View larger
1SDA072826R1
072826
ABB
1 Pcs.
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
| ABB EcoSolutions | |
|---|---|
| ABB EcoSolutions | Yes |
| ABB Site Meeting Group Waste To Landfill Target | UL 2799 Zero Waste To Landfill Validation available |
| End Of Life Disassembling Instructions | 9AKK108468A2360 |
| Environmental Product Declaration - EPD | 9AKK108468A1900 |
| 9AKK108468A3028 | |
| Recyclability Rate of the Product acc. to EN45555 | Design for Closing Resource Loops - Standard EN45555 - 76.4 % |
| Material Compliance | |
| REACH Declaration | 9AKK108466A1425 |
| RoHS Declaration | 9AKK108466A1424 |
| RoHS Information | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
| Conflict Minerals Reporting Template (CMRT) | 9AKK108467A5658 |
| Toxic Substances Control Act - TSCA | 9AKK108467A8326 |
| SCIP | f706f64c-1816-48c2-ba7f-ba318bd1213a Italy |
| Simplified SCIP | c7eaf099-fa25-45c1-9a7d-9cec47719125 Germany |
| 71ab9430-94fc-4b92-9b78-20e066ea0305 Poland | |
| 49d2acbe-277d-4ff0-804b-e125c9d7c39e Poland | |
| 0ec18ee0-651f-4b30-b8f3-2c02abfc4fc1 Sweden | |
| cadaa8c7-2da2-4b7e-bdc8-cee2968000a0 Germany | |
| 9ed46379-537c-4e26-b4da-02297a545931 Croatia | |
| 251a1cab-c91f-4fc8-907a-095eb14c40f6 Czech Republic | |
| 764ebbf2-da91-4ea0-b71e-1d534a3a4a0d Belgium | |
| b1fa6271-af19-418c-8c92-8eec532e362e France | |
| 7d975a2a-363c-4504-921b-910c14b34ac0 Norway | |
| aeb71983-023d-4681-b0a5-ebf762cc8688 Finland | |
| 2d1f7c44-1978-4392-baac-5fb5296c13de Estonia | |
| 9da780f7-43f1-4d0a-859b-94986a8f1069 Hungary | |
| 158d43e7-7ec9-48a9-9f31-d1a3d560d67e Greece | |
| 97bd931a-2d31-4611-8086-74d8093b5443 Portugal | |
| 8a0b9a63-56e9-46f5-8185-0165294db14c Denmark | |
| 57409d2d-c9bb-4f57-b4ad-b8f47679475f Germany | |
| 5b110416-dfea-4cb7-9796-def364c7d1a0 France | |
| 5d3145aa-7fff-436e-b269-ba7d3989bcba Germany | |
| b1a06eeb-eac9-4158-9d65-64ddbc8f9865 Poland | |
| 2ebf9784-2676-4bee-8bcd-2791a4bf8167 Sweden | |
| 652366ad-cc17-4050-b318-6449e7e5c01e Belgium | |
| a91d2139-5d19-4b94-a965-d7b82a76f6f5 Netherlands | |
| 59d3891e-40c7-4528-b46c-1a4fd6a6cdfb Hungary | |
| 8968bf8c-e5d9-47cc-82d1-8f25c6e72e41 Germany | |
| f62dfbf9-5502-4255-aad3-f2ac03b3f78d Spain | |
| a058f189-cca7-491e-918e-8dbdeac70498 Bulgaria | |
| Environmental | |
| Environmental Information | 9AKK108467A6707 |
| Ordering | |
| Order Code US and Canada | ZANREHAF000A000000XX |
| EAN | 8015644766764 |
| Minimum Order Quantity | 1 piece |
| Customs Tariff Number | 85362090 |
| Dimensions | |
| Product Net Width | 348 mm |
| Product Net Height | 363.5 mm |
| Product Net Depth / Length | 271 mm |
| Product Net Weight | 20 kg |
| Container Information | |
| Package Level 1 Units | box 1 piece |
| Package Level 1 Width | 350 mm |
| Package Level 1 Height | 350 mm |
| Package Level 1 Depth / Length | 330 mm |
| Package Level 1 Gross Weight | 23 kg |
| Package Level 1 EAN | 8015644766764 |
| Additional Information | |
| Product Main Type | SACE Emax 2 |
| Product Name | Air Circuit Breaker |
| Product Type | Air Circuit Breaker |
| Version | W |
| CAD Dimensional Drawing | 1SDH001252R0065 |
| Technical | |
| Current Type | AC |
| Electrical Durability | Ue =< 440 V 8000 cycle |
| Ue = 500 ... 690 V 6500 cycle | |
| 30 cycles per hour | |
| Mechanical Durability | 20000 cycle |
| 60 cycles per hour | |
| Neutral Pole Current ([%Iu]) | 100 % |
| Number of Poles | 4P |
| Power Loss | 244 W |
| Rated Current (In) | 1250 A |
| Rated Impulse Withstand Voltage (Uimp) | acc. to IEC 60947-2 12 kV |
| Rated Insulation Voltage (Ui) | AC 1000 V |
| Rated Operational Voltage | 690 V AC |
| Rated Service Short-Circuit Breaking Capacity (Ics) | (220 V AC) 50 kA |
| (230 V AC) 50 kA | |
| (380 V AC) 50 kA | |
| (400 V AC) 50 kA | |
| (415 V AC) 50 kA | |
| (440 V AC) 50 kA | |
| (500 V AC) 50 kA | |
| (660 V AC) 50 kA | |
| (690 V AC) 50 kA | |
| Rated Service Short-Circuit Breaking Capacity, in % of Icu (Ics) | 100 % |
| Rated Short-time Withstand Current Low Voltage (Icw) | for 1 s 50 kA |
| for 3 s 30 kA | |
| Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (400 V AC) 66 kA |
| (415 V AC) 66 kA | |
| (440 V AC) 66 kA | |
| (500 V AC) 50 kA | |
| (525 V AC) 50 kA | |
| (690 V AC) 50 kA | |
| Rated Uninterrupted Current (Iu) | 1250 A |
| Rated Voltage (Ur) | 690 V |
| Release | Ekip Touch LSIG |
| Release Type | EL |
| Short-Circuit Performance Level | N |
| Standards | IEC |
| Sub-type | E1.2 |
| Suitable for IT Networks | Yes, 690V |
| Certificates and Declarations | |
| ATEX Certificate | No certification needed |
| CSA Certificate | No certification needed |
| CSA Certificate (Intrinsic Safe) | No certification needed |
| Data Sheet, Technical Information | 1SDC200023D0209 |
| Declaration of Conformity - CE | 9AKK106713A5546 |
| UL Certificate | No certification needed |
| VDE Certificate | No certification needed |
| Mechanical Drawings | 1SDH000999R0103 |
| Wiring Diagram | 1SDM000091R0001 |
| Instructions and Manuals | 1SDH000999R0002 |
| Instructions and Manuals (Part 2) | 1SDH001316R1002 |
| External Classifications and Standards | |
| ETIM 9 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
| ETIM 10 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
| IDEA Granular Category Code (IGCC) | 4926 >> Air circuit breakers |
| Object Classification Code | Q |
| UNSPSC | 39121615 |
| WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) |
| eClass | V11.1 : 27370409 |
| Feature Name | Feature Value |
|---|---|
| Rated permanent current Iu (EF001389) | 1250 A |
| Rated voltage (EF003977) | 690 V |
| Rated short-circuit breaking capacity Icu at 400 V, 50 Hz (EF007048) | 66 kA |
| Overload release current setting (EF002336) | 1250 A |
| Adjustment range short-term delayed short-circuit release (EF007129) | 12500 A |
| Adjustment range undelayed short-circuit release (EF007131) | 1875.0 A |
| Integrated earth fault protection (EF007296) | Yes |
| Type of electrical connection of main circuit (EF006819) | Connection at separate chassis part |
| Device construction (EF008240) | Built-in device slide-in technique (withdrawable) |
| Suitable for DIN rail (top hat rail) mounting (EF007250) | No |
| DIN rail (top hat rail) mounting optional (EF008904) | No |
| Number of auxiliary contacts as normally closed contact (EF001377) | 0 |
| Number of auxiliary contacts as normally open contact (EF001376) | 0 |
| Number of auxiliary contacts as change-over contact (EF003531) | 4 |
| With switched-off indicator (EF007006) | Yes |
| With integrated under voltage release (EF001390) | No |
| Number of poles (EF001391) | 4 |
| Position of connection for main current circuit (EF006671) | Connection at separate chassis part |
| Type of control element (EF006976) | Push button |
| Complete device with protection unit (EF008906) | Yes |
| Motor drive integrated (EF006697) | No |
| Motor drive optional (EF007386) | Yes |
| Degree of protection (IP) (EF005474) | IP30 |