View larger
1SDA071614R1
071614
ABB
1 Pcs.
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
| ABB EcoSolutions | |
|---|---|
| ABB EcoSolutions | Yes |
| ABB Site Meeting Group Waste To Landfill Target | UL 2799 Zero Waste To Landfill Validation available |
| End Of Life Disassembling Instructions | 9AKK108468A2361 |
| Environmental Product Declaration - EPD | 9AKK108468A1902 |
| 9AKK108468A1909 | |
| Extended Product Lifetime | Lifetime Extension Services are Offered |
| Recyclability Rate of the Product acc. to EN45555 | Design for Closing Resource Loops - Standard EN45555 - 79.1 % |
| Material Compliance | |
| REACH Declaration | 9AKK108466A1425 |
| RoHS Declaration | 9AKK108466A1424 |
| RoHS Information | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
| Conflict Minerals Reporting Template (CMRT) | 9AKK108467A5658 |
| Toxic Substances Control Act - TSCA | 9AKK108467A8326 |
| SCIP | b76917b2-3118-4ae8-ab6c-c9b187febfa6 Italy |
| Simplified SCIP | 17322e66-82e5-4e80-a588-9af3ea7871b8 Germany |
| c2b30478-6474-46dd-b4b6-a00d4ec5a3b9 Poland | |
| f2774f31-c183-46bb-8542-f73eb7ac6da4 Hungary | |
| ae934500-898a-46a2-a034-8846a9ab861b Spain | |
| 14baefdb-66da-4641-8039-562cc11d94ff Belgium | |
| f10db918-0aff-4b52-81ff-fdbc162112b7 France | |
| 7dd93e35-c0c9-4503-aea3-d680aa23ce58 Finland | |
| 65d39d35-3aa0-4c80-89f5-36a25472bb86 Netherlands | |
| b9971b0d-963d-450b-9253-71c836049e9d Poland | |
| fc96341e-7731-492c-88a2-26015e451d4f Norway | |
| fb4d8f21-d2eb-4fbb-a8c6-282d1f685311 Hungary | |
| f6db9496-b6e3-45e9-a662-c8d5d348db69 Sweden | |
| 4ed7775f-f4c6-4574-af96-c07f319b0dec Greece | |
| bf0ff894-6577-4e6c-be69-23309283ad58 Estonia | |
| deb315dd-ded4-48bc-8229-8c8b3ff97349 Germany | |
| a9385cf2-5650-4140-a4af-dea15d786d26 Bulgaria | |
| 21db4c19-032e-4de6-81c7-0fcda57bd3f6 Belgium | |
| 80b2a29b-6108-4942-b26f-a9d2ec646c8d Germany | |
| 334179a4-1c48-4df4-8233-97808e3a3add Denmark | |
| 3ef1fcc9-d97f-49e3-8fb2-08125f50be1f Germany | |
| 5790bf8f-cd8d-4738-b7a3-2bcdb91f84b8 Germany | |
| 5d547f13-6757-413b-a56e-6061ca23dfe1 France | |
| c389bb78-5d26-4788-b332-d6a9d27a65ee Croatia | |
| 376bbc87-4e71-4d70-b0f6-e3a486337723 Poland | |
| ac8bdc07-7735-4b63-946c-9eb901df7885 Sweden | |
| a7eb9686-583c-4d70-9dc9-7103942efb13 Portugal | |
| 53addd3d-9b41-4260-a04b-435aee12e385 Czech Republic | |
| Environmental | |
| Environmental Information | 9AKK108467A6707 |
| Ordering | |
| Order Code US and Canada | ZBBSEJBD000A000000XX |
| EAN | 8015644754648 |
| Minimum Order Quantity | 1 piece |
| Customs Tariff Number | 85362090 |
| Dimensions | |
| Product Net Width | 366 mm |
| Product Net Height | 371 mm |
| Product Net Depth / Length | 270 mm |
| Product Net Weight | 53 kg |
| Container Information | |
| Package Level 1 Units | box 1 piece |
| Package Level 1 Width | 515 mm |
| Package Level 1 Height | 610 mm |
| Package Level 1 Depth / Length | 615 mm |
| Package Level 1 Gross Weight | 58 kg |
| Package Level 1 EAN | 8015644754648 |
| Additional Information | |
| Product Main Type | SACE Emax 2 |
| Product Name | Air Circuit Breaker |
| Product Type | Air Circuit Breaker |
| Version | F |
| CAD Dimensional Drawing | 1SDH001252R0123 |
| Technical | |
| Connecting Capacity | 1200 mm² |
| Current Type | AC |
| Electrical Durability | Ue =< 440 V 12000 cycle |
| Ue = 500 ... 690 V 10000 cycle | |
| 30 cycles per hour | |
| Mechanical Durability | 25000 cycle |
| 60 cycles per hour | |
| Neutral Pole Current ([%Iu]) | 100 % |
| Number of Poles | 4P |
| Power Loss | 136 W |
| Rated Current (In) | 1600 A |
| Rated Impulse Withstand Voltage (Uimp) | acc. to IEC 60947-2 12 kV |
| Rated Insulation Voltage (Ui) | AC 1000 V |
| Rated Operational Voltage | 690 V AC |
| Rated Service Short-Circuit Breaking Capacity (Ics) | (220 V AC) 42 kA |
| (230 V AC) 42 kA | |
| (380 V AC) 42 kA | |
| (400 V AC) 42 kA | |
| (415 V AC) 42 kA | |
| (440 V AC) 42 kA | |
| Rated Service Short-Circuit Breaking Capacity, in % of Icu (Ics) | 100 % |
| Rated Short-time Withstand Current Low Voltage (Icw) | for 1 s 42 kA |
| for 3 s 42 kA | |
| Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (400 V AC) 42 kA |
| (415 V AC) 42 kA | |
| (440 V AC) 42 kA | |
| (500 V AC) 42 kA | |
| (525 V AC) 42 kA | |
| (690 V AC) 42 kA | |
| Rated Uninterrupted Current (Iu) | 1600 A |
| Rated Voltage (Ur) | 690 V |
| Recommended Screw Driver | M12 |
| Release | Ekip Touch LI |
| Release Type | EL |
| Short-Circuit Performance Level | B |
| Standards | IEC |
| Sub-type | E2.2 |
| Suitable for IT Networks | Yes, 690V |
| Terminal Connection Type | Rear flat Horizontal |
| Terminal Type | Bolt |
| Tightening Torque | 70 N·m |
| Certificates and Declarations | |
| ATEX Certificate | No certification needed |
| CSA Certificate | No certification needed |
| CSA Certificate (Intrinsic Safe) | No certification needed |
| Data Sheet, Technical Information | 1SDC200023D0209 |
| Declaration of Conformity - CE | 9AKK106713A5902 |
| EU Data Act Compliance Declaration | 1SDH002560A1001 |
| UL Certificate | No certification needed |
| VDE Certificate | No certification needed |
| Mechanical Drawings | 1SDH001000R0100 |
| Wiring Diagram | 1SDM000091R0001 |
| Instructions and Manuals | 1SDH001000R0002 |
| Instructions and Manuals (Part 2) | 1SDH001316R1002 |
| External Classifications and Standards | |
| ETIM 9 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
| ETIM 10 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
| IDEA Granular Category Code (IGCC) | 4926 >> Air circuit breakers |
| Object Classification Code | Q |
| UNSPSC | 39121615 |
| WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) |
| eClass | V11.1 : 27370409 |