View larger
1SDA071616R1
071616
ABB
1 Pcs.
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
| ABB EcoSolutions | |
|---|---|
| ABB EcoSolutions | Yes |
| ABB Site Meeting Group Waste To Landfill Target | UL 2799 Zero Waste To Landfill Validation available |
| End Of Life Disassembling Instructions | 9AKK108468A2361 |
| Environmental Product Declaration - EPD | 9AKK108468A1902 |
| 9AKK108468A1909 | |
| Extended Product Lifetime | Lifetime Extension Services are Offered |
| Recyclability Rate of the Product acc. to EN45555 | Design for Closing Resource Loops - Standard EN45555 - 79.1 % |
| Material Compliance | |
| REACH Declaration | 9AKK108466A1425 |
| RoHS Declaration | 9AKK108466A1424 |
| RoHS Information | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
| Conflict Minerals Reporting Template (CMRT) | 9AKK108467A5658 |
| Toxic Substances Control Act - TSCA | 9AKK108467A8326 |
| SCIP | 5db9272f-d385-4a4a-a0e6-73274e7613b2 Italy |
| Simplified SCIP | e37504eb-5819-4400-90f8-d3600caf9042 Poland |
| 2702db69-0e01-40de-b4b4-8a8728498dbe Germany | |
| ac767638-06cb-44b9-8385-7bf7f3ecba34 France | |
| d31b5142-dea6-4403-a92f-557b883cc512 Spain | |
| 1d9dc29d-a6cb-40fd-8d88-97ce0880e83e Belgium | |
| 7977724f-b919-4dd2-ab09-5472ef9d52a3 Poland | |
| 6ea62607-f2a7-41cb-a88e-59140d19e5a2 Finland | |
| b52e58f3-5277-401c-b0e5-612ee1001a12 Czech Republic | |
| 8b0a5c38-2ce1-4e5b-aa05-34415d2309f4 Hungary | |
| 03e97960-e212-40d4-a1ac-c7e76cc6f0d8 Netherlands | |
| a8fc3df7-2849-445d-a3e3-01946673cd5e Hungary | |
| f80489b1-9261-482c-943d-3e1a371eae30 Estonia | |
| 67dacb9e-1089-4ad6-a2be-4bc8108e34d5 Sweden | |
| c2e0179a-7944-4aad-8f9d-03d3dca477b5 France | |
| cb0be72f-1d6b-4964-a221-b93cb635f55a Bulgaria | |
| c81f3b9a-c14d-4053-b586-49fcac32ffa7 Poland | |
| 70054365-d51a-4b2c-998b-1224bebcb35b Greece | |
| 357ac243-7790-46c0-bd29-c5728c7b3375 Germany | |
| 4edb563d-9fa4-42c8-8b71-0c9b10c7bb6b Germany | |
| 29814934-70ae-4d09-9f99-1c8da5e0641b Sweden | |
| 71f07e39-2ef0-4637-b63a-05b478f9764d Portugal | |
| 25a18d0f-bcf1-404d-93f0-6d0552cb73cd Belgium | |
| 738ae1a0-ef38-4c69-846f-11fe5f33f53f Norway | |
| 03a47ac4-f0db-4a08-93e7-5923e52002a3 Germany | |
| e6fa8ed4-e093-4ef4-80f9-d70464409e04 Denmark | |
| 6fd1c781-be54-47cd-b640-2d83b9002e9b Croatia | |
| 0df77ff9-6fed-403d-90a8-009ac45bed0a Germany | |
| Environmental | |
| Environmental Information | 9AKK108467A6707 |
| Ordering | |
| Order Code US and Canada | ZBBSEJBF000A000000XX |
| EAN | 8015644754662 |
| Minimum Order Quantity | 1 piece |
| Customs Tariff Number | 85362090 |
| Dimensions | |
| Product Net Width | 366 mm |
| Product Net Height | 371 mm |
| Product Net Depth / Length | 270 mm |
| Product Net Weight | 53 kg |
| Container Information | |
| Package Level 1 Units | box 1 piece |
| Package Level 1 Width | 515 mm |
| Package Level 1 Height | 610 mm |
| Package Level 1 Depth / Length | 615 mm |
| Package Level 1 Gross Weight | 58 kg |
| Package Level 1 EAN | 8015644754662 |
| Additional Information | |
| Product Main Type | SACE Emax 2 |
| Product Name | Air Circuit Breaker |
| Product Type | Air Circuit Breaker |
| Version | F |
| CAD Dimensional Drawing | 1SDH001252R0123 |
| Technical | |
| Connecting Capacity | 1200 mm² |
| Current Type | AC |
| Electrical Durability | Ue =< 440 V 12000 cycle |
| Ue = 500 ... 690 V 10000 cycle | |
| 30 cycles per hour | |
| Mechanical Durability | 25000 cycle |
| 60 cycles per hour | |
| Neutral Pole Current ([%Iu]) | 100 % |
| Number of Poles | 4P |
| Power Loss | 136 W |
| Rated Current (In) | 1600 A |
| Rated Impulse Withstand Voltage (Uimp) | acc. to IEC 60947-2 12 kV |
| Rated Insulation Voltage (Ui) | AC 1000 V |
| Rated Operational Voltage | 690 V AC |
| Rated Service Short-Circuit Breaking Capacity (Ics) | (220 V AC) 42 kA |
| (230 V AC) 42 kA | |
| (380 V AC) 42 kA | |
| (400 V AC) 42 kA | |
| (415 V AC) 42 kA | |
| (440 V AC) 42 kA | |
| Rated Service Short-Circuit Breaking Capacity, in % of Icu (Ics) | 100 % |
| Rated Short-time Withstand Current Low Voltage (Icw) | for 1 s 42 kA |
| for 3 s 42 kA | |
| Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (400 V AC) 42 kA |
| (415 V AC) 42 kA | |
| (440 V AC) 42 kA | |
| (500 V AC) 42 kA | |
| (525 V AC) 42 kA | |
| (690 V AC) 42 kA | |
| Rated Uninterrupted Current (Iu) | 1600 A |
| Rated Voltage (Ur) | 690 V |
| Recommended Screw Driver | M12 |
| Release | Ekip Touch LSIG |
| Release Type | EL |
| Short-Circuit Performance Level | B |
| Standards | IEC |
| Sub-type | E2.2 |
| Suitable for IT Networks | Yes, 690V |
| Terminal Connection Type | Rear flat Horizontal |
| Terminal Type | Bolt |
| Tightening Torque | 70 N·m |
| Certificates and Declarations | |
| ATEX Certificate | No certification needed |
| CSA Certificate | No certification needed |
| CSA Certificate (Intrinsic Safe) | No certification needed |
| Data Sheet, Technical Information | 1SDC200023D0209 |
| Declaration of Conformity - CE | 9AKK106713A5902 |
| EU Data Act Compliance Declaration | 1SDH002560A1001 |
| UL Certificate | No certification needed |
| VDE Certificate | No certification needed |
| Mechanical Drawings | 1SDH001000R0100 |
| Wiring Diagram | 1SDM000091R0001 |
| Instructions and Manuals | 1SDH001000R0002 |
| Instructions and Manuals (Part 2) | 1SDH001316R1002 |
| External Classifications and Standards | |
| ETIM 9 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
| ETIM 10 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
| IDEA Granular Category Code (IGCC) | 4926 >> Air circuit breakers |
| Object Classification Code | Q |
| UNSPSC | 39121615 |
| WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) |
| eClass | V11.1 : 27370409 |