View larger
1SDA073158R1
073158
ABB
1 Pcs.
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
| ABB EcoSolutions | |
|---|---|
| ABB EcoSolutions | Yes |
| ABB Site Meeting Group Waste To Landfill Target | UL 2799 Zero Waste To Landfill Validation available |
| End Of Life Disassembling Instructions | 9AKK108468A2363 |
| Environmental Product Declaration - EPD | 9AKK108468A1904 |
| 9AKK108468A1910 | |
| Extended Product Lifetime | Lifetime Extension Services are Offered |
| Recyclability Rate of the Product acc. to EN45555 | Design for Closing Resource Loops - Standard EN45555 - 79.3 % |
| Material Compliance | |
| REACH Declaration | 9AKK108466A1425 |
| RoHS Declaration | 9AKK108466A1424 |
| RoHS Information | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
| Conflict Minerals Reporting Template (CMRT) | 9AKK108467A5658 |
| Toxic Substances Control Act - TSCA | 9AKK108467A8326 |
| SCIP | 4c180e81-9f8e-401f-92b8-103b827fda2e Italy |
| Simplified SCIP | 2fa20714-fe96-4e55-8202-62217a1cf7ad Hungary |
| ee6d00e9-81a9-42a6-8da9-e98ae76261a6 Belgium | |
| c2994541-c365-44fa-a862-3a8dde56f8ef Poland | |
| dde97b1d-d736-420f-8044-8dc1c8547352 Germany | |
| 3aea7ef5-e5cf-48e1-b470-4cc905c890da Belgium | |
| 0ac33006-a4ce-4635-be54-ccfb3501a1ac Germany | |
| 5502fd2f-f93a-4b6d-9c8f-e0758173392e Norway | |
| 8dda0948-a939-4d53-8072-6eb382b71496 Finland | |
| d0c14b57-6784-40fc-9783-5e39f9e0d252 Croatia | |
| 540fb91f-6a25-423b-834a-d2d59b10cf3a Estonia | |
| bdb24e2c-54c6-4a46-931d-834674377361 Poland | |
| 8cff05f0-e32f-4e61-a9b1-ab196f154c53 Netherlands | |
| bacab227-471d-4a03-b50b-93d0c12f36a1 Hungary | |
| 8daa9565-2a2c-4c23-baf3-32e6c4de68f8 Greece | |
| 0928a0f0-faba-462f-822e-014db6717d10 Sweden | |
| 8a0fef8f-2c1a-48e0-9018-18cd716784a9 Bulgaria | |
| 7b95856f-e603-4c4c-9aa6-e67053aebc9c Portugal | |
| 0177602a-1836-4b86-b259-cc7c5ce2b3d2 Denmark | |
| b146b836-4ce9-4c2b-ab87-364ca25a5771 Germany | |
| 17fe8790-4d5c-4f38-beba-419a2db08230 Czech Republic | |
| 78d5f360-20c3-47c9-863c-497e4aa7a486 Poland | |
| 68ef274c-f32a-4483-a2aa-ed0c2c241fcd France | |
| 721c1968-ed3b-484d-a19c-c7a4681a6739 Germany | |
| 5ef70f06-1940-405d-aea1-b38f8828a207 Germany | |
| bc783dd8-57a6-4499-a1e1-08970fd9f2a7 Sweden | |
| cdf33209-b033-4995-bf5a-50e8deee6a22 Spain | |
| f3348a10-537a-499e-aa52-32ccb0633554 France | |
| Environmental | |
| Environmental Information | 9AKK108467A6707 |
| Ordering | |
| Order Code US and Canada | ZCVVENAJ200A000000XX |
| EAN | 8015644770082 |
| Minimum Order Quantity | 1 piece |
| Customs Tariff Number | 85362090 |
| Dimensions | |
| Product Net Width | 551 mm |
| Product Net Height | 425 mm |
| Product Net Depth / Length | 383 mm |
| Product Net Weight | 74 kg |
| Container Information | |
| Package Level 1 Units | box 1 piece |
| Package Level 1 Width | 515 mm |
| Package Level 1 Height | 610 mm |
| Package Level 1 Depth / Length | 785 mm |
| Package Level 1 Gross Weight | 81 kg |
| Package Level 1 EAN | 8015644770082 |
| Additional Information | |
| Product Main Type | SACE Emax 2 |
| Product Name | Air Circuit Breaker |
| Product Type | Air Circuit Breaker |
| Version | W |
| CAD Dimensional Drawing | 1SDH001252R0434 |
| Technical | |
| Connecting Capacity | 3000 mm² |
| Current Type | AC |
| Electrical Durability | Ue =< 440 V 7000 cycle |
| Ue = 500 ... 690 V 7000 cycle | |
| 20 cycles per hour | |
| Mechanical Durability | 20000 cycle |
| 60 cycles per hour | |
| Neutral Pole Current ([%Iu]) | 100 % |
| Number of Poles | 4P |
| Power Loss | 743 W |
| Rated Current (In) | 3200 A |
| Rated Impulse Withstand Voltage (Uimp) | acc. to IEC 60947-2 12 kV |
| Rated Insulation Voltage (Ui) | AC 1000 V |
| Rated Operational Voltage | 690 V AC |
| Rated Service Short-Circuit Breaking Capacity (Ics) | (220 V AC) 150 kA |
| (230 V AC) 150 kA | |
| (380 V AC) 150 kA | |
| (400 V AC) 150 kA | |
| (415 V AC) 150 kA | |
| (440 V AC) 150 kA | |
| (500 V AC) 100 kA | |
| (660 V AC) 100 kA | |
| (690 V AC) 100 kA | |
| Rated Service Short-Circuit Breaking Capacity, in % of Icu (Ics) | 100 % |
| Rated Short-time Withstand Current Low Voltage (Icw) | for 1 s 100 kA |
| for 3 s 75 kA | |
| Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (400 V AC) 150 kA |
| (415 V AC) 150 kA | |
| (440 V AC) 150 kA | |
| (500 V AC) 100 kA | |
| (525 V AC) 100 kA | |
| (690 V AC) 100 kA | |
| Rated Uninterrupted Current (Iu) | 3200 A |
| Rated Voltage (Ur) | 690 V |
| Recommended Screw Driver | M12 |
| Release | Ekip Hi-Touch LSI |
| Release Type | EL |
| Short-Circuit Performance Level | V |
| Standards | IEC |
| Sub-type | E4.2 |
| Suitable for IT Networks | Yes, 690V |
| Certificates and Declarations | |
| ATEX Certificate | No certification needed |
| CSA Certificate | No certification needed |
| CSA Certificate (Intrinsic Safe) | No certification needed |
| Data Sheet, Technical Information | 1SDC200023D0209 |
| Declaration of Conformity - CE | 9AKK106713A5545 |
| EU Data Act Compliance Declaration | 1SDH002560A1001 |
| UL Certificate | No certification needed |
| VDE Certificate | No certification needed |
| Mechanical Drawings | 1SDH001001R0102 |
| Wiring Diagram | 1SDM000091R0001 |
| Instructions and Manuals | 1SDH001000R0002 |
| Instructions and Manuals (Part 2) | 1SDH001316R1002 |
| External Classifications and Standards | |
| ETIM 9 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
| ETIM 10 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
| IDEA Granular Category Code (IGCC) | 4926 >> Air circuit breakers |
| Object Classification Code | Q |
| UNSPSC | 39121615 |
| WEEE Category | 4. Large Equipment (Any External Dimension More Than 50 cm) |
| eClass | V11.1 : 27370409 |
| Feature Name | Feature Value |
|---|---|
| Rated permanent current Iu (EF001389) | 3200 A |
| Rated voltage (EF003977) | 690 V |
| Rated short-circuit breaking capacity Icu at 400 V, 50 Hz (EF007048) | 150 kA |
| Overload release current setting (EF002336) | 1280.0 A |
| Adjustment range short-term delayed short-circuit release (EF007129) | 1920.0 A |
| Adjustment range undelayed short-circuit release (EF007131) | 4800.0 A |
| Integrated earth fault protection (EF007296) | No |
| Type of electrical connection of main circuit (EF006819) | Connection at separate chassis part |
| Device construction (EF008240) | Built-in device slide-in technique (withdrawable) |
| Suitable for DIN rail (top hat rail) mounting (EF007250) | No |
| DIN rail (top hat rail) mounting optional (EF008904) | No |
| Number of auxiliary contacts as normally closed contact (EF001377) | 0 |
| Number of auxiliary contacts as normally open contact (EF001376) | 0 |
| Number of auxiliary contacts as change-over contact (EF003531) | 4 |
| With switched-off indicator (EF007006) | Yes |
| With integrated under voltage release (EF001390) | No |
| Number of poles (EF001391) | 4 |
| Position of connection for main current circuit (EF006671) | Connection at separate chassis part |
| Type of control element (EF006976) | Push button |
| Complete device with protection unit (EF008906) | Yes |
| Motor drive integrated (EF006697) | No |
| Motor drive optional (EF007386) | Yes |
| Degree of protection (IP) (EF005474) | IP30 |