View larger
1SDA073084R1
073084
ABB
1 Pcs.
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
| ABB EcoSolutions | |
|---|---|
| ABB EcoSolutions | Yes |
| ABB Site Meeting Group Waste To Landfill Target | UL 2799 Zero Waste To Landfill Validation available |
| End Of Life Disassembling Instructions | 9AKK108468A2363 |
| Environmental Product Declaration - EPD | 9AKK108468A1904 |
| 9AKK108468A1910 | |
| Extended Product Lifetime | Lifetime Extension Services are Offered |
| Recyclability Rate of the Product acc. to EN45555 | Design for Closing Resource Loops - Standard EN45555 - 79.3 % |
| Material Compliance | |
| REACH Declaration | 9AKK108466A1425 |
| RoHS Declaration | 9AKK108466A1424 |
| RoHS Information | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
| Conflict Minerals Reporting Template (CMRT) | 9AKK108467A5658 |
| Toxic Substances Control Act - TSCA | 9AKK108467A8326 |
| SCIP | 1356fe53-0d6b-490c-94ba-3ae2686ae3b7 China |
| Simplified SCIP | c0636f68-3e45-455d-9840-41118b3923a7 France |
| d1e11231-0da1-4e08-a2ae-066782fe88c8 Belgium | |
| 5b8d30b6-2706-4723-baf5-7d13c522c32e Finland | |
| 2ba03daf-245d-4e9a-a2f4-92fd38cd7a6b Germany | |
| 5467bb6d-bb4a-4ccb-b4d5-8eb5a7e61690 Germany | |
| b833ada0-a627-4126-beef-563222f76d14 France | |
| 5f051607-b6e5-4104-969d-1ba0f92b92da Hungary | |
| 57495e1c-2a0e-404d-82cb-09af53391b7b Poland | |
| f34c9e26-177a-41d9-b7c8-7614b76f82f7 Estonia | |
| 40766de1-6063-4257-93c2-3ebdae5982dc Bulgaria | |
| 1c912145-2d6e-44c6-8df6-7b998d0c01ac Portugal | |
| ba20c94d-4add-4f86-a99c-12920619089f Sweden | |
| 3c3d4dd7-9046-49f7-a1ec-586bd86bf3cf Germany | |
| 0f99fb22-7067-4feb-9e19-7cfa8be8abb1 Denmark | |
| ea1c6bfa-8f4e-478a-b814-826bf8140bf6 Germany | |
| 6ffb9e71-78f8-4c15-b438-f10884704bcc Norway | |
| 40d576ff-2603-4165-a186-3db223400c52 Greece | |
| 2b770aa5-4c44-41c7-838a-819927466414 Poland | |
| e24ccaa6-c733-467e-9505-4ad43250d221 Hungary | |
| a2253a46-cb0e-4549-b6da-a25af9644e53 Belgium | |
| 6c16fb66-5280-4f94-9e2e-4cbff409f038 Croatia | |
| 7228ce79-2027-4fdb-a74e-00b6f4a97406 Sweden | |
| ca4ceae0-a766-4389-b315-af73a6396d5c Spain | |
| 6fd79bb9-2514-4e02-813c-cab5837c99e9 Czech Republic | |
| 037f1045-c900-4c22-aa32-323b821fc9d9 Poland | |
| 2b9cae5a-1c83-4acc-ad68-5e0321812d08 Netherlands | |
| 3ef88255-e317-4e0d-9a50-6ad9543ba91a Germany | |
| Environmental | |
| Environmental Information | 9AKK108467A6707 |
| Ordering | |
| Order Code US and Canada | ZCVTEKAD000A000000XX |
| EAN | 8015644769345 |
| Minimum Order Quantity | 1 piece |
| Customs Tariff Number | 85362090 |
| Dimensions | |
| Product Net Width | 551 mm |
| Product Net Height | 425 mm |
| Product Net Depth / Length | 383 mm |
| Product Net Weight | 74 kg |
| Container Information | |
| Package Level 1 Units | box 1 piece |
| Package Level 1 Width | 515 mm |
| Package Level 1 Height | 610 mm |
| Package Level 1 Depth / Length | 785 mm |
| Package Level 1 Gross Weight | 81 kg |
| Package Level 1 EAN | 8015644769345 |
| Additional Information | |
| Product Main Type | SACE Emax 2 |
| Product Name | Air Circuit Breaker |
| Product Type | Air Circuit Breaker |
| Version | W |
| CAD Dimensional Drawing | 1SDH001252R0434 |
| Technical | |
| Connecting Capacity | 1600 mm² |
| Current Type | AC |
| Electrical Durability | Ue =< 440 V 10000 cycle |
| Ue = 500 ... 690 V 10000 cycle | |
| 20 cycles per hour | |
| Mechanical Durability | 20000 cycle |
| 60 cycles per hour | |
| Neutral Pole Current ([%Iu]) | 100 % |
| Number of Poles | 4P |
| Power Loss | 743 W |
| Rated Current (In) | 2000 A |
| Rated Impulse Withstand Voltage (Uimp) | acc. to IEC 60947-2 12 kV |
| Rated Insulation Voltage (Ui) | AC 1000 V |
| Rated Operational Voltage | 690 V AC |
| Rated Service Short-Circuit Breaking Capacity (Ics) | (220 V AC) 150 kA |
| (230 V AC) 150 kA | |
| (380 V AC) 150 kA | |
| (400 V AC) 150 kA | |
| (415 V AC) 150 kA | |
| (440 V AC) 150 kA | |
| (500 V AC) 100 kA | |
| (660 V AC) 100 kA | |
| (690 V AC) 100 kA | |
| Rated Service Short-Circuit Breaking Capacity, in % of Icu (Ics) | 100 % |
| Rated Short-time Withstand Current Low Voltage (Icw) | for 1 s 100 kA |
| for 3 s 75 kA | |
| Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (400 V AC) 150 kA |
| (415 V AC) 150 kA | |
| (440 V AC) 150 kA | |
| (500 V AC) 100 kA | |
| (525 V AC) 100 kA | |
| (690 V AC) 100 kA | |
| Rated Uninterrupted Current (Iu) | 2000 A |
| Rated Voltage (Ur) | 690 V |
| Recommended Screw Driver | M12 |
| Release | Ekip Touch LI |
| Release Type | EL |
| Short-Circuit Performance Level | V |
| Standards | IEC |
| Sub-type | E4.2 |
| Suitable for IT Networks | Yes, 690V |
| Certificates and Declarations | |
| ATEX Certificate | No certification needed |
| CSA Certificate | No certification needed |
| CSA Certificate (Intrinsic Safe) | No certification needed |
| Data Sheet, Technical Information | 1SDC200023D0209 |
| Declaration of Conformity - CE | 9AKK106713A5545 |
| EU Data Act Compliance Declaration | 1SDH002560A1001 |
| UL Certificate | No certification needed |
| VDE Certificate | No certification needed |
| Mechanical Drawings | 1SDH001001R0102 |
| Wiring Diagram | 1SDM000091R0001 |
| Instructions and Manuals | 1SDH001000R0002 |
| Instructions and Manuals (Part 2) | 1SDH001316R1002 |
| External Classifications and Standards | |
| ETIM 9 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
| ETIM 10 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
| IDEA Granular Category Code (IGCC) | 4926 >> Air circuit breakers |
| Object Classification Code | Q |
| UNSPSC | 39121615 |
| WEEE Category | 4. Large Equipment (Any External Dimension More Than 50 cm) |
| eClass | V11.1 : 27370409 |