View larger
1SDA073646R1 ABB E2.2S 250 Ekip Hi-Touch LSIG 4p F HR
1SDA073646R1
073646
ABB
1 Pcs.
Automation > Power circuit-breaker for trafo/generator/installation protection
E2.2
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
An ABB E2.2S 250 Ekip Hi-Touch LSIG 4p F HR air circuit breaker provides comprehensive protection and control for complex electrical distribution networks. It safely interrupts high fault currents and monitors system parameters to prevent damage in commercial and industrial switchboards.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- ABB EcoSolutions: Yes
- Circular Design Principles Recyclability Rate: Design for Closing Resource Loops - Standard EN45555 - 79.1 %
- Conflict Minerals Reporting Template (CMRT): 9AKK108467A5658
- End of Life Instructions: 9AKK108468A2361
- Group Waste to Landfill Target: UL 2799 Zero Waste To Landfill Validation available
- Toxic Substances Control Act - TSCA: 9AKK108467A8326
- Environmental Product Declaration - EPD: 9AKK108468A1902
- Environmental Information: 9AKK108467A6707
- REACH Declaration: 9AKK108466A1425
- RoHS Information: Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
- RoHS Status: Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
- SCIP: 5db9272f-d385-4a4a-a0e6-73274e7613b2 Italy (IT)
- Order Code US and Canada: ZBSMECBK200A000000XX
- EAN: 8015644775797
- Minimum Order Quantity: 1 piece
- Customs Tariff Number: 85362090
More info
▲| ABB EcoSolutions | |
|---|---|
| ABB EcoSolutions | Yes |
| Circular Value | |
| Circular Design Principles Recyclability Rate | Design for Closing Resource Loops - Standard EN45555 - 79.1 % |
| Conflict Minerals Reporting Template (CMRT) | 9AKK108467A5658 |
| End of Life Instructions | 9AKK108468A2361 |
| Group Waste to Landfill Target | UL 2799 Zero Waste To Landfill Validation available |
| Toxic Substances Control Act - TSCA | 9AKK108467A8326 |
| Eco Transparency | |
| Environmental Product Declaration - EPD | 9AKK108468A1902 |
| 9AKK108468A1909 | |
| Environmental | |
| Environmental Information | 9AKK108467A6707 |
| REACH Declaration | 9AKK108466A1425 |
| RoHS Information | 9AKK108466A1424 |
| RoHS Status | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
| SCIP | 5db9272f-d385-4a4a-a0e6-73274e7613b2 Italy (IT) |
| Ordering | |
| Order Code US and Canada | ZBSMECBK200A000000XX |
| EAN | 8015644775797 |
| Minimum Order Quantity | 1 piece |
| Customs Tariff Number | 85362090 |
| Dimensions | |
| Product Net Width | 366 mm |
| Product Net Height | 371 mm |
| Product Net Depth / Length | 270 mm |
| Product Net Weight | 53 kg |
| Container Information | |
| Package Level 1 Units | box 1 piece |
| Package Level 1 Width | 515 mm |
| Package Level 1 Height | 610 mm |
| Package Level 1 Depth / Length | 615 mm |
| Package Level 1 Gross Weight | 58 kg |
| Package Level 1 EAN | 8015644775797 |
| Additional Information | |
| Current Type | AC |
| Electrical Durability | Ue =< 440 V 15000 cycle |
| Ue = 500 ... 690 V 15000 cycle | |
| 30 cycles per hour | |
| Mechanical Durability | 25000 cycle |
| 60 cycles per hour | |
| Neutral Pole Current ([%Iu]) | 100 % |
| Number of Poles | 4 |
| Power Loss | 50 W |
| Product Main Type | SACE Emax 2 |
| Product Name | Air Circuit Breaker |
| Product Type | Air Circuit Breaker |
| Rated Service Short-Circuit Breaking Capacity, in % of Icu (Ics) | 100 % |
| Rated Current (In) | 250 A |
| Rated Voltage (Ur) | 690 V |
| Rated Impulse Withstand Voltage (Uimp) | acc. to IEC 60947-2 12 kV |
| Rated Insulation Voltage (Ui) | AC 1000 V |
| Rated Operational Voltage | 690 V AC |
| Rated Service Short-Circuit Breaking Capacity (Ics) | (220 V AC) 85 kA |
| (230 V AC) 85 kA | |
| (380 V AC) 85 kA | |
| (400 V AC) 85 kA | |
| (415 V AC) 85 kA | |
| (440 V AC) 85 kA | |
| (500 V AC) 66 kA | |
| (660 V AC) 66 kA | |
| (690 V AC) 66 kA | |
| Rated Short-time Withstand Current Low Voltage (Icw) | for 1 s 66 kA |
| for 3 s 50 kA | |
| Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (400 V AC) 85 kA |
| (415 V AC) 85 kA | |
| (440 V AC) 85 kA | |
| (500 V AC) 66 kA | |
| (525 V AC) 66 kA | |
| (690 V AC) 66 kA | |
| Rated Uninterrupted Current (Iu) | 250 A |
| Release | Ekip Hi-Touch LSIG |
| Release Type | EL |
| Short-Circuit Performance Level | S |
| Standards | IEC |
| Sub-type | E2.2 |
| Terminal Connection Type | Rear flat Horizontal |
| Version | F |
| Certificates and Declarations | |
| Data Sheet, Technical Information | 1SDC200023D0209 |
| Declaration of Conformity - CE | 9AKK106713A5902 |
| Instructions and Manuals | 1SDH001000R0002 |
| Instructions and Manuals (Part 2) | 1SDH001316R1002 |
| Classifications | |
| ETIM 7 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
| ETIM 8 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
| ETIM 9 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
| IDEA Granular Category Code (IGCC) | 4926 >> Air circuit breakers |
| Object Classification Code | Q |
| UNSPSC | 39121615 |
| WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) |
| eClass | V11.1 : 27370409 |