View larger
1SDA073153R1
073153
ABB
1 Pcs.
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
| ABB EcoSolutions | |
|---|---|
| ABB EcoSolutions | Yes |
| ABB Site Meeting Group Waste To Landfill Target | UL 2799 Zero Waste To Landfill Validation available |
| End Of Life Disassembling Instructions | 9AKK108468A2363 |
| Environmental Product Declaration - EPD | 9AKK108468A1904 |
| 9AKK108468A1910 | |
| Extended Product Lifetime | Lifetime Extension Services are Offered |
| Recyclability Rate of the Product acc. to EN45555 | Design for Closing Resource Loops - Standard EN45555 - 79.3 % |
| Material Compliance | |
| REACH Declaration | 9AKK108466A1425 |
| RoHS Declaration | 9AKK108466A1424 |
| RoHS Information | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
| Conflict Minerals Reporting Template (CMRT) | 9AKK108467A5658 |
| Toxic Substances Control Act - TSCA | 9AKK108467A8326 |
| SCIP | f67d0a5f-c718-4acd-976d-3ef6e275a4ba Italy |
| Simplified SCIP | 72cf74bc-87c4-4b37-938e-513a3239d228 Belgium |
| 7d856703-b1bf-4018-8758-712f9328be46 Hungary | |
| c6758345-0b60-429e-95e2-30d211c7488a France | |
| 0da8d536-4661-4b45-9359-e0abdbf8a59e Spain | |
| 9575e772-7afa-4ff4-b24f-85ad135e9e5a Germany | |
| 00fd9186-899a-470d-81f4-5a034ecd91e0 Sweden | |
| 234a208e-0e3c-4f6c-990b-7f9088a5240d Germany | |
| eda14e17-d797-45f1-8cf7-f00fce2e68f4 Poland | |
| 0f15b567-0a35-409b-b54e-ba63cdb585ef Bulgaria | |
| 8e60fa4c-a926-4b85-8ff0-586a9e3cf263 Sweden | |
| cf0a7e88-cd2b-4d8b-9758-fcdbd32ef2e7 Portugal | |
| d748dc75-ed61-4950-a03d-96f9c26c3818 Greece | |
| 46ad2c91-522e-4fb4-a19e-0dac6dc0cf13 Estonia | |
| 2efd0bd5-3f47-41b4-a700-a28929cb0de4 Hungary | |
| da462808-af09-4372-98e5-270e3dade678 Netherlands | |
| f989544a-8cfd-4f3a-8fd7-1aca9b1e4997 Poland | |
| a69e305d-d512-4307-b903-fd4949ef1fee Czech Republic | |
| 8b6e3e2d-fac7-4de3-823d-74590bb84a10 Germany | |
| de018ca4-0613-4833-9f08-1df935f83f11 Croatia | |
| a293ca36-35b0-44be-882c-db4d6b6f7a30 France | |
| cb6dfb8a-2d60-49b3-accc-79eebf72f8e6 Poland | |
| 016d911c-217f-41ce-afa3-c00c5999acba Germany | |
| 25e8a314-9820-4f40-bc6a-a3528011b61c Norway | |
| b05a6f68-baf5-4605-8ab0-605a042d74d5 Finland | |
| 17b774e4-67eb-4aef-bc5d-8c10dc642525 Germany | |
| 50968e54-e9c2-475f-8f02-e18f0d3d2044 Denmark | |
| 8ebfc6b4-2669-4a6d-9c6e-67de8c920256 Belgium | |
| Environmental | |
| Environmental Information | 9AKK108467A6707 |
| Ordering | |
| Order Code US and Canada | ZCVVENAC000A000000XX |
| EAN | 8015644770037 |
| Minimum Order Quantity | 1 piece |
| Customs Tariff Number | 85362090 |
| Dimensions | |
| Product Net Width | 551 mm |
| Product Net Height | 425 mm |
| Product Net Depth / Length | 383 mm |
| Product Net Weight | 74 kg |
| Container Information | |
| Package Level 1 Units | box 1 piece |
| Package Level 1 Width | 515 mm |
| Package Level 1 Height | 610 mm |
| Package Level 1 Depth / Length | 785 mm |
| Package Level 1 Gross Weight | 81 kg |
| Package Level 1 EAN | 8015644770037 |
| Additional Information | |
| Product Main Type | SACE Emax 2 |
| Product Name | Air Circuit Breaker |
| Product Type | Air Circuit Breaker |
| Version | W |
| CAD Dimensional Drawing | 1SDH001252R0434 |
| Technical | |
| Connecting Capacity | 3000 mm² |
| Current Type | AC |
| Electrical Durability | Ue =< 440 V 7000 cycle |
| Ue = 500 ... 690 V 7000 cycle | |
| 20 cycles per hour | |
| Mechanical Durability | 20000 cycle |
| 60 cycles per hour | |
| Neutral Pole Current ([%Iu]) | 100 % |
| Number of Poles | 4P |
| Power Loss | 743 W |
| Rated Current (In) | 3200 A |
| Rated Impulse Withstand Voltage (Uimp) | acc. to IEC 60947-2 12 kV |
| Rated Insulation Voltage (Ui) | AC 1000 V |
| Rated Operational Voltage | 690 V AC |
| Rated Service Short-Circuit Breaking Capacity (Ics) | (220 V AC) 150 kA |
| (230 V AC) 150 kA | |
| (380 V AC) 150 kA | |
| (400 V AC) 150 kA | |
| (415 V AC) 150 kA | |
| (440 V AC) 150 kA | |
| (500 V AC) 100 kA | |
| (660 V AC) 100 kA | |
| (690 V AC) 100 kA | |
| Rated Service Short-Circuit Breaking Capacity, in % of Icu (Ics) | 100 % |
| Rated Short-time Withstand Current Low Voltage (Icw) | for 1 s 100 kA |
| for 3 s 75 kA | |
| Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (400 V AC) 150 kA |
| (415 V AC) 150 kA | |
| (440 V AC) 150 kA | |
| (500 V AC) 100 kA | |
| (525 V AC) 100 kA | |
| (690 V AC) 100 kA | |
| Rated Uninterrupted Current (Iu) | 3200 A |
| Rated Voltage (Ur) | 690 V |
| Recommended Screw Driver | M12 |
| Release | Ekip Dip LSIG |
| Release Type | EL |
| Short-Circuit Performance Level | V |
| Standards | IEC |
| Sub-type | E4.2 |
| Suitable for IT Networks | Yes, 690V |
| Certificates and Declarations | |
| ATEX Certificate | No certification needed |
| CSA Certificate | No certification needed |
| CSA Certificate (Intrinsic Safe) | No certification needed |
| Data Sheet, Technical Information | 1SDC200023D0209 |
| Declaration of Conformity - CE | 9AKK106713A5545 |
| EU Data Act Compliance Declaration | 1SDH002560A1001 |
| UL Certificate | No certification needed |
| VDE Certificate | No certification needed |
| Mechanical Drawings | 1SDH001001R0102 |
| Wiring Diagram | 1SDM000091R0001 |
| Instructions and Manuals | 1SDH001000R0002 |
| External Classifications and Standards | |
| ETIM 9 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
| ETIM 10 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
| IDEA Granular Category Code (IGCC) | 4926 >> Air circuit breakers |
| Object Classification Code | Q |
| UNSPSC | 39121615 |
| WEEE Category | 4. Large Equipment (Any External Dimension More Than 50 cm) |
| eClass | V11.1 : 27370409 |