View larger
1SDA056153R1 ABB E3N 3200 PR121/P-LSI In 3200A 4p F HR
1SDA056153R1
056153
ABB
1 Pcs.
Automation > Power circuit-breaker for trafo/generator/installation protection
E3
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
ABB 1SDA056153R1 E3N 3200 PR121/P-LSI In 3200A 4p F HR is a high-current air circuit breaker engineered for demanding industrial power management architectures. It safely interrupts extreme fault currents to protect extensive electrical distribution grids.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Conflict Minerals Reporting Template (CMRT): Document availability on demand
- Environmental Information: 9AKK10103A6076
- REACH Declaration: 9AKK108466A1425
- RoHS Information: 9AKK108466A1424
- RoHS Status: Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
- EAN: 8015644574932
- Minimum Order Quantity: 1 piece
- Customs Tariff Number: 85362090
- Product Net Width: 530 mm
- Product Net Height: 418 mm
- Product Net Depth / Length: 302 mm
- Product Net Weight: 76 kg
- Package Level 1 Units: 1 piece
- Package Level 1 Width: 515 mm
- Package Level 1 Height: 600 mm
- Package Level 1 Depth / Length: 785 mm
More info
▲| Circular Value | |
|---|---|
| Conflict Minerals Reporting Template (CMRT) | Document availability on demand |
| Environmental | |
| Environmental Information | 9AKK10103A6076 |
| REACH Declaration | 9AKK108466A1425 |
| RoHS Information | 9AKK108466A1424 |
| RoHS Status | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
| Ordering | |
| EAN | 8015644574932 |
| Minimum Order Quantity | 1 piece |
| Customs Tariff Number | 85362090 |
| Dimensions | |
| Product Net Width | 530 mm |
| Product Net Height | 418 mm |
| Product Net Depth / Length | 302 mm |
| Product Net Weight | 76 kg |
| Container Information | |
| Package Level 1 Units | 1 piece |
| Package Level 1 Width | 515 mm |
| Package Level 1 Height | 600 mm |
| Package Level 1 Depth / Length | 785 mm |
| Package Level 1 Gross Weight | 90 kg |
| Package Level 1 EAN | 8015644574932 |
| Additional Information | |
| Current Type | AC |
| Electrical Durability | Ue =< 440 V 6000 cycle |
| Ue = 500 ... 690 V 5000 cycle | |
| 20 cycles per hour | |
| Mechanical Durability | 20000 cycle |
| 60 cycles per hour | |
| Number of Poles | 4 |
| Power Loss | 330 W |
| Product Main Type | SACE Emax |
| Product Name | Air Circuit Breaker |
| Product Type | Air Circuit Breaker |
| Rated Current (In) | 3200 A |
| Rated Voltage (Ur) | 690 V |
| Rated Impulse Withstand Voltage (Uimp) | 12 kV |
| Rated Insulation Voltage (Ui) | 1000 V |
| Rated Operational Current (Ie) | 3200 A |
| Rated Operational Voltage | 690 V AC |
| Rated Service Short-Circuit Breaking Capacity (Ics) | (220 V AC) 65 kA |
| (230 V AC) 65 kA | |
| (380 V AC) 65 kA | |
| (400 V AC) 65 kA | |
| (415 V AC) 65 kA | |
| (440 V AC) 65 kA | |
| (500 V AC) 65 kA | |
| (660 V AC) 65 kA | |
| (690 V AC) 65 kA | |
| Rated Short-time Withstand Current Low Voltage (Icw) | for 1 s 65 kA |
| for 3 s 65 kA | |
| Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (220 V AC) 65 kA |
| (230 V AC) 65 kA | |
| (380 V AC) 65 kA | |
| (400 V AC) 65 kA | |
| (415 V AC) 65 kA | |
| (440 V AC) 65 kA | |
| (500 V AC) 65 kA | |
| (660 V AC) 65 kA | |
| (690 V AC) 65 kA | |
| Rated Uninterrupted Current (Iu) | 3200 A |
| Release | PR121/P-LSI |
| Release Type | EL |
| Short-Circuit Performance Level | N |
| Standards | IEC |
| Sub-type | E3 |
| Terminal Connection Type | Fixed Circuit-Breakers |
| Rear flat Horizontal | |
| Version | F |
| Certificates and Declarations | |
| Data Sheet, Technical Information | 1SDC200006D0209 |
| Declaration of Conformity - CE | 1SDL000165R0015 |
| Instructions and Manuals | 1SDH000460R0002 |
| Classifications | |
| ETIM 7 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
| ETIM 8 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
| Object Classification Code | Q |
| WEEE Category | 4. Large Equipment (Any External Dimension More Than 50 cm) |