View larger
1SDA073047R1
073047
ABB
1 Pcs.
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
| ABB EcoSolutions | |
|---|---|
| ABB EcoSolutions | Yes |
| ABB Site Meeting Group Waste To Landfill Target | UL 2799 Zero Waste To Landfill Validation available |
| End Of Life Disassembling Instructions | 9AKK108468A2361 |
| Environmental Product Declaration - EPD | 9AKK108468A1902 |
| 9AKK108468A1909 | |
| Extended Product Lifetime | Lifetime Extension Services are Offered |
| Recyclability Rate of the Product acc. to EN45555 | Design for Closing Resource Loops - Standard EN45555 - 79.1 % |
| Material Compliance | |
| REACH Declaration | 9AKK108466A1425 |
| RoHS Declaration | 9AKK108466A1424 |
| RoHS Information | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
| Conflict Minerals Reporting Template (CMRT) | 9AKK108467A5658 |
| Toxic Substances Control Act - TSCA | 9AKK108467A8326 |
| SCIP | ff107143-1375-400d-b1ed-519a274ba3ef Italy |
| Simplified SCIP | cb14f982-f875-4b5c-bfdd-97f7511274f0 Germany |
| 6f30b537-7153-4f98-a953-bff08b0a6026 Poland | |
| d500eebf-6cba-44e7-8dee-94d130883158 Poland | |
| 0ff0466a-34a5-465b-9b6a-c3b4ea8c4f27 Sweden | |
| 153639c4-9fc5-4683-8c5a-0eac575eb38b Bulgaria | |
| 5f516a8e-bcbd-4768-92ec-72ecfe966845 Portugal | |
| 8f14f8b2-9903-4467-8ed1-8a2328f4802b France | |
| d259cdfb-fa57-4c0b-bb2d-f2ac1fb35dfd France | |
| 42f38e22-f1ca-43b7-9ff5-5a2bf28d0ec0 Croatia | |
| 3e849709-a297-4111-a67c-50a2f5c9686f Germany | |
| 2fbcb1ce-49a1-44f9-935b-901e79529757 Denmark | |
| fc169ae6-25fc-4162-92a4-021f1b2a495e Germany | |
| ae811754-a7a6-4f75-983a-fcfa42769b9a Germany | |
| 46bdea1b-56f8-43ba-b738-0081570ee37a Germany | |
| 64cc7c31-3a41-4db4-bfad-1b81676142cf Estonia | |
| d3e2853f-938d-48e2-9781-e2711b519f01 Netherlands | |
| 9352171d-69b7-4af3-88d0-7e2d8ef9468e Finland | |
| d9b6997c-4d3f-4b16-b43f-872b771f3ba4 Greece | |
| 827a455a-9906-4b39-80d9-07dac2f31edd Sweden | |
| c9a8bfeb-4f4a-4e4e-97c4-b198fb33c4dc Belgium | |
| c41670ba-fa49-4ff1-a1c7-2bcf614fadc9 Norway | |
| 41f43c0e-22fe-4931-b033-2909f275a149 Hungary | |
| 9c9caa9a-1b9f-4f90-97c5-8e4b8926d2aa Poland | |
| 691c276d-5d4b-44bb-ad7f-8f7993ab3f9b Czech Republic | |
| 6af6b88f-dfaf-4303-8d1f-620112068cff Spain | |
| e7c4620a-c472-4683-b15b-c1a20ba76c5c Belgium | |
| 3e50c1bd-74f4-496c-ab85-1d9023e39eb1 Hungary | |
| Environmental | |
| Environmental Information | 9AKK108467A6707 |
| Ordering | |
| Order Code US and Canada | ZBNUELAN200A000000XX |
| EAN | 8015644768973 |
| Minimum Order Quantity | 1 piece |
| Customs Tariff Number | 85362090 |
| Dimensions | |
| Product Net Width | 407 mm |
| Product Net Height | 425 mm |
| Product Net Depth / Length | 383 mm |
| Product Net Weight | 55 kg |
| Container Information | |
| Package Level 1 Units | box 1 piece |
| Package Level 1 Width | 515 mm |
| Package Level 1 Height | 610 mm |
| Package Level 1 Depth / Length | 615 mm |
| Package Level 1 Gross Weight | 60 kg |
| Package Level 1 EAN | 8015644768973 |
| Additional Information | |
| Product Main Type | SACE Emax 2 |
| Product Name | Air Circuit Breaker |
| Product Type | Air Circuit Breaker |
| Version | W |
| Technical | |
| Connecting Capacity | 1800 mm² |
| Current Type | AC |
| Electrical Durability | Ue =< 440 V 8000 cycle |
| Ue = 500 ... 690 V 7000 cycle | |
| 30 cycles per hour | |
| Mechanical Durability | 20000 cycle |
| 60 cycles per hour | |
| Neutral Pole Current ([%Iu]) | 100 % |
| Number of Poles | 4P |
| Power Loss | 550 W |
| Rated Current (In) | 2500 A |
| Rated Impulse Withstand Voltage (Uimp) | acc. to IEC 60947-2 12 kV |
| Rated Insulation Voltage (Ui) | AC 1000 V |
| Rated Operational Voltage | 690 V AC |
| Rated Service Short-Circuit Breaking Capacity (Ics) | (220 V AC) 66 kA |
| (230 V AC) 66 kA | |
| (380 V AC) 66 kA | |
| (400 V AC) 66 kA | |
| (415 V AC) 66 kA | |
| (440 V AC) 66 kA | |
| (500 V AC) 66 kA | |
| (660 V AC) 66 kA | |
| (690 V AC) 66 kA | |
| Rated Service Short-Circuit Breaking Capacity, in % of Icu (Ics) | 100 % |
| Rated Short-time Withstand Current Low Voltage (Icw) | for 1 s 66 kA |
| for 3 s 50 kA | |
| Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (400 V AC) 66 kA |
| (415 V AC) 66 kA | |
| (440 V AC) 66 kA | |
| (500 V AC) 66 kA | |
| (525 V AC) 66 kA | |
| (690 V AC) 66 kA | |
| Rated Uninterrupted Current (Iu) | 2500 A |
| Rated Voltage (Ur) | 690 V |
| Recommended Screw Driver | M12 |
| Release | Ekip G Touch LSIG |
| Release Type | EL |
| Short-Circuit Performance Level | N |
| Standards | IEC |
| Sub-type | E2.2 |
| Suitable for IT Networks | Yes, 690V |
| Certificates and Declarations | |
| Data Sheet, Technical Information | 1SDC200023D0209 |
| Declaration of Conformity - CE | 9AKK106713A5902 |
| EU Data Act Compliance Declaration | 1SDH002560A1001 |
| Instructions and Manuals | 1SDH001000R0002 |
| Instructions and Manuals (Part 2) | 1SDH001316R1002 |
| External Classifications and Standards | |
| ETIM 9 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
| ETIM 10 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
| IDEA Granular Category Code (IGCC) | 4926 >> Air circuit breakers |
| Object Classification Code | Q |
| UNSPSC | 39121615 |
| WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) |
| eClass | V11.1 : 27370409 |
| Feature Name | Feature Value |
|---|---|
| Rated permanent current Iu (EF001389) | 2500 A |
| Rated voltage (EF003977) | 690 V |
| Rated short-circuit breaking capacity Icu at 400 V, 50 Hz (EF007048) | 66 kA |
| Overload release current setting (EF002336) | 1000.0 A |
| Adjustment range short-term delayed short-circuit release (EF007129) | 1500.0 A |
| Adjustment range undelayed short-circuit release (EF007131) | 3750.0 A |
| Integrated earth fault protection (EF007296) | Yes |
| Type of electrical connection of main circuit (EF006819) | Connection at separate chassis part |
| Device construction (EF008240) | Built-in device slide-in technique (withdrawable) |
| Suitable for DIN rail (top hat rail) mounting (EF007250) | No |
| DIN rail (top hat rail) mounting optional (EF008904) | No |
| Number of auxiliary contacts as normally closed contact (EF001377) | 0 |
| Number of auxiliary contacts as normally open contact (EF001376) | 0 |
| Number of auxiliary contacts as change-over contact (EF003531) | 4 |
| With switched-off indicator (EF007006) | Yes |
| With integrated under voltage release (EF001390) | No |
| Number of poles (EF001391) | 4 |
| Position of connection for main current circuit (EF006671) | Connection at separate chassis part |
| Type of control element (EF006976) | Push button |
| Complete device with protection unit (EF008906) | Yes |
| Motor drive integrated (EF006697) | No |
| Motor drive optional (EF007386) | Yes |
| Degree of protection (IP) (EF005474) | IP30 |