View larger
1SDA072889R1
072889
ABB
1 Pcs.
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
| ABB EcoSolutions | |
|---|---|
| ABB EcoSolutions | Yes |
| ABB Site Meeting Group Waste To Landfill Target | UL 2799 Zero Waste To Landfill Validation available |
| End Of Life Disassembling Instructions | 9AKK108468A2361 |
| Environmental Product Declaration - EPD | 9AKK108468A1902 |
| 9AKK108468A1909 | |
| Extended Product Lifetime | Lifetime Extension Services are Offered |
| Recyclability Rate of the Product acc. to EN45555 | Design for Closing Resource Loops - Standard EN45555 - 79.1 % |
| Material Compliance | |
| REACH Declaration | 9AKK108466A1425 |
| RoHS Declaration | 9AKK108466A1424 |
| RoHS Information | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
| Conflict Minerals Reporting Template (CMRT) | 9AKK108467A5658 |
| Toxic Substances Control Act - TSCA | 9AKK108467A8326 |
| SCIP | 5db9272f-d385-4a4a-a0e6-73274e7613b2 Italy |
| Environmental | |
| Environmental Information | 9AKK108467A6707 |
| Ordering | |
| Order Code US and Canada | ZBSPEFAK200A000000XX |
| EAN | 8015644767396 |
| Minimum Order Quantity | 1 piece |
| Customs Tariff Number | 85362090 |
| Dimensions | |
| Product Net Width | 407 mm |
| Product Net Height | 425 mm |
| Product Net Depth / Length | 383 mm |
| Product Net Weight | 55 kg |
| Container Information | |
| Package Level 1 Units | box 1 piece |
| Package Level 1 Width | 515 mm |
| Package Level 1 Height | 610 mm |
| Package Level 1 Depth / Length | 615 mm |
| Package Level 1 Gross Weight | 60 kg |
| Package Level 1 EAN | 8015644767396 |
| Additional Information | |
| Product Main Type | SACE Emax 2 |
| Product Name | Air Circuit Breaker |
| Product Type | Air Circuit Breaker |
| Version | W |
| CAD Dimensional Drawing | 1SDH001252R0432 |
| Technical | |
| Connecting Capacity | 600 mm² |
| Current Type | AC |
| Electrical Durability | Ue =< 440 V 15000 cycle |
| Ue = 500 ... 690 V 15000 cycle | |
| 30 cycles per hour | |
| Mechanical Durability | 25000 cycle |
| 60 cycles per hour | |
| Neutral Pole Current ([%Iu]) | 100 % |
| Number of Poles | 4P |
| Power Loss | 72 W |
| Rated Current (In) | 800 A |
| Rated Impulse Withstand Voltage (Uimp) | acc. to IEC 60947-2 12 kV |
| Rated Insulation Voltage (Ui) | AC 1000 V |
| Rated Operational Voltage | 690 V AC |
| Rated Service Short-Circuit Breaking Capacity (Ics) | (220 V AC) 85 kA |
| (230 V AC) 85 kA | |
| (380 V AC) 85 kA | |
| (400 V AC) 85 kA | |
| (415 V AC) 85 kA | |
| (440 V AC) 85 kA | |
| (500 V AC) 66 kA | |
| (660 V AC) 66 kA | |
| (690 V AC) 66 kA | |
| Rated Service Short-Circuit Breaking Capacity, in % of Icu (Ics) | 100 % |
| Rated Short-time Withstand Current Low Voltage (Icw) | for 1 s 66 kA |
| for 3 s 50 kA | |
| Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (400 V AC) 85 kA |
| (415 V AC) 85 kA | |
| (440 V AC) 85 kA | |
| (500 V AC) 66 kA | |
| (525 V AC) 66 kA | |
| (690 V AC) 66 kA | |
| Rated Uninterrupted Current (Iu) | 800 A |
| Rated Voltage (Ur) | 690 V |
| Recommended Screw Driver | M12 |
| Release | Ekip Hi-Touch LSIG |
| Release Type | EL |
| Short-Circuit Performance Level | S |
| Standards | IEC |
| Sub-type | E2.2 |
| Suitable for IT Networks | Yes, 690V |
| Certificates and Declarations | |
| ATEX Certificate | No certification needed |
| CSA Certificate | No certification needed |
| CSA Certificate (Intrinsic Safe) | No certification needed |
| Data Sheet, Technical Information | 1SDC200023D0209 |
| Declaration of Conformity - CE | 9AKK106713A5902 |
| EU Data Act Compliance Declaration | 1SDH002560A1001 |
| UL Certificate | No certification needed |
| VDE Certificate | No certification needed |
| Mechanical Drawings | 1SDH001000R0102 |
| Wiring Diagram | 1SDM000091R0001 |
| Instructions and Manuals | 1SDH001000R0002 |
| Instructions and Manuals (Part 2) | 1SDH001316R1002 |
| External Classifications and Standards | |
| ETIM 9 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
| ETIM 10 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
| IDEA Granular Category Code (IGCC) | 4926 >> Air circuit breakers |
| Object Classification Code | Q |
| UNSPSC | 39121615 |
| WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) |
| eClass | V11.1 : 27370409 |
| Feature Name | Feature Value |
|---|---|
| Rated permanent current Iu (EF001389) | 800 A |
| Rated voltage (EF003977) | 690 V |
| Rated short-circuit breaking capacity Icu at 400 V, 50 Hz (EF007048) | 85 kA |
| Overload release current setting (EF002336) | 320.0 A |
| Adjustment range short-term delayed short-circuit release (EF007129) | 480.0 A |
| Adjustment range undelayed short-circuit release (EF007131) | 1200.0 A |
| Integrated earth fault protection (EF007296) | Yes |
| Type of electrical connection of main circuit (EF006819) | Connection at separate chassis part |
| Device construction (EF008240) | Built-in device slide-in technique (withdrawable) |
| Suitable for DIN rail (top hat rail) mounting (EF007250) | No |
| DIN rail (top hat rail) mounting optional (EF008904) | No |
| Number of auxiliary contacts as normally closed contact (EF001377) | 0 |
| Number of auxiliary contacts as normally open contact (EF001376) | 0 |
| Number of auxiliary contacts as change-over contact (EF003531) | 4 |
| With switched-off indicator (EF007006) | Yes |
| With integrated under voltage release (EF001390) | No |
| Number of poles (EF001391) | 4 |
| Position of connection for main current circuit (EF006671) | Connection at separate chassis part |
| Type of control element (EF006976) | Push button |
| Complete device with protection unit (EF008906) | Yes |
| Motor drive integrated (EF006697) | No |
| Motor drive optional (EF007386) | Yes |
| Degree of protection (IP) (EF005474) | IP30 |