View larger
1SDA072103R1
072103
ABB
1 Pcs.
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
| ABB EcoSolutions | |
|---|---|
| ABB EcoSolutions | Yes |
| ABB Site Meeting Group Waste To Landfill Target | UL 2799 Zero Waste To Landfill Validation available |
| End Of Life Disassembling Instructions | 9AKK108468A2360 |
| Environmental Product Declaration - EPD | 9AKK108468A1900 |
| 9AKK108468A3028 | |
| Extended Product Lifetime | Lifetime Extension Services are Offered |
| Recyclability Rate of the Product acc. to EN45555 | Design for Closing Resource Loops - Standard EN45555 - 76.4 % |
| Material Compliance | |
| REACH Declaration | 9AKK108466A1425 |
| RoHS Declaration | 9AKK108466A1424 |
| RoHS Information | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
| Conflict Minerals Reporting Template (CMRT) | 9AKK108467A5658 |
| Toxic Substances Control Act - TSCA | 9AKK108467A8326 |
| SCIP | d2580eba-e4af-4f7f-b6d5-dc9e7c0fecbd India |
| Simplified SCIP | e89c7cd8-2e5a-4574-9628-44cf109fb474 Spain |
| 825f732f-9a53-4915-96d8-97b8c7305a18 Belgium | |
| a43e58c5-40f1-48b6-ab1c-00786e789b6e Estonia | |
| c1333cf9-3d1c-409a-9e58-2f9c9a26ca27 Netherlands | |
| 3b36febb-e8d4-4175-9e0c-e12c5a23fe5f Poland | |
| d4e0f21e-4e1b-489c-a63b-30a248d4918b Croatia | |
| bcc8ebaa-9e17-46b8-890d-279dbc8ea284 Czech Republic | |
| 81613e3d-acec-4342-ade4-943a584141b0 Hungary | |
| ace8d33a-eeda-4808-804b-0d8a83f8311d Hungary | |
| 05d3cd14-b27b-4ed0-a58b-ae8c3232723c Sweden | |
| 6e113542-8606-4c96-b5e1-92094680b66b Poland | |
| 8369a4d4-61a6-4a50-b838-644d58abe4fa Bulgaria | |
| b32e7177-a3e3-48ed-8ab7-c6b4ddc8fafe Greece | |
| 8b2e1a77-8b9c-4ca9-b8d1-ba411acdd5fd Portugal | |
| 879d942f-5b93-4daa-9fd2-8b60d93b42cd France | |
| 575a490c-8c20-4261-ad50-6c5bf8c22277 Sweden | |
| 4becf26b-91a2-4209-9ee1-d65e4af7f749 Germany | |
| f4aab910-4dff-427b-a4ad-ec7cc6b48547 Poland | |
| 70e1b383-eb44-4dbb-8264-7b9216c6ea0a Germany | |
| bf25fdf1-589a-4490-bd14-2d7d8b817e0c Germany | |
| e7fdb631-f594-4f3d-b9e7-626895499228 France | |
| 63fd7359-1343-42f7-8594-5156ed5d5e8f Denmark | |
| 92473a84-5801-42c1-b796-7f7915cb216b Germany | |
| cd67240f-331c-47bc-8088-30b9c861e3c2 Belgium | |
| ae25f062-a937-42b3-aa66-fce47583544c Norway | |
| 617a6061-b5fd-4030-9069-c2e65c58cd6f Germany | |
| b7930c37-083e-4a26-8c4b-e5262f4af79f Finland | |
| Environmental | |
| Environmental Information | 9AKK108467A6707 |
| Ordering | |
| Order Code US and Canada | Z1CPEFAC000A000000XX |
| EAN | 8015644759537 |
| Minimum Order Quantity | 1 piece |
| Customs Tariff Number | 85362090 |
| Dimensions | |
| Product Net Width | 278 mm |
| Product Net Height | 363.5 mm |
| Product Net Depth / Length | 271 mm |
| Product Net Weight | 18 kg |
| Container Information | |
| Package Level 1 Units | box 1 piece |
| Package Level 1 Width | 270 mm |
| Package Level 1 Height | 350 mm |
| Package Level 1 Depth / Length | 330 mm |
| Package Level 1 Gross Weight | 20 kg |
| Package Level 1 EAN | 8015644759537 |
| Additional Information | |
| Product Main Type | SACE Emax 2 |
| Product Name | Air Circuit Breaker |
| Product Type | Air Circuit Breaker |
| Version | W |
| CAD Dimensional Drawing | 1SDH001252R0024 |
| Technical | |
| Connecting Capacity | 500 mm² |
| Current Type | AC |
| Electrical Durability | Ue =< 440 V 8000 cycle |
| Ue = 500 ... 690 V 8000 cycle | |
| 30 cycles per hour | |
| Mechanical Durability | 20000 cycle |
| 60 cycles per hour | |
| Number of Poles | 3P |
| Power Loss | 100 W |
| Rated Current (In) | 800 A |
| Rated Impulse Withstand Voltage (Uimp) | acc. to IEC 60947-2 12 kV |
| Rated Insulation Voltage (Ui) | AC 1000 V |
| Rated Operational Voltage | 690 V AC |
| Rated Service Short-Circuit Breaking Capacity (Ics) | (220 V AC) 50 kA |
| (230 V AC) 50 kA | |
| (380 V AC) 50 kA | |
| (400 V AC) 50 kA | |
| (415 V AC) 50 kA | |
| (440 V AC) 50 kA | |
| (500 V AC) 42 kA | |
| (660 V AC) 42 kA | |
| (690 V AC) 42 kA | |
| Rated Service Short-Circuit Breaking Capacity, in % of Icu (Ics) | 100 % |
| Rated Short-time Withstand Current Low Voltage (Icw) | for 1 s 42 kA |
| for 3 s 24 kA | |
| Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (400 V AC) 50 kA |
| (415 V AC) 50 kA | |
| (440 V AC) 50 kA | |
| (500 V AC) 42 kA | |
| (525 V AC) 42 kA | |
| (690 V AC) 42 kA | |
| Rated Uninterrupted Current (Iu) | 800 A |
| Rated Voltage (Ur) | 690 V |
| Recommended Screw Driver | M12 |
| Release | Ekip Dip LSIG |
| Release Type | EL |
| Short-Circuit Performance Level | C |
| Standards | IEC |
| Sub-type | E1.2 |
| Suitable for IT Networks | Yes, 690V |
| Certificates and Declarations | |
| ATEX Certificate | No certification needed |
| CSA Certificate | No certification needed |
| CSA Certificate (Intrinsic Safe) | No certification needed |
| Data Sheet, Technical Information | 1SDC200023D0209 |
| Declaration of Conformity - CE | 9AKK106713A5546 |
| EU Data Act Compliance Declaration | 1SDH002560A1001 |
| UL Certificate | No certification needed |
| VDE Certificate | No certification needed |
| Mechanical Drawings | 1SDH000999R0103 |
| Wiring Diagram | 1SDM000091R0001 |
| Instructions and Manuals | 1SDH000999R0002 |
| External Classifications and Standards | |
| ETIM 9 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
| ETIM 10 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
| IDEA Granular Category Code (IGCC) | 4926 >> Air circuit breakers |
| Object Classification Code | Q |
| UNSPSC | 39121615 |
| WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) |
| eClass | V11.1 : 27370409 |
| Feature Name | Feature Value |
|---|---|
| Rated permanent current Iu (EF001389) | 800 A |
| Rated voltage (EF003977) | 690 V |
| Rated short-circuit breaking capacity Icu at 400 V, 50 Hz (EF007048) | 50 kA |
| Overload release current setting (EF002336) | 320.0 A |
| Adjustment range short-term delayed short-circuit release (EF007129) | 480.0 A |
| Adjustment range undelayed short-circuit release (EF007131) | 1200.0 A |
| Integrated earth fault protection (EF007296) | Yes |
| Type of electrical connection of main circuit (EF006819) | Connection at separate chassis part |
| Device construction (EF008240) | Built-in device slide-in technique (withdrawable) |
| Suitable for DIN rail (top hat rail) mounting (EF007250) | No |
| DIN rail (top hat rail) mounting optional (EF008904) | No |
| Number of auxiliary contacts as normally closed contact (EF001377) | 0 |
| Number of auxiliary contacts as normally open contact (EF001376) | 0 |
| Number of auxiliary contacts as change-over contact (EF003531) | 4 |
| With switched-off indicator (EF007006) | Yes |
| With integrated under voltage release (EF001390) | No |
| Number of poles (EF001391) | 3 |
| Position of connection for main current circuit (EF006671) | Connection at separate chassis part |
| Type of control element (EF006976) | Push button |
| Complete device with protection unit (EF008906) | Yes |
| Motor drive integrated (EF006697) | No |
| Motor drive optional (EF007386) | Yes |
| Degree of protection (IP) (EF005474) | IP30 |