View larger
1SDA073083R1
073083
ABB
1 Pcs.
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
| ABB EcoSolutions | |
|---|---|
| ABB EcoSolutions | Yes |
| Circular Value | |
| Circular Design Principles Recyclability Rate | Design for Closing Resource Loops - Standard EN45555 - 79.3 % |
| Conflict Minerals Reporting Template (CMRT) | 9AKK108467A5658 |
| End of Life Instructions | 9AKK108468A2363 |
| Group Waste to Landfill Target | UL 2799 Zero Waste To Landfill Validation available |
| Toxic Substances Control Act - TSCA | 9AKK108467A8326 |
| Eco Transparency | |
| Environmental Product Declaration - EPD | 9AKK108468A1904 |
| 9AKK108468A1910 | |
| Environmental | |
| Environmental Information | 9AKK108467A6707 |
| REACH Declaration | 9AKK108466A1425 |
| RoHS Information | 9AKK108466A1424 |
| RoHS Status | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
| SCIP | d3888c32-896f-4b78-bb28-613956b082c5 Italy (IT) |
| Simplified SCIP | 31efa287-d9a6-4b23-8fc1-ca9a822de5ad Germany (DE) |
| 54897843-73fd-4497-8976-1320d6ecfb55 Hungary (HU) | |
| 954e59d1-af16-4f1a-b863-b4169ac12350 Bulgaria (BG) | |
| f35a2333-6fa8-45d3-901f-f59339aedccd Poland (PL) | |
| f437a10e-fd5f-4b6a-8b12-69a82fbdaab2 Czech Republic (CZ) | |
| 83df6cfb-e221-4bbc-834d-3beb7b7b9a22 Poland (PL) | |
| 60c53bde-ea5b-460a-8e91-b622e47298e7 Sweden (SE) | |
| 9780f547-0aa8-4a4d-866d-49df36be2283 Portugal (PT) | |
| 4f6d406a-a830-4ecb-a015-b67a2cac809f Hungary (HU) | |
| 1141bb11-9071-4b94-a4ce-604238644fc3 Spain (ES) | |
| 5f623579-a0c6-4a77-920c-067ee1b45abd Belgium (BE) | |
| bbaa8526-5a6e-4a1a-809d-4b56dad4935a France (FR) | |
| 53a9a7b8-1c49-4d69-ab9c-f2d881e65dab Denmark (DK) | |
| 25978a2e-60a4-4fd1-962f-d3db70a68b43 Germany (DE) | |
| 273ff3a2-649e-4c72-b65c-427e7b025815 Germany (DE) | |
| 7bcd480a-dc2e-41da-a9a9-ccd7f2f6826a Sweden (SE) | |
| d9f798fd-dbd1-469b-b549-60b86df0c2c9 Greece (GR) | |
| 7fb699b5-7d04-4e98-9663-be616aaf9c9e Belgium (BE) | |
| fdc5284a-ba60-4501-85d1-ff53034eda8e Finland (FI) | |
| a5e56a43-d7e1-46fd-9998-959b6e2a6aaf Estonia (EE) | |
| d4261e25-6817-4cb1-8a3b-a4787d89b887 Croatia (HR) | |
| a8968002-6b28-4ae1-9fb8-bff41f7d501c Germany (DE) | |
| c9b0c296-6233-40ff-862a-cc2f747ea93f Germany (DE) | |
| c91dbf03-1ffc-4449-89da-2d2af6bc5b7d France (FR) | |
| 07e193bf-1e3f-47ed-b80c-38ccb16350fc Netherlands (NL) | |
| b3d05c12-e265-4b80-b32a-68cb5820642d Poland (PL) | |
| 69cb0d92-8eea-43f4-99de-5095e38765a4 Norway (NO) | |
| Ordering | |
| Order Code US and Canada | ZCVTEKAC000A000000XX |
| EAN | 8015644769338 |
| Minimum Order Quantity | 1 piece |
| Customs Tariff Number | 85362090 |
| Dimensions | |
| Product Net Width | 551 mm |
| Product Net Height | 425 mm |
| Product Net Depth / Length | 383 mm |
| Product Net Weight | 74 kg |
| Container Information | |
| Package Level 1 Units | box 1 piece |
| Package Level 1 Width | 515 mm |
| Package Level 1 Height | 610 mm |
| Package Level 1 Depth / Length | 785 mm |
| Package Level 1 Gross Weight | 81 kg |
| Package Level 1 EAN | 8015644769338 |
| Additional Information | |
| Current Type | AC |
| Electrical Durability | Ue =< 440 V 10000 cycle |
| Ue = 500 ... 690 V 10000 cycle | |
| 20 cycles per hour | |
| Mechanical Durability | 20000 cycle |
| 60 cycles per hour | |
| Neutral Pole Current ([%Iu]) | 100 % |
| Number of Poles | 4 |
| Power Loss | 743 W |
| Product Main Type | SACE Emax 2 |
| Product Name | Air Circuit Breaker |
| Product Type | Air Circuit Breaker |
| Rated Service Short-Circuit Breaking Capacity, in % of Icu (Ics) | 100 % |
| Rated Current (In) | 2000 A |
| Rated Voltage (Ur) | 690 V |
| Rated Impulse Withstand Voltage (Uimp) | acc. to IEC 60947-2 12 kV |
| Rated Insulation Voltage (Ui) | AC 1000 V |
| Rated Operational Voltage | 690 V AC |
| Rated Service Short-Circuit Breaking Capacity (Ics) | (220 V AC) 150 kA |
| (230 V AC) 150 kA | |
| (380 V AC) 150 kA | |
| (400 V AC) 150 kA | |
| (415 V AC) 150 kA | |
| (440 V AC) 150 kA | |
| (500 V AC) 100 kA | |
| (660 V AC) 100 kA | |
| (690 V AC) 100 kA | |
| Rated Short-time Withstand Current Low Voltage (Icw) | for 1 s 100 kA |
| for 3 s 75 kA | |
| Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (400 V AC) 150 kA |
| (415 V AC) 150 kA | |
| (440 V AC) 150 kA | |
| (500 V AC) 100 kA | |
| (525 V AC) 100 kA | |
| (690 V AC) 100 kA | |
| Rated Uninterrupted Current (Iu) | 2000 A |
| Release | Ekip Dip LSIG |
| Release Type | EL |
| Short-Circuit Performance Level | V |
| Standards | IEC |
| Sub-type | E4.2 |
| Version | W |
| CAD Dimensional Drawing | 1SDH001252R0434 |
| Certificates and Declarations | |
| ATEX Certificate | No certification needed |
| CSA Certificate | No certification needed |
| CSA Certificate (Intrinsic Safe) | No certification needed |
| Data Sheet, Technical Information | 1SDC200023D0209 |
| Declaration of Conformity - CE | 9AKK106713A5545 |
| UL Certificate | No certification needed |
| VDE Certificate | No certification needed |
| Mechanical Drawings | 1SDH001001R0102 |
| Wiring Diagram | 1SDM000091R0001 |
| Instructions and Manuals | 1SDH001000R0002 |
| Classifications | |
| ETIM 7 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
| ETIM 8 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
| ETIM 9 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
| IDEA Granular Category Code (IGCC) | 4926 >> Air circuit breakers |
| Object Classification Code | Q |
| UNSPSC | 39121615 |
| WEEE Category | 4. Large Equipment (Any External Dimension More Than 50 cm) |
| eClass | V11.1 : 27370409 |
| Feature Name | Feature Value |
|---|---|
| Rated permanent current Iu (EF001389) | 2000 A |
| Rated voltage (EF003977) | 690 V |
| Rated short-circuit breaking capacity Icu at 400 V, 50 Hz (EF007048) | 150 kA |
| Overload release current setting (EF002336) | 2000 A |
| Adjustment range short-term delayed short-circuit release (EF007129) | 1200.0 A |
| Adjustment range undelayed short-circuit release (EF007131) | 3000.0 A |
| Integrated earth fault protection (EF007296) | Yes |
| Type of electrical connection of main circuit (EF006819) | Connection at separate chassis part |
| Device construction (EF008240) | Built-in device slide-in technique (withdrawable) |
| Suitable for DIN rail (top hat rail) mounting (EF007250) | No |
| DIN rail (top hat rail) mounting optional (EF008904) | No |
| Number of auxiliary contacts as normally closed contact (EF001377) | 0 |
| Number of auxiliary contacts as normally open contact (EF001376) | 0 |
| Number of auxiliary contacts as change-over contact (EF003531) | 4 |
| With switched-off indicator (EF007006) | Yes |
| With integrated under voltage release (EF001390) | No |
| Number of poles (EF001391) | 4 |
| Position of connection for main current circuit (EF006671) | Connection at separate chassis part |
| Type of control element (EF006976) | Push button |
| Complete device with protection unit (EF008906) | Yes |
| Motor drive integrated (EF006697) | No |
| Motor drive optional (EF007386) | Yes |
| Degree of protection (IP) (EF005474) | IP30 |