View larger
1SDA071512R1
071512
ABB
1 Pcs.
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
| ABB EcoSolutions | |
|---|---|
| ABB EcoSolutions | Yes |
| ABB Site Meeting Group Waste To Landfill Target | UL 2799 Zero Waste To Landfill Validation available |
| End Of Life Disassembling Instructions | 9AKK108468A2360 |
| Environmental Product Declaration - EPD | 9AKK108468A1900 |
| 9AKK108468A3028 | |
| Extended Product Lifetime | Lifetime Extension Services are Offered |
| Recyclability Rate of the Product acc. to EN45555 | Design for Closing Resource Loops - Standard EN45555 - 76.4 % |
| Material Compliance | |
| REACH Declaration | 9AKK108466A1425 |
| RoHS Declaration | 9AKK108466A1424 |
| RoHS Information | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
| Conflict Minerals Reporting Template (CMRT) | 9AKK108467A5658 |
| Toxic Substances Control Act - TSCA | 9AKK108467A8326 |
| SCIP | cd77eb44-4c5a-40ed-ba58-6a4669f9ba39 China |
| Simplified SCIP | 9d593f9d-1963-41c1-b8e4-52d573dfe4c4 France |
| f212a843-af55-4bea-832e-c98a29be476f Sweden | |
| af0a00d9-104c-40e0-bc86-3aa351e2f89d Poland | |
| 3bafacfb-c1fc-4d82-8a1e-652c171a4d77 Belgium | |
| e151e4f4-e75e-4855-82a2-159f8251d840 Spain | |
| 34ccd810-87a1-4462-8022-95fe94c2a3c3 Hungary | |
| 38c0d049-5b38-4efe-ade8-c75fca836054 Croatia | |
| 3b952e54-4bbe-40ed-8ef7-7d0a1dbe382f Germany | |
| 92b56eab-7e90-4cac-a509-a4ac2ac4a140 Greece | |
| 1ad130bc-d838-47f3-912c-5db8e38aa895 Norway | |
| d2d78c5b-a17e-4958-a678-25aaaad3597f Poland | |
| 2399f1aa-146a-4d6c-a7c8-64aed43b19df Germany | |
| 49021f3f-b896-4dd9-9e5a-7d8616115c8c Estonia | |
| 45239b3d-b322-4bd1-a493-3004e7ddad5b Hungary | |
| ab6a65a7-ddb4-48fe-91bc-f69fb2700845 Sweden | |
| 00361ecb-5fb2-48d3-a9ef-5d645d7efd15 Bulgaria | |
| 1b9758ce-b5df-4c6c-98b2-6898903d43d0 Portugal | |
| 8fdcf8c1-fd33-4544-ac75-d7c8d72cc309 Belgium | |
| 78ae54f7-9ab2-4e95-a7b0-da356dc7320d Germany | |
| 38618190-e8bc-4f62-b240-10877415bd21 Poland | |
| d085b5e3-42ee-4174-b69f-b62328f6232a Netherlands | |
| af4afe3d-94f5-43f7-ac3c-f5164e27afee Czech Republic | |
| e871d122-28f0-459d-9de3-16971ec2f158 Denmark | |
| 0fb10ac1-2d76-4964-86f4-8a1350236f8f Finland | |
| d05cba8f-4bca-46e5-bbc7-b98e29cb02cb Germany | |
| 5babaad2-6d82-4b0b-a8c1-877a69f90373 France | |
| 38ba77d2-10c8-4f98-8347-27977c265563 Germany | |
| Environmental | |
| Environmental Information | 9AKK108467A6707 |
| Ordering | |
| Order Code US and Canada | ZANSEJBB000A000000XX |
| EAN | 8015644753627 |
| Minimum Order Quantity | 1 piece |
| Customs Tariff Number | 85362090 |
| Dimensions | |
| Product Net Width | 280 mm |
| Product Net Height | 296 mm |
| Product Net Depth / Length | 183 mm |
| Product Net Weight | 16 kg |
| Container Information | |
| Package Level 1 Units | box 1 piece |
| Package Level 1 Width | 350 mm |
| Package Level 1 Height | 350 mm |
| Package Level 1 Depth / Length | 330 mm |
| Package Level 1 Gross Weight | 18 kg |
| Package Level 1 EAN | 8015644753627 |
| Additional Information | |
| Product Main Type | SACE Emax 2 |
| Product Name | Air Circuit Breaker |
| Product Type | Air Circuit Breaker |
| Version | F |
| CAD Dimensional Drawing | 1SDH001252R0042 |
| Technical | |
| Connecting Capacity | 1200 mm² |
| Current Type | AC |
| Electrical Durability | Ue =< 440 V 3000 cycle |
| Ue = 500 ... 690 V 6500 cycle | |
| 30 cycles per hour | |
| Mechanical Durability | 20000 cycle |
| 60 cycles per hour | |
| Neutral Pole Current ([%Iu]) | 100 % |
| Number of Poles | 4P |
| Power Loss | 201 W |
| Rated Current (In) | 1600 A |
| Rated Impulse Withstand Voltage (Uimp) | acc. to IEC 60947-2 12 kV |
| Rated Insulation Voltage (Ui) | AC 1000 V |
| Rated Operational Voltage | 690 V AC |
| Rated Service Short-Circuit Breaking Capacity (Ics) | (220 V AC) 50 kA |
| (230 V AC) 50 kA | |
| (380 V AC) 50 kA | |
| (400 V AC) 50 kA | |
| (415 V AC) 50 kA | |
| (440 V AC) 50 kA | |
| (500 V AC) 50 kA | |
| (660 V AC) 50 kA | |
| (690 V AC) 50 kA | |
| Rated Service Short-Circuit Breaking Capacity, in % of Icu (Ics) | 100 % |
| Rated Short-time Withstand Current Low Voltage (Icw) | for 1 s 50 kA |
| for 3 s 30 kA | |
| Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (400 V AC) 66 kA |
| (415 V AC) 66 kA | |
| (440 V AC) 66 kA | |
| (500 V AC) 50 kA | |
| (525 V AC) 50 kA | |
| (690 V AC) 50 kA | |
| Rated Uninterrupted Current (Iu) | 1600 A |
| Rated Voltage (Ur) | 690 V |
| Recommended Screw Driver | M12 |
| Release | Ekip Dip LSI |
| Release Type | EL |
| Short-Circuit Performance Level | N |
| Standards | IEC |
| Sub-type | E1.2 |
| Suitable for IT Networks | Yes, 690V |
| Terminal Connection Type | Front |
| Terminal Type | Bolt |
| Tightening Torque | 45 N·m |
| Certificates and Declarations | |
| ATEX Certificate | No certification needed |
| CSA Certificate | No certification needed |
| CSA Certificate (Intrinsic Safe) | No certification needed |
| Data Sheet, Technical Information | 1SDC200023D0209 |
| Declaration of Conformity - CE | 9AKK106713A5546 |
| EU Data Act Compliance Declaration | 1SDH002560A1001 |
| UL Certificate | No certification needed |
| VDE Certificate | No certification needed |
| Mechanical Drawings | 1SDH000999R0101 |
| Wiring Diagram | 1SDM000091R0001 |
| Instructions and Manuals | 1SDH000999R0002 |
| External Classifications and Standards | |
| ETIM 9 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
| ETIM 10 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
| IDEA Granular Category Code (IGCC) | 4926 >> Air circuit breakers |
| Object Classification Code | Q |
| UNSPSC | 39121615 |
| WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) |
| eClass | V11.1 : 27370409 |
| Feature Name | Feature Value |
|---|---|
| Rated permanent current Iu (EF001389) | 1600 A |
| Rated voltage (EF003977) | 690 V |
| Rated short-circuit breaking capacity Icu at 400 V, 50 Hz (EF007048) | 66 kA |
| Overload release current setting (EF002336) | 1600 A |
| Adjustment range short-term delayed short-circuit release (EF007129) | 16000 A |
| Adjustment range undelayed short-circuit release (EF007131) | 2400.0 A |
| Integrated earth fault protection (EF007296) | No |
| Type of electrical connection of main circuit (EF006819) | Bolt connection |
| Device construction (EF008240) | Built-in device fixed built-in technique |
| Suitable for DIN rail (top hat rail) mounting (EF007250) | No |
| DIN rail (top hat rail) mounting optional (EF008904) | No |
| Number of auxiliary contacts as normally closed contact (EF001377) | 0 |
| Number of auxiliary contacts as normally open contact (EF001376) | 0 |
| Number of auxiliary contacts as change-over contact (EF003531) | 4 |
| With switched-off indicator (EF007006) | Yes |
| With integrated under voltage release (EF001390) | No |
| Number of poles (EF001391) | 4 |
| Position of connection for main current circuit (EF006671) | Back |
| Type of control element (EF006976) | Push button |
| Complete device with protection unit (EF008906) | Yes |
| Motor drive integrated (EF006697) | No |
| Motor drive optional (EF007386) | Yes |
| Degree of protection (IP) (EF005474) | IP30 |