| ABB EcoSolutions | |
|---|---|
| ABB EcoSolutions | Yes |
| ABB Site Meeting Group Waste To Landfill Target | UL 2799 Zero Waste To Landfill Validation available |
| End Of Life Disassembling Instructions | 9AKK108468A2360 |
| Environmental Product Declaration - EPD | 9AKK108468A1900 |
| 9AKK108468A3028 | |
| Extended Product Lifetime | Lifetime Extension Services are Offered |
| Recyclability Rate of the Product acc. to EN45555 | Design for Closing Resource Loops - Standard EN45555 - 76.4 % |
| Material Compliance | |
| REACH Declaration | 9AKK108466A1425 |
| RoHS Declaration | 9AKK108466A1424 |
| RoHS Information | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
| Conflict Minerals Reporting Template (CMRT) | 9AKK108467A5658 |
| Toxic Substances Control Act - TSCA | 9AKK108467A8326 |
| SCIP | 3b13cbee-c1ba-47c5-b0f5-82b409ca9749 India |
| Simplified SCIP | e0c4ebe3-1699-4766-8338-548d2a3ff633 Hungary |
| 5a0bbde7-2eea-440b-9208-b338b61a35c0 France | |
| f4b198c4-0698-4007-aab9-996eec4aa0d3 Bulgaria | |
| 52571264-6e3c-4f53-ae59-c2a774ae39fc Netherlands | |
| b187b493-d307-4c82-b60e-362ee58e9296 Germany | |
| 2e7800dc-eeaf-46cf-9ced-0ce25d2cbaec Poland | |
| ecc8e392-c6fe-4174-90dd-b741784d36a9 Greece | |
| 10163023-bee0-40dd-ad75-34ae7d5afdb3 Poland | |
| 6b413efa-33c4-4d1d-9284-63623bcb46b0 France | |
| 44c248e8-d87e-4d5a-a347-10b89dc2b027 Sweden | |
| 14af85ab-87fd-4484-b872-5ac8e9b7c82d Sweden | |
| ebb3aec2-e54c-4de8-9e21-abc76624301d Germany | |
| 4f2a957a-13ef-4111-ad76-b282695124ac Germany | |
| 03f34e4f-61ca-4843-8302-67fca2c097cd Portugal | |
| b47014ba-92f3-4f80-a9e4-89b9f4ea3c5c Estonia | |
| 90ce64b3-19c8-41e6-8359-16b5fffde252 Denmark | |
| 251fcf69-ebec-4403-b4f6-7116bff26255 Finland | |
| 3646c23c-1276-4d30-bfb8-e30c4d13d9d8 Germany | |
| 24910d86-fcf1-4e03-ab91-b7cb03bf2683 Belgium | |
| 2cc9bd2b-1f7f-4e24-9597-4d6b7f8f9e8e Norway | |
| 248283be-7c83-4dc1-b8a8-85d994d6cdec Germany | |
| b3b81eee-c7dc-449f-9ad1-d258f605b941 Croatia | |
| eead17fb-cdee-4f45-b238-8e5c1ed616fa Czech Republic | |
| dc717dc7-799d-470a-9a1c-b76c76319b04 Belgium | |
| a0b0d9b2-4fb5-4df2-9be5-4aedb2abbf86 Spain | |
| 381f999c-d015-4103-b293-47d53f0210be Hungary | |
| c1126de6-0484-4015-9133-b3ae6d850e92 Poland | |
| Environmental | |
| Environmental Information | 9AKK108467A6707 |
| Ordering | |
| Order Code US and Canada | Z1NQEGBF000A000000XX |
| EAN | 8015644746568 |
| Minimum Order Quantity | 1 piece |
| Customs Tariff Number | 85362090 |
| Dimensions | |
| Product Net Width | 210 mm |
| Product Net Height | 296 mm |
| Product Net Depth / Length | 183 mm |
| Product Net Weight | 14 kg |
| Container Information | |
| Package Level 1 Units | box 1 piece |
| Package Level 1 Width | 270 mm |
| Package Level 1 Height | 350 mm |
| Package Level 1 Depth / Length | 330 mm |
| Package Level 1 Gross Weight | 16 kg |
| Package Level 1 EAN | 8015644746568 |
| Additional Information | |
| Product Main Type | SACE Emax 2 |
| Product Name | Air Circuit Breaker |
| Product Type | Air Circuit Breaker |
| Version | F |
| CAD Dimensional Drawing | 1SDH001252R0001 |
| Technical | |
| Connecting Capacity | 1000 mm² |
| Current Type | AC |
| Electrical Durability | Ue =< 440 V 8000 cycle |
| Ue = 500 ... 690 V 8000 cycle | |
| 30 cycles per hour | |
| Mechanical Durability | 20000 cycle |
| 60 cycles per hour | |
| Number of Poles | 3P |
| Power Loss | 78 W |
| Rated Current (In) | 1000 A |
| Rated Impulse Withstand Voltage (Uimp) | acc. to IEC 60947-2 12 kV |
| Rated Insulation Voltage (Ui) | AC 1000 V |
| Rated Operational Voltage | 690 V AC |
| Rated Service Short-Circuit Breaking Capacity (Ics) | (220 V AC) 50 kA |
| (230 V AC) 50 kA | |
| (380 V AC) 50 kA | |
| (400 V AC) 50 kA | |
| (415 V AC) 50 kA | |
| (440 V AC) 50 kA | |
| (500 V AC) 50 kA | |
| (660 V AC) 50 kA | |
| (690 V AC) 50 kA | |
| Rated Service Short-Circuit Breaking Capacity, in % of Icu (Ics) | 100 % |
| Rated Short-time Withstand Current Low Voltage (Icw) | for 1 s 50 kA |
| for 3 s 30 kA | |
| Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (400 V AC) 66 kA |
| (415 V AC) 66 kA | |
| (440 V AC) 66 kA | |
| (500 V AC) 50 kA | |
| (525 V AC) 50 kA | |
| (690 V AC) 50 kA | |
| Rated Uninterrupted Current (Iu) | 1000 A |
| Rated Voltage (Ur) | 690 V |
| Recommended Screw Driver | M12 |
| Release | Ekip Touch LSIG |
| Release Type | EL |
| Short-Circuit Performance Level | N |
| Standards | IEC |
| Sub-type | E1.2 |
| Suitable for IT Networks | Yes, 690V |
| Terminal Connection Type | Front |
| Terminal Type | Bolt |
| Tightening Torque | 45 N·m |
| Certificates and Declarations | |
| ATEX Certificate | No certification needed |
| CSA Certificate | No certification needed |
| CSA Certificate (Intrinsic Safe) | No certification needed |
| Data Sheet, Technical Information | 1SDC200023D0209 |
| Declaration of Conformity - CE | 9AKK106713A5546 |
| EU Data Act Compliance Declaration | 1SDH002560A1001 |
| UL Certificate | No certification needed |
| VDE Certificate | No certification needed |
| Mechanical Drawings | 1SDH000999R0101 |
| Wiring Diagram | 1SDM000091R0001 |
| Instructions and Manuals | 1SDH000999R0002 |
| Instructions and Manuals (Part 2) | 1SDH001316R1002 |
| External Classifications and Standards | |
| ETIM 9 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
| ETIM 10 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
| IDEA Granular Category Code (IGCC) | 4926 >> Air circuit breakers |
| Object Classification Code | Q |
| UNSPSC | 39121615 |
| WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) |
| eClass | V11.1 : 27370409 |
| Feature Name | Feature Value |
|---|---|
| Rated permanent current Iu (EF001389) | 1000 A |
| Rated voltage (EF003977) | 690 V |
| Rated short-circuit breaking capacity Icu at 400 V, 50 Hz (EF007048) | 66 kA |
| Overload release current setting (EF002336) | 1000 A |
| Adjustment range short-term delayed short-circuit release (EF007129) | 10000 A |
| Adjustment range undelayed short-circuit release (EF007131) | 1500.0 A |
| Integrated earth fault protection (EF007296) | Yes |
| Type of electrical connection of main circuit (EF006819) | Bolt connection |
| Device construction (EF008240) | Built-in device fixed built-in technique |
| Suitable for DIN rail (top hat rail) mounting (EF007250) | No |
| DIN rail (top hat rail) mounting optional (EF008904) | No |
| Number of auxiliary contacts as normally closed contact (EF001377) | 0 |
| Number of auxiliary contacts as normally open contact (EF001376) | 0 |
| Number of auxiliary contacts as change-over contact (EF003531) | 4 |
| With switched-off indicator (EF007006) | Yes |
| With integrated under voltage release (EF001390) | No |
| Number of poles (EF001391) | 3 |
| Position of connection for main current circuit (EF006671) | Back |
| Type of control element (EF006976) | Push button |
| Complete device with protection unit (EF008906) | Yes |
| Motor drive integrated (EF006697) | No |
| Motor drive optional (EF007386) | Yes |
| Degree of protection (IP) (EF005474) | IP30 |