View larger
1SDA073035R1
073035
ABB
1 Pcs.
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
| ABB EcoSolutions | |
|---|---|
| ABB EcoSolutions | Yes |
| ABB Site Meeting Group Waste To Landfill Target | UL 2799 Zero Waste To Landfill Validation available |
| End Of Life Disassembling Instructions | 9AKK108468A2361 |
| Environmental Product Declaration - EPD | 9AKK108468A1902 |
| 9AKK108468A1909 | |
| Extended Product Lifetime | Lifetime Extension Services are Offered |
| Recyclability Rate of the Product acc. to EN45555 | Design for Closing Resource Loops - Standard EN45555 - 79.1 % |
| Material Compliance | |
| REACH Declaration | 9AKK108466A1425 |
| RoHS Declaration | 9AKK108466A1424 |
| RoHS Information | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
| Conflict Minerals Reporting Template (CMRT) | 9AKK108467A5658 |
| Toxic Substances Control Act - TSCA | 9AKK108467A8326 |
| SCIP | 5ea49c09-eaf7-4eb3-bf91-27cf72e0bfce Italy |
| Simplified SCIP | 336e6278-7772-48ba-a1a1-39e4fed974ae Germany |
| f1c6f135-8eb8-4f92-a263-3b7aa53feddf France | |
| 3f1bb0bb-10e5-4f2e-bd17-937ac8f1d51f Spain | |
| 7f7b459b-0514-419e-aff6-056685244cbd Belgium | |
| fe7f83f1-286b-452e-b3e0-119defe14ab6 Hungary | |
| 19b3e7db-6cb1-43a3-8abc-f6c60bab9006 Sweden | |
| f96f4eaa-a3ab-49e3-8074-380a4b8a389e Finland | |
| bb12cb44-78b5-4cd9-a0a4-f80c1bf65a86 Greece | |
| 843a880d-f27c-4e0e-baf4-b80d41f84649 Estonia | |
| c1981b96-8b93-45ba-8c04-ae04fd4b8d82 Belgium | |
| d5c4aa37-ceac-4ce7-b346-6c1b55c153c3 Poland | |
| 56e66147-2590-4200-a0a9-4cf58a047c80 Hungary | |
| 73b5c393-53cc-4761-a3ec-76fba542145e Norway | |
| 44dbc549-44df-4382-8a23-a79b07399aaf Netherlands | |
| 2e7a4bf3-caf3-47e5-80bb-4ad544dc17eb Denmark | |
| c642f75e-4b14-4f63-9417-6b58d3f28052 Germany | |
| f4be6819-6985-497d-a434-7d4b8d27d8b1 Germany | |
| 61c9dc0b-3009-49ff-82b4-caa16908d209 Croatia | |
| f35bc8bc-a3d7-46fb-b6bf-991031270e6d Germany | |
| e0670e6d-7914-4751-b38a-30ef5692a25f Germany | |
| a380fb7c-8219-49a1-9a12-6a6d8b9a1b44 France | |
| f45c41e8-2edf-44c0-bbec-fd5f72dad1ec Sweden | |
| fe980ff6-d8e2-4b90-9cb8-25cc3b408455 Portugal | |
| 3b08ef98-744f-44f7-ba27-4ab1bd153218 Bulgaria | |
| e7710b15-0011-4cfc-959c-e677adc88df2 Poland | |
| 3024b61f-b2d2-41e0-9917-7c220bab725a Czech Republic | |
| cc20ee30-32a7-4935-bafa-939bfa7d203d Poland | |
| Environmental | |
| Environmental Information | 9AKK108467A6707 |
| Ordering | |
| Order Code US and Canada | ZBHTEKAE000A000000XX |
| EAN | 8015644768850 |
| Minimum Order Quantity | 1 piece |
| Customs Tariff Number | 85362090 |
| Dimensions | |
| Product Net Width | 407 mm |
| Product Net Height | 425 mm |
| Product Net Depth / Length | 383 mm |
| Product Net Weight | 55 kg |
| Container Information | |
| Package Level 1 Units | box 1 piece |
| Package Level 1 Width | 515 mm |
| Package Level 1 Height | 610 mm |
| Package Level 1 Depth / Length | 615 mm |
| Package Level 1 Gross Weight | 60 kg |
| Package Level 1 EAN | 8015644768850 |
| Additional Information | |
| Product Main Type | SACE Emax 2 |
| Product Name | Air Circuit Breaker |
| Product Type | Air Circuit Breaker |
| Version | W |
| CAD Dimensional Drawing | 1SDH001252R0432 |
| Technical | |
| Connecting Capacity | 1800 mm² |
| Current Type | AC |
| Electrical Durability | Ue =< 440 V 10000 cycle |
| Ue = 500 ... 690 V 8000 cycle | |
| 30 cycles per hour | |
| Mechanical Durability | 25000 cycle |
| 60 cycles per hour | |
| Neutral Pole Current ([%Iu]) | 100 % |
| Number of Poles | 4P |
| Power Loss | 450 W |
| Rated Current (In) | 2000 A |
| Rated Impulse Withstand Voltage (Uimp) | acc. to IEC 60947-2 12 kV |
| Rated Insulation Voltage (Ui) | AC 1000 V |
| Rated Operational Voltage | 690 V AC |
| Rated Service Short-Circuit Breaking Capacity (Ics) | (220 V AC) 100 kA |
| (230 V AC) 100 kA | |
| (380 V AC) 100 kA | |
| (400 V AC) 100 kA | |
| (415 V AC) 100 kA | |
| (440 V AC) 100 kA | |
| (500 V AC) 85 kA | |
| (660 V AC) 85 kA | |
| (690 V AC) 85 kA | |
| Rated Service Short-Circuit Breaking Capacity, in % of Icu (Ics) | 100 % |
| Rated Short-time Withstand Current Low Voltage (Icw) | for 1 s 85 kA |
| for 3 s 66 kA | |
| Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (400 V AC) 100 kA |
| (415 V AC) 100 kA | |
| (440 V AC) 100 kA | |
| (500 V AC) 85 kA | |
| (525 V AC) 85 kA | |
| (690 V AC) 85 kA | |
| Rated Uninterrupted Current (Iu) | 2000 A |
| Rated Voltage (Ur) | 690 V |
| Recommended Screw Driver | M12 |
| Release | Ekip Touch LSI |
| Release Type | EL |
| Short-Circuit Performance Level | H |
| Standards | IEC |
| Sub-type | E2.2 |
| Suitable for IT Networks | Yes, 690V |
| Certificates and Declarations | |
| ATEX Certificate | No certification needed |
| CSA Certificate | No certification needed |
| CSA Certificate (Intrinsic Safe) | No certification needed |
| Data Sheet, Technical Information | 1SDC200023D0209 |
| Declaration of Conformity - CE | 9AKK106713A5902 |
| EU Data Act Compliance Declaration | 1SDH002560A1001 |
| UL Certificate | No certification needed |
| VDE Certificate | No certification needed |
| Mechanical Drawings | 1SDH001000R0102 |
| Wiring Diagram | 1SDM000091R0001 |
| Instructions and Manuals | 1SDH001000R0002 |
| Instructions and Manuals (Part 2) | 1SDH001316R1002 |
| External Classifications and Standards | |
| ETIM 9 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
| ETIM 10 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
| IDEA Granular Category Code (IGCC) | 4926 >> Air circuit breakers |
| Object Classification Code | Q |
| UNSPSC | 39121615 |
| WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) |
| eClass | V11.1 : 27370409 |
| Feature Name | Feature Value |
|---|---|
| Rated permanent current Iu (EF001389) | 2000 A |
| Rated voltage (EF003977) | 690 V |
| Rated short-circuit breaking capacity Icu at 400 V, 50 Hz (EF007048) | 100 kA |
| Overload release current setting (EF002336) | 2000 A |
| Adjustment range short-term delayed short-circuit release (EF007129) | 1200.0 A |
| Adjustment range undelayed short-circuit release (EF007131) | 3000.0 A |
| Integrated earth fault protection (EF007296) | No |
| Type of electrical connection of main circuit (EF006819) | Connection at separate chassis part |
| Device construction (EF008240) | Built-in device slide-in technique (withdrawable) |
| Suitable for DIN rail (top hat rail) mounting (EF007250) | No |
| DIN rail (top hat rail) mounting optional (EF008904) | No |
| Number of auxiliary contacts as normally closed contact (EF001377) | 0 |
| Number of auxiliary contacts as normally open contact (EF001376) | 0 |
| Number of auxiliary contacts as change-over contact (EF003531) | 4 |
| With switched-off indicator (EF007006) | Yes |
| With integrated under voltage release (EF001390) | No |
| Number of poles (EF001391) | 4 |
| Position of connection for main current circuit (EF006671) | Connection at separate chassis part |
| Type of control element (EF006976) | Push button |
| Complete device with protection unit (EF008906) | Yes |
| Motor drive integrated (EF006697) | No |
| Motor drive optional (EF007386) | Yes |
| Degree of protection (IP) (EF005474) | IP30 |