View larger
1SDA073159R1
073159
ABB
1 Pcs.
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
| ABB EcoSolutions | |
|---|---|
| ABB EcoSolutions | Yes |
| ABB Site Meeting Group Waste To Landfill Target | UL 2799 Zero Waste To Landfill Validation available |
| End Of Life Disassembling Instructions | 9AKK108468A2363 |
| Environmental Product Declaration - EPD | 9AKK108468A1904 |
| 9AKK108468A1910 | |
| Extended Product Lifetime | Lifetime Extension Services are Offered |
| Recyclability Rate of the Product acc. to EN45555 | Design for Closing Resource Loops - Standard EN45555 - 79.3 % |
| Material Compliance | |
| REACH Declaration | 9AKK108466A1425 |
| RoHS Declaration | 9AKK108466A1424 |
| RoHS Information | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
| Conflict Minerals Reporting Template (CMRT) | 9AKK108467A5658 |
| Toxic Substances Control Act - TSCA | 9AKK108467A8326 |
| SCIP | 2899687f-d714-43e2-9392-dd6650aa6fa2 Italy |
| Simplified SCIP | ffdb3038-1b57-447c-927c-cb6cb95eab27 Germany |
| b28a766e-79d9-40e0-a9d4-b09cdad31fd3 Belgium | |
| 766b87c6-6351-4d40-8bbb-33b37a734fdd Spain | |
| 6234a8c0-455e-4013-b6c3-b67a3100280b Hungary | |
| 0f0e49f3-15c3-42bc-9ba3-fe536d477610 France | |
| 78c6dea2-259d-444a-920f-39084352f0b1 France | |
| 94afb44f-9c9b-40a4-8ddf-d7387207f7a3 Germany | |
| ec136180-3ad5-45d0-b66e-84c59356346a Croatia | |
| 1718fad2-8e48-4b88-958d-66eb6fd818a3 Greece | |
| 0269d005-62a3-47b1-ad5f-26f630faecbd Germany | |
| c490fe0c-3a77-402a-92df-17e275128046 Denmark | |
| 0354dca2-b792-4225-90e5-364dd1b77b27 Germany | |
| 110e9dbc-44bb-4cfd-9c15-7efc293dd249 Belgium | |
| c558dad7-b489-491b-8eb7-5e795710778e Sweden | |
| 53205403-be57-47f7-8248-c653ab529eab Germany | |
| 31aa078d-3b45-4562-a2a0-ad66724cc5bc Estonia | |
| 2db74f06-d9e6-43ef-9ed6-88befe23c76b Netherlands | |
| 94c4846e-fdd8-4e23-8465-c3bec9f6ba38 Finland | |
| b0ae5d74-a281-4ec5-a235-19823aa89e29 Hungary | |
| b15961a1-694a-4f85-a25e-3a543e0851f9 Norway | |
| 8206c4c2-88db-400b-8911-670b085cc825 Poland | |
| be719604-f6a0-43e2-8ca0-09371f3a002a Czech Republic | |
| 12851088-7736-4300-9f51-71893c1b095f Poland | |
| 60d1363b-1b5e-4f56-811e-201eb8b8dfec Poland | |
| 7cfde1c7-a4e7-4b7a-8501-07dff7fde8ef Bulgaria | |
| 9e6e36dc-46f6-42b4-a2d3-b8f351373a7c Sweden | |
| 0ec8329e-4a2b-4dcf-aa2b-3b3b3c0c8974 Portugal | |
| Environmental | |
| Environmental Information | 9AKK108467A6707 |
| Ordering | |
| Order Code US and Canada | ZCVVENAK200A000000XX |
| EAN | 8015644770099 |
| Minimum Order Quantity | 1 piece |
| Customs Tariff Number | 85362090 |
| Dimensions | |
| Product Net Width | 551 mm |
| Product Net Height | 425 mm |
| Product Net Depth / Length | 383 mm |
| Product Net Weight | 74 kg |
| Container Information | |
| Package Level 1 Units | box 1 piece |
| Package Level 1 Width | 515 mm |
| Package Level 1 Height | 610 mm |
| Package Level 1 Depth / Length | 785 mm |
| Package Level 1 Gross Weight | 81 kg |
| Package Level 1 EAN | 8015644770099 |
| Additional Information | |
| Product Main Type | SACE Emax 2 |
| Product Name | Air Circuit Breaker |
| Product Type | Air Circuit Breaker |
| Version | W |
| CAD Dimensional Drawing | 1SDH001252R0434 |
| Technical | |
| Connecting Capacity | 3000 mm² |
| Current Type | AC |
| Electrical Durability | Ue =< 440 V 7000 cycle |
| Ue = 500 ... 690 V 7000 cycle | |
| 20 cycles per hour | |
| Mechanical Durability | 20000 cycle |
| 60 cycles per hour | |
| Neutral Pole Current ([%Iu]) | 100 % |
| Number of Poles | 4P |
| Power Loss | 743 W |
| Rated Current (In) | 3200 A |
| Rated Impulse Withstand Voltage (Uimp) | acc. to IEC 60947-2 12 kV |
| Rated Insulation Voltage (Ui) | AC 1000 V |
| Rated Operational Voltage | 690 V AC |
| Rated Service Short-Circuit Breaking Capacity (Ics) | (220 V AC) 150 kA |
| (230 V AC) 150 kA | |
| (380 V AC) 150 kA | |
| (400 V AC) 150 kA | |
| (415 V AC) 150 kA | |
| (440 V AC) 150 kA | |
| (500 V AC) 100 kA | |
| (660 V AC) 100 kA | |
| (690 V AC) 100 kA | |
| Rated Service Short-Circuit Breaking Capacity, in % of Icu (Ics) | 100 % |
| Rated Short-time Withstand Current Low Voltage (Icw) | for 1 s 100 kA |
| for 3 s 75 kA | |
| Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (400 V AC) 150 kA |
| (415 V AC) 150 kA | |
| (440 V AC) 150 kA | |
| (500 V AC) 100 kA | |
| (525 V AC) 100 kA | |
| (690 V AC) 100 kA | |
| Rated Uninterrupted Current (Iu) | 3200 A |
| Rated Voltage (Ur) | 690 V |
| Recommended Screw Driver | M12 |
| Release | Ekip Hi-Touch LSIG |
| Release Type | EL |
| Short-Circuit Performance Level | V |
| Standards | IEC |
| Sub-type | E4.2 |
| Suitable for IT Networks | Yes, 690V |
| Certificates and Declarations | |
| ATEX Certificate | No certification needed |
| CSA Certificate | No certification needed |
| CSA Certificate (Intrinsic Safe) | No certification needed |
| Data Sheet, Technical Information | 1SDC200023D0209 |
| Declaration of Conformity - CE | 9AKK106713A5545 |
| EU Data Act Compliance Declaration | 1SDH002560A1001 |
| UL Certificate | No certification needed |
| VDE Certificate | No certification needed |
| Mechanical Drawings | 1SDH001001R0102 |
| Wiring Diagram | 1SDM000091R0001 |
| Instructions and Manuals | 1SDH001000R0002 |
| Instructions and Manuals (Part 2) | 1SDH001316R1002 |
| External Classifications and Standards | |
| ETIM 9 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
| ETIM 10 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
| IDEA Granular Category Code (IGCC) | 4926 >> Air circuit breakers |
| Object Classification Code | Q |
| UNSPSC | 39121615 |
| WEEE Category | 4. Large Equipment (Any External Dimension More Than 50 cm) |
| eClass | V11.1 : 27370409 |
| Feature Name | Feature Value |
|---|---|
| Rated permanent current Iu (EF001389) | 3200 A |
| Rated voltage (EF003977) | 690 V |
| Rated short-circuit breaking capacity Icu at 400 V, 50 Hz (EF007048) | 150 kA |
| Overload release current setting (EF002336) | 1280.0 A |
| Adjustment range short-term delayed short-circuit release (EF007129) | 1920.0 A |
| Adjustment range undelayed short-circuit release (EF007131) | 4800.0 A |
| Integrated earth fault protection (EF007296) | Yes |
| Type of electrical connection of main circuit (EF006819) | Connection at separate chassis part |
| Device construction (EF008240) | Built-in device slide-in technique (withdrawable) |
| Suitable for DIN rail (top hat rail) mounting (EF007250) | No |
| DIN rail (top hat rail) mounting optional (EF008904) | No |
| Number of auxiliary contacts as normally closed contact (EF001377) | 0 |
| Number of auxiliary contacts as normally open contact (EF001376) | 0 |
| Number of auxiliary contacts as change-over contact (EF003531) | 4 |
| With switched-off indicator (EF007006) | Yes |
| With integrated under voltage release (EF001390) | No |
| Number of poles (EF001391) | 4 |
| Position of connection for main current circuit (EF006671) | Connection at separate chassis part |
| Type of control element (EF006976) | Push button |
| Complete device with protection unit (EF008906) | Yes |
| Motor drive integrated (EF006697) | No |
| Motor drive optional (EF007386) | Yes |
| Degree of protection (IP) (EF005474) | IP30 |