E1.2N 1250 Ekip Hi-Touch LSI 4p WMP

Automation > Power circuit-breaker for trafo/generator/installation protection
E1.2

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.

Request Quote

Product Overview

This Abb 1SDA072828R1 circuit-breaker is a high-capacity switching component designed to protect large-scale industrial electrical grids against damaging fault conditions. It provides dependable circuit isolation and automated overcurrent protection.

Pricing, availability and lead time are confirmed per enquiry through an RFQ.

  • ABB EcoSolutions: Yes
  • ABB Site Meeting Group Waste To Landfill Target: UL 2799 Zero Waste To Landfill Validation available
  • End Of Life Disassembling Instructions: 9AKK108468A2360
  • Environmental Product Declaration - EPD: 9AKK108468A1900
  • Recyclability Rate of the Product acc. to EN45555: Design for Closing Resource Loops - Standard EN45555 - 76.4 %
  • REACH Declaration: 9AKK108466A1425
  • RoHS Declaration: 9AKK108466A1424
  • RoHS Information: Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
  • Conflict Minerals Reporting Template (CMRT): 9AKK108467A5658
  • Toxic Substances Control Act - TSCA: 9AKK108467A8326
  • Environmental Information: 9AKK108467A6707
  • Order Code US and Canada: ZANREHAJ200A000000XX
  • EAN: 8015644766788
  • Minimum Order Quantity: 1 piece
  • Customs Tariff Number: 85362090
  • Product Net Width: 348 mm

More info

▲
ABB EcoSolutions
ABB EcoSolutionsYes
ABB Site Meeting Group Waste To Landfill TargetUL 2799 Zero Waste To Landfill Validation available
End Of Life Disassembling Instructions9AKK108468A2360
Environmental Product Declaration - EPD9AKK108468A1900
9AKK108468A3028
Recyclability Rate of the Product acc. to EN45555Design for Closing Resource Loops - Standard EN45555 - 76.4 %
Material Compliance
REACH Declaration9AKK108466A1425
RoHS Declaration9AKK108466A1424
RoHS InformationFollowing EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)9AKK108467A5658
Toxic Substances Control Act - TSCA9AKK108467A8326
Environmental
Environmental Information9AKK108467A6707
Ordering
Order Code US and CanadaZANREHAJ200A000000XX
EAN8015644766788
Minimum Order Quantity1 piece
Customs Tariff Number85362090
Dimensions
Product Net Width348 mm
Product Net Height363.5 mm
Product Net Depth / Length271 mm
Product Net Weight20 kg
Container Information
Package Level 1 Unitsbox 1 piece
Package Level 1 Width350 mm
Package Level 1 Height350 mm
Package Level 1 Depth / Length330 mm
Package Level 1 Gross Weight23 kg
Package Level 1 EAN8015644766788
Additional Information
Product Main TypeSACE Emax 2
Product NameAir Circuit Breaker
Product TypeAir Circuit Breaker
VersionW
CAD Dimensional Drawing1SDH001252R0065
Technical
Current TypeAC
Electrical DurabilityUe =< 440 V 8000 cycle
Ue = 500 ... 690 V 6500 cycle
30 cycles per hour
Mechanical Durability20000 cycle
60 cycles per hour
Neutral Pole Current ([%Iu])100 %
Number of Poles4P
Power Loss244 W
Rated Current (In)1250 A
Rated Impulse Withstand Voltage (Uimp)acc. to IEC 60947-2 12 kV
Rated Insulation Voltage (Ui)AC 1000 V
Rated Operational Voltage690 V AC
Rated Service Short-Circuit Breaking Capacity (Ics)(220 V AC) 50 kA
(230 V AC) 50 kA
(380 V AC) 50 kA
(400 V AC) 50 kA
(415 V AC) 50 kA
(440 V AC) 50 kA
(500 V AC) 50 kA
(660 V AC) 50 kA
(690 V AC) 50 kA
Rated Service Short-Circuit Breaking Capacity, in % of Icu (Ics)100 %
Rated Short-time Withstand Current Low Voltage (Icw)for 1 s 50 kA
for 3 s 30 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)(400 V AC) 66 kA
(415 V AC) 66 kA
(440 V AC) 66 kA
(500 V AC) 50 kA
(525 V AC) 50 kA
(690 V AC) 50 kA
Rated Uninterrupted Current (Iu)1250 A
Rated Voltage (Ur)690 V
ReleaseEkip Hi-Touch LSI
Release TypeEL
Short-Circuit Performance LevelN
StandardsIEC
Sub-typeE1.2
Suitable for IT NetworksYes, 690V
Certificates and Declarations
ATEX CertificateNo certification needed
CSA CertificateNo certification needed
CSA Certificate (Intrinsic Safe)No certification needed
Data Sheet, Technical Information1SDC200023D0209
Declaration of Conformity - CE9AKK106713A5546
UL CertificateNo certification needed
VDE CertificateNo certification needed
Mechanical Drawings1SDH000999R0103
Wiring Diagram1SDM000091R0001
Instructions and Manuals1SDH000999R0002
Instructions and Manuals (Part 2)1SDH001316R1002
External Classifications and Standards
ETIM 9EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 10EC000228 - Power circuit-breaker for trafo/generator/installation protection
IDEA Granular Category Code (IGCC)4926 >> Air circuit breakers
Object Classification CodeQ
UNSPSC39121615
WEEE Category5. Small Equipment (No External Dimension More Than 50 cm)
eClassV11.1 : 27370409

Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.