ABB 1SDA071637R1 1SDA071637R1 ABB E2.2S 1600 Ekip G Touch LSIG 4p F HR View larger
Images are for illustrative purposes only. Please refer to data sheet for details

1SDA071637R1 ABB E2.2S 1600 Ekip G Touch LSIG 4p F HR

1SDA071637R1

071637

ABB

1 Pcs.

E2.2S 1600 Ekip G Touch LSIG 4p F HR

Automation > Power circuit-breaker for trafo/generator/installation protection
E2.2

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.

Request Quote

Product Overview

A 1SDA071637R1 ABB E2.2S 1600 Ekip G Touch LSIG 4p F HR is an air circuit breaker utilized for heavy-duty electrical protection and system control in large-scale industrial facilities. Such devices provide advanced trip unit capabilities to manage complex power grids and safeguard high-amperage electrical assets from fault conditions.

Pricing, availability and lead time are confirmed per enquiry through an RFQ.

  • ABB EcoSolutions: Yes
  • Circular Design Principles Recyclability Rate: Design for Closing Resource Loops - Standard EN45555 - 79.1 %
  • Conflict Minerals Reporting Template (CMRT): 9AKK108467A5658
  • End of Life Instructions: 9AKK108468A2361
  • Group Waste to Landfill Target: UL 2799 Zero Waste To Landfill Validation available
  • Toxic Substances Control Act - TSCA: 9AKK108467A8326
  • Environmental Product Declaration - EPD: 9AKK108468A1902
  • Environmental Information: 9AKK108467A6707
  • REACH Declaration: 9AKK108466A1425
  • RoHS Information: 9AKK108466A1424
  • RoHS Status: Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
  • Order Code US and Canada: ZBSSEJBN200A000000XX
  • EAN: 8015644754877
  • Minimum Order Quantity: 1 piece
  • Customs Tariff Number: 85362090
  • Product Net Width: 366 mm

More info

▲
ABB EcoSolutions
ABB EcoSolutionsYes
Circular Value
Circular Design Principles Recyclability RateDesign for Closing Resource Loops - Standard EN45555 - 79.1 %
Conflict Minerals Reporting Template (CMRT)9AKK108467A5658
End of Life Instructions9AKK108468A2361
Group Waste to Landfill TargetUL 2799 Zero Waste To Landfill Validation available
Toxic Substances Control Act - TSCA9AKK108467A8326
Eco Transparency
Environmental Product Declaration - EPD9AKK108468A1902
9AKK108468A1909
Environmental
Environmental Information9AKK108467A6707
REACH Declaration9AKK108466A1425
RoHS Information9AKK108466A1424
RoHS StatusFollowing EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Ordering
Order Code US and CanadaZBSSEJBN200A000000XX
EAN8015644754877
Minimum Order Quantity1 piece
Customs Tariff Number85362090
Dimensions
Product Net Width366 mm
Product Net Height371 mm
Product Net Depth / Length270 mm
Product Net Weight53 kg
Container Information
Package Level 1 Unitsbox 1 piece
Package Level 1 Width515 mm
Package Level 1 Height610 mm
Package Level 1 Depth / Length615 mm
Package Level 1 Gross Weight58 kg
Package Level 1 EAN8015644754877
Additional Information
Current TypeAC
Electrical DurabilityUe =< 440 V 12000 cycle
Ue = 500 ... 690 V 10000 cycle
30 cycles per hour
Mechanical Durability25000 cycle
60 cycles per hour
Neutral Pole Current ([%Iu])100 %
Number of Poles4
Power Loss136 W
Product Main TypeSACE Emax 2
Product NameAir Circuit Breaker
Product TypeAir Circuit Breaker
Rated Service Short-Circuit Breaking Capacity, in % of Icu (Ics)100 %
Rated Current (In)1600 A
Rated Voltage (Ur)690 V
Rated Impulse Withstand Voltage (Uimp)acc. to IEC 60947-2 12 kV
Rated Insulation Voltage (Ui)AC 1000 V
Rated Operational Voltage690 V AC
Rated Service Short-Circuit Breaking Capacity (Ics)(220 V AC) 85 kA
(230 V AC) 85 kA
(380 V AC) 85 kA
(400 V AC) 85 kA
(415 V AC) 85 kA
(440 V AC) 85 kA
(500 V AC) 66 kA
(660 V AC) 66 kA
(690 V AC) 66 kA
Rated Short-time Withstand Current Low Voltage (Icw)for 1 s 66 kA
for 3 s 50 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)(400 V AC) 85 kA
(415 V AC) 85 kA
(440 V AC) 85 kA
(500 V AC) 66 kA
(525 V AC) 66 kA
(690 V AC) 66 kA
Rated Uninterrupted Current (Iu)1600 A
ReleaseEkip G Touch LSIG
Release TypeEL
Short-Circuit Performance LevelS
StandardsIEC
Sub-typeE2.2
Terminal Connection TypeRear flat Horizontal
VersionF
Certificates and Declarations
Data Sheet, Technical Information1SDC200023D0209
Declaration of Conformity - CE9AKK106713A5902
Instructions and Manuals1SDH001000R0002
Instructions and Manuals (Part 2)1SDH001316R1002
Classifications
ETIM 7EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 8EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9EC000228 - Power circuit-breaker for trafo/generator/installation protection
IDEA Granular Category Code (IGCC)4926 >> Air circuit breakers
Object Classification CodeQ
UNSPSC39121615
WEEE Category5. Small Equipment (No External Dimension More Than 50 cm)
eClassV11.1 : 27370409

Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.