 1SDH001000R0002 |
| External Classifications and Standards | |
| ETIM 9 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
| ETIM 10 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
| Object Classification Code | Q |
| WEEE Category | 4. Large Equipment (Any External Dimension More Than 50 cm) |
| eClass | V11.1 : 27370409 |
| Feature Name | Feature Value |
|---|---|
| Rated permanent current Iu (EF001389) | 4000 A |
| Rated voltage (EF003977) | 690 V |
| Rated short-circuit breaking capacity Icu at 400 V, 50 Hz (EF007048) | 150 kA |
| Overload release current setting (EF002336) | 1600.0 A |
| Adjustment range undelayed short-circuit release (EF007131) | 6000.0 A |
| Integrated earth fault protection (EF007296) | No |
| Type of electrical connection of main circuit (EF006819) | Connection at separate chassis part |
| Device construction (EF008240) | Built-in device slide-in technique (withdrawable) |
| Suitable for DIN rail (top hat rail) mounting (EF007250) | No |
| DIN rail (top hat rail) mounting optional (EF008904) | No |
| Number of auxiliary contacts as normally closed contact (EF001377) | 0 |
| Number of auxiliary contacts as normally open contact (EF001376) | 0 |
| Number of auxiliary contacts as change-over contact (EF003531) | 4 |
| With switched-off indicator (EF007006) | Yes |
| With integrated under voltage release (EF001390) | No |
| Number of poles (EF001391) | 4 |
| Position of connection for main current circuit (EF006671) | Connection at separate chassis part |
| Type of control element (EF006976) | Push button |
| Complete device with protection unit (EF008906) | Yes |
| Motor drive integrated (EF006697) | No |
| Motor drive optional (EF007386) | Yes |
| Degree of protection (IP) (EF005474) | IP30 |