View larger
1SDA073102R1
073102
ABB
1 Pcs.
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
| ABB EcoSolutions | |
|---|---|
| ABB EcoSolutions | Yes |
| ABB Site Meeting Group Waste To Landfill Target | UL 2799 Zero Waste To Landfill Validation available |
| End Of Life Disassembling Instructions | 9AKK108468A2363 |
| Environmental Product Declaration - EPD | 9AKK108468A1904 |
| 9AKK108468A1910 | |
| Extended Product Lifetime | Lifetime Extension Services are Offered |
| Recyclability Rate of the Product acc. to EN45555 | Design for Closing Resource Loops - Standard EN45555 - 79.3 % |
| Material Compliance | |
| REACH Declaration | 9AKK108466A1425 |
| RoHS Declaration | 9AKK108466A1424 |
| RoHS Information | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
| Conflict Minerals Reporting Template (CMRT) | 9AKK108467A5658 |
| Toxic Substances Control Act - TSCA | 9AKK108467A8326 |
| SCIP | c1b0992b-43eb-4ef1-9ef1-39da06bd59d1 Italy |
| Simplified SCIP | edf2479e-9142-427f-bf13-b4b0c0f2f41a Germany |
| 75bc0622-2fbe-4f7b-b217-42f353d2c951 Poland | |
| 50cabcee-e742-481c-a60e-7c722cd2c7ca Poland | |
| e1dc2238-ac99-41a7-bffe-7ee3f2b7c259 Bulgaria | |
| 918a022e-9977-40d1-b4ce-bdf5963b42eb Sweden | |
| 293bfc62-d7fe-40d6-b45d-3ec79fa90a4f Portugal | |
| 53aa35a4-2cb7-4f1f-a025-5ab4f09c95be France | |
| bcc14c7f-f177-4382-9aa7-13fe3701ab1b Czech Republic | |
| d431ef3f-ce55-450a-86ff-ca79b1cb1ebc Norway | |
| 08ccfdcc-ff18-4302-8e3f-ba9f3cf0bff9 Hungary | |
| 3b38cc4c-a0bd-4630-9e93-1faa9fa9682e Poland | |
| 2523718d-b8fb-4337-81b4-dda69192a52a Croatia | |
| 58d31049-31b5-4edb-822a-b91bde092188 Germany | |
| a88c64c4-60ff-42d4-911d-79b5826fb0ee Denmark | |
| 3db016aa-e4a2-4f37-8cb3-353ec77a7194 Germany | |
| 80ae3efe-cd30-4b22-91ac-9e5b0f11f33d Germany | |
| 8e957892-dd29-4af0-a034-734d5255ce3c Germany | |
| 4a2c1f8a-c3c8-4e45-b92c-aca7e5fc1916 Sweden | |
| bd829724-efe1-486b-9698-d1fb4a820c6a Greece | |
| 392d60cd-fc1c-4e3d-a508-32a603bab323 Estonia | |
| 85a2736f-3bba-4758-8042-350c1c91f60e Netherlands | |
| 04834964-9e54-4804-9234-03330b14c00a Finland | |
| eb147f9e-da9c-43db-902b-3e323e1f090d Belgium | |
| 706b3225-f6a3-4173-acef-71bb43c53781 France | |
| 035af78b-a6e9-4684-bd83-52c89e058d12 Spain | |
| 3c769c4b-6279-4ada-b9d4-3432b4617e48 Belgium | |
| c40fc42d-b3aa-4792-971e-cb0187fe8140 Hungary | |
| Environmental | |
| Environmental Information | 9AKK108467A6707 |
| Ordering | |
| Order Code US and Canada | ZCVUELAB000A000000XX |
| EAN | 8015644769529 |
| Minimum Order Quantity | 1 piece |
| Customs Tariff Number | 85362090 |
| Dimensions | |
| Product Net Width | 551 mm |
| Product Net Height | 425 mm |
| Product Net Depth / Length | 383 mm |
| Product Net Weight | 74 kg |
| Container Information | |
| Package Level 1 Units | box 1 piece |
| Package Level 1 Width | 515 mm |
| Package Level 1 Height | 610 mm |
| Package Level 1 Depth / Length | 785 mm |
| Package Level 1 Gross Weight | 81 kg |
| Package Level 1 EAN | 8015644769529 |
| Additional Information | |
| Product Main Type | SACE Emax 2 |
| Product Name | Air Circuit Breaker |
| Product Type | Air Circuit Breaker |
| Version | W |
| CAD Dimensional Drawing | 1SDH001252R0434 |
| Technical | |
| Connecting Capacity | 2000 mm² |
| Current Type | AC |
| Electrical Durability | Ue =< 440 V 8000 cycle |
| Ue = 500 ... 690 V 8000 cycle | |
| 20 cycles per hour | |
| Mechanical Durability | 20000 cycle |
| 60 cycles per hour | |
| Neutral Pole Current ([%Iu]) | 100 % |
| Number of Poles | 4P |
| Power Loss | 743 W |
| Rated Current (In) | 2500 A |
| Rated Impulse Withstand Voltage (Uimp) | acc. to IEC 60947-2 12 kV |
| Rated Insulation Voltage (Ui) | AC 1000 V |
| Rated Operational Voltage | 690 V AC |
| Rated Service Short-Circuit Breaking Capacity (Ics) | (220 V AC) 150 kA |
| (230 V AC) 150 kA | |
| (380 V AC) 150 kA | |
| (400 V AC) 150 kA | |
| (415 V AC) 150 kA | |
| (440 V AC) 150 kA | |
| (500 V AC) 100 kA | |
| (660 V AC) 100 kA | |
| (690 V AC) 100 kA | |
| Rated Service Short-Circuit Breaking Capacity, in % of Icu (Ics) | 100 % |
| Rated Short-time Withstand Current Low Voltage (Icw) | for 1 s 100 kA |
| for 3 s 75 kA | |
| Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (400 V AC) 150 kA |
| (415 V AC) 150 kA | |
| (440 V AC) 150 kA | |
| (500 V AC) 100 kA | |
| (525 V AC) 100 kA | |
| (690 V AC) 100 kA | |
| Rated Uninterrupted Current (Iu) | 2500 A |
| Rated Voltage (Ur) | 690 V |
| Recommended Screw Driver | M12 |
| Release | Ekip Dip LSI |
| Release Type | EL |
| Short-Circuit Performance Level | V |
| Standards | IEC |
| Sub-type | E4.2 |
| Suitable for IT Networks | Yes, 690V |
| Certificates and Declarations | |
| ATEX Certificate | No certification needed |
| CSA Certificate | No certification needed |
| CSA Certificate (Intrinsic Safe) | No certification needed |
| Data Sheet, Technical Information | 1SDC200023D0209 |
| Declaration of Conformity - CE | 9AKK106713A5545 |
| EU Data Act Compliance Declaration | 1SDH002560A1001 |
| UL Certificate | No certification needed |
| VDE Certificate | No certification needed |
| Mechanical Drawings | 1SDH001001R0102 |
| Wiring Diagram | 1SDM000091R0001 |
| Instructions and Manuals | 1SDH001000R0002 |
| External Classifications and Standards | |
| ETIM 9 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
| ETIM 10 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
| IDEA Granular Category Code (IGCC) | 4926 >> Air circuit breakers |
| Object Classification Code | Q |
| UNSPSC | 39121615 |
| WEEE Category | 4. Large Equipment (Any External Dimension More Than 50 cm) |
| eClass | V11.1 : 27370409 |
| Feature Name | Feature Value |
|---|---|
| Rated permanent current Iu (EF001389) | 2500 A |
| Rated voltage (EF003977) | 690 V |
| Rated short-circuit breaking capacity Icu at 400 V, 50 Hz (EF007048) | 150 kA |
| Overload release current setting (EF002336) | 1000.0 A |
| Adjustment range short-term delayed short-circuit release (EF007129) | 1500.0 A |
| Adjustment range undelayed short-circuit release (EF007131) | 3750.0 A |
| Integrated earth fault protection (EF007296) | No |
| Type of electrical connection of main circuit (EF006819) | Connection at separate chassis part |
| Device construction (EF008240) | Built-in device slide-in technique (withdrawable) |
| Suitable for DIN rail (top hat rail) mounting (EF007250) | No |
| DIN rail (top hat rail) mounting optional (EF008904) | No |
| Number of auxiliary contacts as normally closed contact (EF001377) | 0 |
| Number of auxiliary contacts as normally open contact (EF001376) | 0 |
| Number of auxiliary contacts as change-over contact (EF003531) | 4 |
| With switched-off indicator (EF007006) | Yes |
| With integrated under voltage release (EF001390) | No |
| Number of poles (EF001391) | 4 |
| Position of connection for main current circuit (EF006671) | Connection at separate chassis part |
| Type of control element (EF006976) | Push button |
| Complete device with protection unit (EF008906) | Yes |
| Motor drive integrated (EF006697) | No |
| Motor drive optional (EF007386) | Yes |
| Degree of protection (IP) (EF005474) | IP30 |