View larger
1SDA072350R1
072350
ABB
1 Pcs.
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
| ABB EcoSolutions | |
|---|---|
| ABB EcoSolutions | Yes |
| ABB Site Meeting Group Waste To Landfill Target | UL 2799 Zero Waste To Landfill Validation available |
| End Of Life Disassembling Instructions | 9AKK108468A2361 |
| Environmental Product Declaration - EPD | 9AKK108468A1902 |
| 9AKK108468A1909 | |
| Extended Product Lifetime | Lifetime Extension Services are Offered |
| Recyclability Rate of the Product acc. to EN45555 | Design for Closing Resource Loops - Standard EN45555 - 79.1 % |
| Material Compliance | |
| REACH Declaration | 9AKK108466A1425 |
| RoHS Declaration | 9AKK108466A1424 |
| RoHS Information | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
| Conflict Minerals Reporting Template (CMRT) | 9AKK108467A5658 |
| Toxic Substances Control Act - TSCA | 9AKK108467A8326 |
| SCIP | ae7bebb0-71e1-4d4d-b496-8fafd1f9d6f5 Italy |
| Simplified SCIP | 3ef2388b-d7ce-462c-92fc-417dc95e179e Sweden |
| 853346ab-9815-4a36-b2d1-03496976c381 Germany | |
| d4ed424b-1423-46dd-a17a-6e9110670975 Germany | |
| 37bce78b-5fb4-41e8-8107-959410aad6c7 Germany | |
| 0b21eb76-4967-4914-9e0f-2326cd10ae1d Norway | |
| 320d7b51-d3b2-4c84-8f05-e4d507b9ab9c Poland | |
| 21d20545-985a-426d-ab26-011587e17a40 Spain | |
| 7218a69b-f568-405e-aa9f-ca9127d5bf8a Poland | |
| 9c805ec9-d327-4a8b-b9bb-07ea7cee709a Poland | |
| 8f5b8af5-7e50-41df-aa59-4cf72104ea89 Belgium | |
| 42852259-24bb-4d94-bfea-01cb828bd381 Germany | |
| ace22ded-3558-4273-83f5-09fd843c46e0 Finland | |
| b1229cbd-c08b-44e1-836f-caeb59d64c73 Germany | |
| 412cea7b-25f0-4a53-8827-5f1bce25e6dc Czech Republic | |
| bf5070bd-9fac-4d93-8b60-b1b2b720bb4f Belgium | |
| 2fdbc231-ea1c-49f6-96ef-07c44a639cfd Croatia | |
| 1aababf2-fa6e-450b-a5e5-6baa10682c7a Greece | |
| 13625463-ed2f-4775-8f11-d8d0e1e7c4f5 Bulgaria | |
| 4f31008c-bb6c-42d1-9de6-5bb2b45200f4 Portugal | |
| 1de85ead-73a6-4e3a-b9c8-4ae7e070df4c Denmark | |
| 37589718-bc95-4719-b2a1-dbba7a5e81a7 France | |
| 8688f7d4-40d8-4aed-9231-d1fad0d52263 Hungary | |
| c65b4653-8be1-45b3-9838-8c0f5da5c04c France | |
| e524083f-9b2c-4ad9-84d6-4b4297f76198 Netherlands | |
| 0344efd1-f33e-40af-b7db-0d21f36e111d Sweden | |
| Environmental | |
| Environmental Information | 9AKK108467A6707 |
| Ordering | |
| Order Code US and Canada | Z2NSEJAQ200A000000XX |
| EAN | 8015644762001 |
| Minimum Order Quantity | 1 piece |
| Customs Tariff Number | 85362090 |
| Dimensions | |
| Product Net Width | 317 mm |
| Product Net Height | 425 mm |
| Product Net Depth / Length | 383 mm |
| Product Net Weight | 48 kg |
| Container Information | |
| Package Level 1 Units | box 1 piece |
| Package Level 1 Width | 515 mm |
| Package Level 1 Height | 610 mm |
| Package Level 1 Depth / Length | 515 mm |
| Package Level 1 Gross Weight | 53 kg |
| Package Level 1 EAN | 8015644762001 |
| Additional Information | |
| Product Main Type | SACE Emax 2 |
| Product Name | Air Circuit Breaker |
| Product Type | Air Circuit Breaker |
| Version | W |
| Technical | |
| Connecting Capacity | 1200 mm² |
| Current Type | AC |
| Electrical Durability | Ue =< 440 V 12000 cycle |
| Ue = 500 ... 690 V 10000 cycle | |
| 30 cycles per hour | |
| Mechanical Durability | 25000 cycle |
| 60 cycles per hour | |
| Number of Poles | 3P |
| Power Loss | 288 W |
| Rated Current (In) | 1600 A |
| Rated Impulse Withstand Voltage (Uimp) | acc. to IEC 60947-2 12 kV |
| Rated Insulation Voltage (Ui) | AC 1000 V |
| Rated Operational Voltage | 690 V AC |
| Rated Service Short-Circuit Breaking Capacity (Ics) | (220 V AC) 66 kA |
| (230 V AC) 66 kA | |
| (380 V AC) 66 kA | |
| (400 V AC) 66 kA | |
| (415 V AC) 66 kA | |
| (440 V AC) 66 kA | |
| (500 V AC) 66 kA | |
| (660 V AC) 66 kA | |
| (690 V AC) 66 kA | |
| Rated Service Short-Circuit Breaking Capacity, in % of Icu (Ics) | 100 % |
| Rated Short-time Withstand Current Low Voltage (Icw) | for 1 s 66 kA |
| for 3 s 50 kA | |
| Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (400 V AC) 66 kA |
| (415 V AC) 66 kA | |
| (440 V AC) 66 kA | |
| (500 V AC) 66 kA | |
| (525 V AC) 66 kA | |
| (690 V AC) 66 kA | |
| Rated Uninterrupted Current (Iu) | 1600 A |
| Rated Voltage (Ur) | 690 V |
| Recommended Screw Driver | M12 |
| Release | Ekip G Hi-Touch LSIG |
| Release Type | EL |
| Short-Circuit Performance Level | N |
| Standards | IEC |
| Sub-type | E2.2 |
| Suitable for IT Networks | Yes, 690V |
| Certificates and Declarations | |
| Data Sheet, Technical Information | 1SDC200023D0209 |
| Declaration of Conformity - CE | 9AKK106713A5902 |
| EU Data Act Compliance Declaration | 1SDH002560A1001 |
| Instructions and Manuals | 1SDH001000R0002 |
| Instructions and Manuals (Part 2) | 1SDH001316R1002 |
| External Classifications and Standards | |
| ETIM 9 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
| ETIM 10 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
| IDEA Granular Category Code (IGCC) | 4926 >> Air circuit breakers |
| Object Classification Code | Q |
| UNSPSC | 39121615 |
| WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) |
| eClass | V11.1 : 27370409 |
| Feature Name | Feature Value |
|---|---|
| Rated permanent current Iu (EF001389) | 1600 A |
| Rated voltage (EF003977) | 690 V |
| Rated short-circuit breaking capacity Icu at 400 V, 50 Hz (EF007048) | 66 kA |
| Overload release current setting (EF002336) | 1600 A |
| Adjustment range short-term delayed short-circuit release (EF007129) | 16000 A |
| Adjustment range undelayed short-circuit release (EF007131) | 2400.0 A |
| Integrated earth fault protection (EF007296) | Yes |
| Type of electrical connection of main circuit (EF006819) | Connection at separate chassis part |
| Device construction (EF008240) | Built-in device slide-in technique (withdrawable) |
| Suitable for DIN rail (top hat rail) mounting (EF007250) | No |
| DIN rail (top hat rail) mounting optional (EF008904) | No |
| Number of auxiliary contacts as normally closed contact (EF001377) | 0 |
| Number of auxiliary contacts as normally open contact (EF001376) | 0 |
| Number of auxiliary contacts as change-over contact (EF003531) | 4 |
| With switched-off indicator (EF007006) | Yes |
| With integrated under voltage release (EF001390) | No |
| Number of poles (EF001391) | 3 |
| Position of connection for main current circuit (EF006671) | Connection at separate chassis part |
| Type of control element (EF006976) | Push button |
| Complete device with protection unit (EF008906) | Yes |
| Motor drive integrated (EF006697) | No |
| Motor drive optional (EF007386) | Yes |
| Degree of protection (IP) (EF005474) | IP30 |