View larger
Images are for illustrative purposes only. Please refer to data sheet for details
1SDA056401R1 ABB E3H 1600 PR121/P-LSI In 1600A 3p F HR
1SDA056401R1
056401
ABB
1 Pcs.
E3H 1600 PR121/P-LSI In=1600A 3p F HR
E3H1600 PR121/P LSI 3P F HR
Automation > Power circuit-breaker for trafo/generator/installation protection
E3
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Manufacturer ABB offers the 1SDA056401R1 electrical protection unit to manage high-capacity power lines securely. Such devices are built for demanding industrial switchgear applications where reliable circuit isolation is required.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- REACH Declaration: 9AKK108466A1425
- RoHS Declaration: 9AKK108466A1424
- RoHS Information: Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
- Conflict Minerals Reporting Template (CMRT): Document availability on demand
- SCIP: d1f917d9-49b7-4f07-987b-dc5d91c3cef1 Italy
- Simplified SCIP: 4ef3f816-c230-4759-9a55-4e1106b265e3 Netherlands
- Environmental Information: 9AKK10103A6076
- EAN: 8015644577414
- Minimum Order Quantity: 1 piece
- Customs Tariff Number: 85362090
- Product Net Width: 404 mm
- Product Net Height: 418 mm
- Product Net Depth / Length: 302 mm
- Product Net Weight: 60 kg
- Package Level 1 Units: 1 piece
- Package Level 1 Width: 515 mm
More info
▲| Material Compliance | |
|---|---|
| REACH Declaration | 9AKK108466A1425 |
| RoHS Declaration | 9AKK108466A1424 |
| RoHS Information | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
| Conflict Minerals Reporting Template (CMRT) | Document availability on demand |
| SCIP | d1f917d9-49b7-4f07-987b-dc5d91c3cef1 Italy |
| Simplified SCIP | 4ef3f816-c230-4759-9a55-4e1106b265e3 Netherlands |
| 327c0582-286d-47c2-b1a3-e2c2dc3c2b16 France | |
| f62085d8-1cf2-40f8-a749-05497eaeb9b4 Hungary | |
| 344fb83b-8f6e-4118-83eb-ba62bd9be757 Sweden | |
| d75227e4-337c-4dc7-a78e-d0af17ec3465 Germany | |
| dda6ba33-4b2f-4d64-9e9c-3741eacf9ad2 Germany | |
| 93a91c8d-057a-42c7-b917-fbf02d295def Spain | |
| 468baeaa-5515-4097-b039-c30f0add9747 Poland | |
| 35015216-cea2-4d04-9b69-bfdb2bcf51df Belgium | |
| 0e4ca7d5-1997-496d-8808-b8c525a57662 Norway | |
| baa6a753-b37a-49fd-b50b-a9c07ba57b62 France | |
| ef74b337-c87b-4f0f-be10-d3de471f37b9 Poland | |
| e1eb62eb-fbc7-46eb-a5e0-b8b698bdce5b Germany | |
| 73aefe8b-c65e-45e2-8491-33093d982a48 Sweden | |
| 72008756-8f0f-4b2f-a36b-357f711b101a Denmark | |
| aa0ac33b-7b28-44f8-a130-ce5081d56d89 Germany | |
| ec322fd1-0b78-40b8-92d6-5e6dd1c26553 Poland | |
| 6cf8377a-c556-4370-ba5f-75a8794e6fdb Germany | |
| b5bc980b-5d3e-4c51-91d0-27d6aafe904c Finland | |
| b4e8960e-d5ed-4b6d-9769-042536475cc4 Belgium | |
| 852fb56b-9fb5-4bfc-a894-bf1238b841c1 Czech Republic | |
| 512875aa-0e1a-4c1b-b41e-007517435c77 Croatia | |
| 44179a64-acce-439b-a22a-5d25a072b2ea Greece | |
| 19b96bb2-4ba1-40de-bcc6-6b2400b354ec Bulgaria | |
| 2c7c9fc9-3ce9-49de-9b3a-c0cc0a59ec32 Portugal | |
| Environmental | |
| Environmental Information | 9AKK10103A6076 |
| Ordering | |
| EAN | 8015644577414 |
| Minimum Order Quantity | 1 piece |
| Customs Tariff Number | 85362090 |
| Dimensions | |
| Product Net Width | 404 mm |
| Product Net Height | 418 mm |
| Product Net Depth / Length | 302 mm |
| Product Net Weight | 60 kg |
| Container Information | |
| Package Level 1 Units | 1 piece |
| Package Level 1 Width | 515 mm |
| Package Level 1 Height | 600 mm |
| Package Level 1 Depth / Length | 615 mm |
| Package Level 1 Gross Weight | 72 kg |
| Package Level 1 EAN | 8015644577414 |
| Additional Information | |
| Product Main Type | SACE Emax |
| Product Name | Air Circuit Breaker |
| Product Type | Air Circuit Breaker |
| Version | F |
| Technical | |
| Current Type | AC |
| Electrical Durability | Ue =< 440 V 10000 cycle |
| Ue = 500 ... 690 V 10000 cycle | |
| 20 cycles per hour | |
| Mechanical Durability | 20000 cycle |
| 60 cycles per hour | |
| Number of Poles | 3P |
| Power Loss | 85 W |
| Rated Current (In) | 1600 A |
| Rated Impulse Withstand Voltage (Uimp) | 12 kV |
| Rated Insulation Voltage (Ui) | 1000 V |
| Rated Operational Current (Ie) | 1600 A |
| Rated Operational Voltage | 690 V AC |
| Rated Service Short-Circuit Breaking Capacity (Ics) | (220 V AC) 85 kA |
| (230 V AC) 85 kA | |
| (380 V AC) 85 kA | |
| (400 V AC) 85 kA | |
| (415 V AC) 85 kA | |
| (440 V AC) 85 kA | |
| (500 V AC) 85 kA | |
| (660 V AC) 85 kA | |
| (690 V AC) 85 kA | |
| Rated Short-time Withstand Current Low Voltage (Icw) | for 1 s 75 kA |
| for 3 s 65 kA | |
| Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (220 V AC) 100 kA |
| (230 V AC) 100 kA | |
| (380 V AC) 100 kA | |
| (400 V AC) 100 kA | |
| (415 V AC) 100 kA | |
| (440 V AC) 100 kA | |
| (500 V AC) 100 kA | |
| (660 V AC) 85 kA | |
| (690 V AC) 85 kA | |
| Rated Uninterrupted Current (Iu) | 1600 A |
| Rated Voltage (Ur) | 690 V |
| Release | PR121/P-LSI |
| Release Type | EL |
| Short-Circuit Performance Level | H |
| Standards | IEC |
| Sub-type | E3 |
| Terminal Connection Type | Fixed Circuit-Breakers |
| Rear flat Horizontal | |
| Certificates and Declarations | |
| Data Sheet, Technical Information | 1SDC200006D0209 |
| Declaration of Conformity - CE | 1SDL000165R0015 |
| Instructions and Manuals | 1SDH000460R0002 |
| External Classifications and Standards | |
| Object Classification Code | Q |
| UNSPSC | 39120000 |
| WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) |