View larger
1SDA070692R1
070692
ABB
1 Pcs.
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
| ABB EcoSolutions | |
|---|---|
| ABB EcoSolutions | Yes |
| ABB Site Meeting Group Waste To Landfill Target | UL 2799 Zero Waste To Landfill Validation available |
| End Of Life Disassembling Instructions | 9AKK108468A2360 |
| Environmental Product Declaration - EPD | 9AKK108468A1900 |
| 9AKK108468A3028 | |
| Extended Product Lifetime | Lifetime Extension Services are Offered |
| Recyclability Rate of the Product acc. to EN45555 | Design for Closing Resource Loops - Standard EN45555 - 76.4 % |
| Material Compliance | |
| REACH Declaration | 9AKK108466A1425 |
| RoHS Declaration | 9AKK108466A1424 |
| RoHS Information | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
| Conflict Minerals Reporting Template (CMRT) | 9AKK108467A5658 |
| Toxic Substances Control Act - TSCA | 9AKK108467A8326 |
| SCIP | 3d7d4cbb-8534-43b6-bbef-ec2860286cb7 Italy |
| Simplified SCIP | a62ec404-db0c-463e-b156-31fe70253a3f Belgium |
| f63ec70f-ae27-401a-bf39-1acfb788a8d5 Hungary | |
| 75639fc9-f633-4f4f-afae-9a23a124de1d Spain | |
| a83d6d41-51f8-4f4c-b3fc-e3ce5b1f0da8 France | |
| 9f89620d-dbab-4527-bad0-fb374dde9754 France | |
| 89eddfa2-0355-4c40-99ab-61533c6bc4d2 Germany | |
| 569429a3-8f3e-4b01-98c7-79757e9f2408 Germany | |
| 74f92646-6c73-4759-97ce-532c130ac749 Poland | |
| c484eec5-0513-4832-a090-a9b4cbbdd32a Germany | |
| 0e4c1425-75aa-4848-8ac1-40bd7cdca710 Norway | |
| 8d7ad42a-2be5-43ab-8c30-a6dcea2ef6b5 Finland | |
| 528b3246-ea0c-4ff7-851f-709bf2233ac5 Germany | |
| 9733657b-6efd-428f-ba67-0be4128fe172 Belgium | |
| a5ecb447-48de-444a-a83d-175934750bf7 Netherlands | |
| 9a5b1ea1-d929-47d4-9089-db40eb33ae58 Hungary | |
| 933f168a-29ef-4436-a415-da65265bf012 Czech Republic | |
| 50c5def5-8683-4fab-967e-d671134dc01b Poland | |
| 086a37e0-e7c7-4353-bbf6-8319a89b9726 Denmark | |
| 490e61f7-a1c1-4b9b-92ed-7ff0f1ee0d56 Germany | |
| 11d221fe-82e2-436a-902e-6df70b07ccc2 Croatia | |
| b369d939-1c17-42fb-b717-b697ed6305e5 Poland | |
| 6a22e741-6567-4d92-8e48-60675797448f Sweden | |
| 09507c00-4aaf-49d0-a50c-fc0f54286d95 Bulgaria | |
| c14ff619-d79f-4dd6-8581-fc58a34b1ad9 Greece | |
| 8e2ae7cb-a3c2-4395-a28f-d877362d735c Portugal | |
| 818f80e2-6fdd-49b9-a411-d757362aaea8 Estonia | |
| 5cdb3246-e109-4567-818b-595e95882a01 Sweden | |
| Environmental | |
| Environmental Information | 9AKK108467A6707 |
| Ordering | |
| Order Code US and Canada | Z1NMECBB000A000000XX |
| EAN | 8015644745424 |
| Minimum Order Quantity | 1 piece |
| Customs Tariff Number | 85362090 |
| Dimensions | |
| Product Net Width | 210 mm |
| Product Net Height | 296 mm |
| Product Net Depth / Length | 183 mm |
| Product Net Weight | 14 kg |
| Container Information | |
| Package Level 1 Units | box 1 piece |
| Package Level 1 Width | 270 mm |
| Package Level 1 Height | 350 mm |
| Package Level 1 Depth / Length | 330 mm |
| Package Level 1 Gross Weight | 16 kg |
| Package Level 1 EAN | 8015644745424 |
| Additional Information | |
| Product Main Type | SACE Emax 2 |
| Product Name | Air Circuit Breaker |
| Product Type | Air Circuit Breaker |
| Version | F |
| Technical | |
| Connecting Capacity | 120 mm² |
| Current Type | AC |
| Electrical Durability | Ue =< 440 V 8000 cycle |
| Ue = 500 ... 690 V 8000 cycle | |
| 30 cycles per hour | |
| Mechanical Durability | 20000 cycle |
| 60 cycles per hour | |
| Number of Poles | 3P |
| Power Loss | 31 W |
| Rated Current (In) | 250 A |
| Rated Impulse Withstand Voltage (Uimp) | acc. to IEC 60947-2 12 kV |
| Rated Insulation Voltage (Ui) | AC 1000 V |
| Rated Operational Voltage | 690 V AC |
| Rated Service Short-Circuit Breaking Capacity (Ics) | (220 V AC) 50 kA |
| (230 V AC) 50 kA | |
| (380 V AC) 50 kA | |
| (400 V AC) 50 kA | |
| (415 V AC) 50 kA | |
| (440 V AC) 50 kA | |
| (500 V AC) 50 kA | |
| (660 V AC) 50 kA | |
| (690 V AC) 50 kA | |
| Rated Service Short-Circuit Breaking Capacity, in % of Icu (Ics) | 100 % |
| Rated Short-time Withstand Current Low Voltage (Icw) | for 1 s 50 kA |
| for 3 s 30 kA | |
| Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (400 V AC) 66 kA |
| (415 V AC) 66 kA | |
| (440 V AC) 66 kA | |
| (500 V AC) 50 kA | |
| (525 V AC) 50 kA | |
| (690 V AC) 50 kA | |
| Rated Uninterrupted Current (Iu) | 250 A |
| Rated Voltage (Ur) | 690 V |
| Recommended Screw Driver | M12 |
| Release | Ekip Dip LSI |
| Release Type | EL |
| Short-Circuit Performance Level | N |
| Standards | IEC |
| Sub-type | E1.2 |
| Suitable for IT Networks | Yes, 690V |
| Terminal Connection Type | Front |
| Certificates and Declarations | |
| Data Sheet, Technical Information | 1SDC200023D0209 |
| Declaration of Conformity - CE | 9AKK106713A5546 |
| EU Data Act Compliance Declaration | 1SDH002560A1001 |
| Instructions and Manuals | 1SDH000999R0002 |
| External Classifications and Standards | |
| ETIM 9 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
| ETIM 10 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
| IDEA Granular Category Code (IGCC) | 4926 >> Air circuit breakers |
| Object Classification Code | Q |
| UNSPSC | 39121615 |
| WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) |