1SDA055763R1 ABB E1N 1600 PR122/P-LI In 1600A 3p F HR
1SDA055763R1
055763
ABB
1 Pcs.
Automation > Power circuit-breaker for trafo/generator/installation protection
Service Breakers
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
An ABB air circuit breaker provides high-capacity current interruption and system isolation for heavy industrial power distribution grids. Engineers specify these units for main switchboards to maintain safe operation and prevent catastrophic electrical failures. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- REACH Declaration: 9AKK108466A1425
- RoHS Declaration: 9AKK108466A1424
- RoHS Information: Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
- Conflict Minerals Reporting Template (CMRT): Document availability on demand
- SCIP: ae1dbe4c-8262-4813-ab48-faff3155522c Italy
- Simplified SCIP: 43d9c245-f3d8-4ef9-a578-a334b426dd92 Estonia
- Environmental Information: 9AKK10103A6076
- EAN: 8015644571030
- Minimum Order Quantity: 1 piece
- Customs Tariff Number: 85362090
- Product Net Width: 296 mm
- Product Net Height: 418 mm
- Product Net Depth / Length: 302 mm
- Product Net Weight: 40 kg
- Package Level 1 Units: 1 piece
- Package Level 1 Width: 515 mm
More info
▲| Material Compliance | |
|---|---|
| REACH Declaration | 9AKK108466A1425 |
| RoHS Declaration | 9AKK108466A1424 |
| RoHS Information | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
| Conflict Minerals Reporting Template (CMRT) | Document availability on demand |
| SCIP | ae1dbe4c-8262-4813-ab48-faff3155522c Italy |
| Simplified SCIP | 43d9c245-f3d8-4ef9-a578-a334b426dd92 Estonia |
| 85abc78c-df6a-41fc-b2bd-e04bbac21081 Sweden | |
| fb38ac74-cb31-4514-ab1d-93bf85c82a1c Spain | |
| 836d9057-3629-4f3e-82d6-633e65cf87e0 Poland | |
| 708507a2-695f-473b-8a2c-95da0409538a Sweden | |
| 893b52bf-a857-43e3-aec5-e0b2c5f38ea5 France | |
| 0ffebe1b-2102-4f98-95e7-1a2d89a1d158 Germany | |
| fba62237-22d1-4322-849d-9d238bdcd44b France | |
| 7dd50116-e9e9-4fd0-befa-b6a610fd8111 Hungary | |
| 74deb1e0-7f1e-475c-a31b-0835aa598873 Germany | |
| 9e7d57f0-1db8-4eb4-b097-e6bb111575ec Belgium | |
| 66b95026-bd62-4163-bf66-589942650c9c Greece | |
| 06848f48-a7a3-46cd-a549-5222c9e98f36 Germany | |
| 5346245c-89df-4170-9cc8-57078506e282 Bulgaria | |
| 103bf210-98ff-4798-8727-d17c5d4925e1 Denmark | |
| 2842d0ff-ee97-40b2-92d6-5e723e1cd6ad Germany | |
| 44886603-ba59-4c26-bee8-92ba76dd0e1d Germany | |
| f4a63e12-0b93-4271-8db5-3c6df7501a87 Poland | |
| c63641d8-426b-4c8b-9341-60d38fb97a4f Norway | |
| bbe4bfee-2cee-46a1-930a-4152b4b6a20b Finland | |
| 2861c543-0875-4d8b-b2ae-e304666af1ad Hungary | |
| 6ebc3f6d-93fe-4834-91d0-a4ec1fce4fb0 Netherlands | |
| 3b596d1a-f12f-4a54-b093-e571094aceea Portugal | |
| 395ee919-b70e-4633-ab4e-305f1fef02ff Croatia | |
| dfcfa345-f55b-4fb5-b55f-45c6b0db227f Poland | |
| d7916830-b0b6-47b2-9d13-6513924777e9 Belgium | |
| 339b69f0-9841-404b-8166-20040bb70f43 Czech Republic | |
| Environmental | |
| Environmental Information | 9AKK10103A6076 |
| Ordering | |
| EAN | 8015644571030 |
| Minimum Order Quantity | 1 piece |
| Customs Tariff Number | 85362090 |
| Dimensions | |
| Product Net Width | 296 mm |
| Product Net Height | 418 mm |
| Product Net Depth / Length | 302 mm |
| Product Net Weight | 40 kg |
| Container Information | |
| Package Level 1 Units | 1 piece |
| Package Level 1 Width | 515 mm |
| Package Level 1 Height | 600 mm |
| Package Level 1 Depth / Length | 515 mm |
| Package Level 1 Gross Weight | 50 kg |
| Package Level 1 EAN | 8015644571030 |
| Additional Information | |
| Product Main Type | SACE Emax |
| Product Name | Air Circuit Breaker |
| Product Type | Air Circuit Breaker |
| Version | F |
| Technical | |
| Current Type | AC |
| Electrical Durability | Ue =< 440 V 10000 cycle |
| Ue = 500 ... 690 V 8000 cycle | |
| 30 cycles per hour | |
| Mechanical Durability | 25000 cycle |
| 60 cycles per hour | |
| Number of Poles | 3P |
| Power Loss | 253 W |
| Rated Current (In) | 1600 A |
| Rated Impulse Withstand Voltage (Uimp) | 12 kV |
| Rated Insulation Voltage (Ui) | 1000 V |
| Rated Operational Current (Ie) | 1600 A |
| Rated Operational Voltage | 690 V AC |
| Rated Service Short-Circuit Breaking Capacity (Ics) | (220 V AC) 50 kA |
| (230 V AC) 50 kA | |
| (400 V AC) 50 kA | |
| (415 V AC) 50 kA | |
| (440 V AC) 50 kA | |
| (500 V AC) 50 kA | |
| (660 V AC) 50 kA | |
| (380 V AC) 50 kA | |
| (690 V AC) 50 kA | |
| Rated Short-time Withstand Current Low Voltage (Icw) | for 1 s 50 kA |
| for 3 s 36 kA | |
| Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (220 V AC) 50 kA |
| (230 V AC) 50 kA | |
| (400 V AC) 50 kA | |
| (415 V AC) 50 kA | |
| (440 V AC) 50 kA | |
| (500 V AC) 50 kA | |
| (660 V AC) 50 kA | |
| (380 V AC) 50 kA | |
| (690 V AC) 50 kA | |
| Rated Uninterrupted Current (Iu) | 1600 A |
| Rated Voltage (Ur) | 690 V |
| Release | PR122/P-LI |
| Release Type | EL |
| Short-Circuit Performance Level | N |
| Standards | IEC |
| Sub-type | E1 |
| Terminal Connection Type | Fixed Circuit-Breakers |
| Rear flat Horizontal | |
| Certificates and Declarations | |
| Data Sheet, Technical Information | 1SDC200006D0209 |
| Declaration of Conformity - CE | 1SDL000165R0013 |
| Instructions and Manuals | 1SDH000460R0002 |
| 1SDH000460R0102 | |
| External Classifications and Standards | |
| Object Classification Code | Q |
| UNSPSC | 39120000 |
| WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) |