View larger
1SDA071689R1
071689
ABB
1 Pcs.
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
| ABB EcoSolutions | |
|---|---|
| ABB EcoSolutions | Yes |
| ABB Site Meeting Group Waste To Landfill Target | UL 2799 Zero Waste To Landfill Validation available |
| End Of Life Disassembling Instructions | 9AKK108468A2361 |
| Environmental Product Declaration - EPD | 9AKK108468A1902 |
| 9AKK108468A1909 | |
| Extended Product Lifetime | Lifetime Extension Services are Offered |
| Recyclability Rate of the Product acc. to EN45555 | Design for Closing Resource Loops - Standard EN45555 - 79.1 % |
| Material Compliance | |
| REACH Declaration | 9AKK108466A1425 |
| RoHS Declaration | 9AKK108466A1424 |
| RoHS Information | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
| Conflict Minerals Reporting Template (CMRT) | 9AKK108467A5658 |
| Toxic Substances Control Act - TSCA | 9AKK108467A8326 |
| SCIP | 497eb8fd-6486-46c2-93db-55db8b080e27 Italy |
| Simplified SCIP | c3a54d35-f4b4-4944-b880-b2153362f34c Finland |
| bb2667d4-385b-4168-8d6e-daa59ff6a884 Poland | |
| 0e6a39d0-4aea-4671-b14e-9aeef9f442d8 Sweden | |
| 756435ba-a146-4765-995e-fce0b6a16b11 Poland | |
| 33c75aa0-dd53-4b4f-ab77-dcec93d1889c Spain | |
| 47dcaa65-ffac-4eab-9248-0b6dcbc6b06d Belgium | |
| 8a901f5a-c08e-42ab-b151-b1b0f8e5a938 Poland | |
| c84c6da9-1930-49bc-afbf-b8da67fbf12c Norway | |
| 200603c8-2399-4794-bb28-0240dba41d95 Germany | |
| 5043ecac-3223-4ec7-ae18-e306b95d83a6 Germany | |
| cd842709-69b1-4da0-93bf-2d5aea80fc83 Sweden | |
| da639206-1c41-4355-bcc4-7b55ee43efc1 France | |
| 463fd2c5-0045-4666-9fe1-3d6e41f343f9 Netherlands | |
| c17c4697-aee2-4762-88c8-354a4317b0e5 Czech Republic | |
| b2bfda40-565e-4c92-8925-0bbc2118280b Croatia | |
| e9c01a8f-8b69-4674-81e4-b89fd584ed76 Bulgaria | |
| cea9ba0e-9406-480e-a218-782a784d75a2 Greece | |
| e5713330-e0ab-485a-ab4f-6d093da2ef6d Denmark | |
| a2cd91b7-e8fb-4149-9a46-0471f3af319e Portugal | |
| 6a56576f-6dcf-4546-bc24-08b1be34cd72 Hungary | |
| 2c1f6f43-8c15-4512-bb10-e866254fe2cd Germany | |
| 313ccde7-91a4-424c-aeab-8b1b15f817a1 Belgium | |
| dd75163d-0621-43ea-a847-32399200281b France | |
| e9c6f461-4fe4-44bc-a4a9-a230411eae9e Germany | |
| c492ba5c-871c-4d27-8b81-67faf67ee6be Germany | |
| Environmental | |
| Environmental Information | 9AKK108467A6707 |
| Ordering | |
| Order Code US and Canada | ZBHTEKBK200A000000XX |
| EAN | 8015644755393 |
| Minimum Order Quantity | 1 piece |
| Customs Tariff Number | 85362090 |
| Dimensions | |
| Product Net Width | 366 mm |
| Product Net Height | 371 mm |
| Product Net Depth / Length | 270 mm |
| Product Net Weight | 53 kg |
| Container Information | |
| Package Level 1 Units | box 1 piece |
| Package Level 1 Width | 515 mm |
| Package Level 1 Height | 610 mm |
| Package Level 1 Depth / Length | 615 mm |
| Package Level 1 Gross Weight | 58 kg |
| Package Level 1 EAN | 8015644755393 |
| Additional Information | |
| Product Main Type | SACE Emax 2 |
| Product Name | Air Circuit Breaker |
| Product Type | Air Circuit Breaker |
| Version | F |
| CAD Dimensional Drawing | 1SDH001252R0123 |
| Technical | |
| Connecting Capacity | 1800 mm² |
| Current Type | AC |
| Electrical Durability | Ue =< 440 V 10000 cycle |
| Ue = 500 ... 690 V 8000 cycle | |
| 30 cycles per hour | |
| Mechanical Durability | 25000 cycle |
| 60 cycles per hour | |
| Neutral Pole Current ([%Iu]) | 100 % |
| Number of Poles | 4P |
| Power Loss | 212 W |
| Rated Current (In) | 2000 A |
| Rated Impulse Withstand Voltage (Uimp) | acc. to IEC 60947-2 12 kV |
| Rated Insulation Voltage (Ui) | AC 1000 V |
| Rated Operational Voltage | 690 V AC |
| Rated Service Short-Circuit Breaking Capacity (Ics) | (220 V AC) 100 kA |
| (230 V AC) 100 kA | |
| (380 V AC) 100 kA | |
| (400 V AC) 100 kA | |
| (415 V AC) 100 kA | |
| (440 V AC) 100 kA | |
| (500 V AC) 85 kA | |
| (660 V AC) 85 kA | |
| (690 V AC) 85 kA | |
| Rated Service Short-Circuit Breaking Capacity, in % of Icu (Ics) | 100 % |
| Rated Short-time Withstand Current Low Voltage (Icw) | for 1 s 85 kA |
| for 3 s 66 kA | |
| Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (400 V AC) 100 kA |
| (415 V AC) 100 kA | |
| (440 V AC) 100 kA | |
| (500 V AC) 85 kA | |
| (525 V AC) 85 kA | |
| (690 V AC) 85 kA | |
| Rated Uninterrupted Current (Iu) | 2000 A |
| Rated Voltage (Ur) | 690 V |
| Recommended Screw Driver | M12 |
| Release | Ekip Hi-Touch LSIG |
| Release Type | EL |
| Short-Circuit Performance Level | H |
| Standards | IEC |
| Sub-type | E2.2 |
| Suitable for IT Networks | Yes, 690V |
| Terminal Connection Type | Rear flat Horizontal |
| Terminal Type | Bolt |
| Tightening Torque | 70 N·m |
| Certificates and Declarations | |
| ATEX Certificate | No certification needed |
| CSA Certificate | No certification needed |
| CSA Certificate (Intrinsic Safe) | No certification needed |
| Data Sheet, Technical Information | 1SDC200023D0209 |
| Declaration of Conformity - CE | 9AKK106713A5902 |
| EU Data Act Compliance Declaration | 1SDH002560A1001 |
| UL Certificate | No certification needed |
| VDE Certificate | No certification needed |
| Mechanical Drawings | 1SDH001000R0100 |
| Wiring Diagram | 1SDM000091R0001 |
| Instructions and Manuals | 1SDH001000R0002 |
| Instructions and Manuals (Part 2) | 1SDH001316R1002 |
| External Classifications and Standards | |
| ETIM 9 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
| ETIM 10 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
| IDEA Granular Category Code (IGCC) | 4926 >> Air circuit breakers |
| Object Classification Code | Q |
| UNSPSC | 39121615 |
| WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) |
| eClass | V11.1 : 27370409 |