View larger
1SDA072101R1
072101
ABB
1 Pcs.
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
| ABB EcoSolutions | |
|---|---|
| ABB EcoSolutions | Yes |
| ABB Site Meeting Group Waste To Landfill Target | UL 2799 Zero Waste To Landfill Validation available |
| End Of Life Disassembling Instructions | 9AKK108468A2360 |
| Environmental Product Declaration - EPD | 9AKK108468A1900 |
| 9AKK108468A3028 | |
| Extended Product Lifetime | Lifetime Extension Services are Offered |
| Recyclability Rate of the Product acc. to EN45555 | Design for Closing Resource Loops - Standard EN45555 - 76.4 % |
| Material Compliance | |
| REACH Declaration | 9AKK108466A1425 |
| RoHS Declaration | 9AKK108466A1424 |
| RoHS Information | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
| Conflict Minerals Reporting Template (CMRT) | 9AKK108467A5658 |
| Toxic Substances Control Act - TSCA | 9AKK108467A8326 |
| SCIP | 00481da2-8021-42e3-a155-3564d0c07083 India |
| Simplified SCIP | 402b8139-0a06-47c8-ab0a-f92c97e3d89a Hungary |
| e0d25b9f-230b-4b11-8843-63c395f49ef0 Hungary | |
| c78dd83b-ba2c-4dda-9f3b-e3e9ea9e1262 Netherlands | |
| 32116ee0-6c69-44ff-b1f0-3e5849d85258 Norway | |
| 0db7ed48-8248-4f79-99e8-35c24f87f8d5 Belgium | |
| 6c66c0b3-01c2-4f6f-8143-0974d49ba7ee Denmark | |
| a47de024-2565-4a5f-a4f8-117d68fbd0f4 Germany | |
| 76e1f4fd-ebe7-4850-a036-85e21ee46959 Poland | |
| 52b52d9e-eee3-431f-97cc-4adc1c907299 Czech Republic | |
| 25ae465b-f371-427e-a9a7-2da1ef9644ac Croatia | |
| 3ae27e78-2504-41fc-9530-11600eac603d Belgium | |
| 9a6d35f4-8784-43cd-948b-5f48d207bd97 Spain | |
| 212974c8-a825-48d8-be67-c10acc1281c5 Estonia | |
| 71b9f2a8-5209-4e73-8455-2fa9792e6082 Portugal | |
| c50d148e-db89-4327-9e37-e3427559fe93 France | |
| 4079f4ba-6b0e-41d5-9ed6-1a0887c6e71a France | |
| d5972a58-71b4-4025-9739-4f9824a7392b Sweden | |
| fe034484-c71a-4558-8856-7f4fe8f6e601 Germany | |
| e8a5570e-5646-4eb2-9010-5f5a5bf9aefd Germany | |
| d12012e5-063f-41c7-bd36-090e0f67e0a8 Bulgaria | |
| 74ec9478-ddb6-4075-9b01-77950e83433c Poland | |
| 2919a714-c145-4ce4-8bf2-6a8eddd776fe Sweden | |
| d9582723-dd16-4c72-9a37-75bdca91302b Greece | |
| 37db113c-daf0-48ca-a990-d076c3d1e9c4 Germany | |
| 9dd32509-25c1-4e76-baee-eebae7ea39a5 Poland | |
| 60ae9838-0a3b-4f0e-a0c6-3ed4d12f9d94 Finland | |
| cd203d8d-1ec2-4af8-8879-f7605bfe59d9 Germany | |
| Environmental | |
| Environmental Information | 9AKK108467A6707 |
| Ordering | |
| Order Code US and Canada | Z1CPEFAA000A000000XX |
| EAN | 8015644759513 |
| Minimum Order Quantity | 1 piece |
| Customs Tariff Number | 85362090 |
| Dimensions | |
| Product Net Width | 278 mm |
| Product Net Height | 363.5 mm |
| Product Net Depth / Length | 271 mm |
| Product Net Weight | 18 kg |
| Container Information | |
| Package Level 1 Units | box 1 piece |
| Package Level 1 Width | 270 mm |
| Package Level 1 Height | 350 mm |
| Package Level 1 Depth / Length | 330 mm |
| Package Level 1 Gross Weight | 20 kg |
| Package Level 1 EAN | 8015644759513 |
| Additional Information | |
| Product Main Type | SACE Emax 2 |
| Product Name | Air Circuit Breaker |
| Product Type | Air Circuit Breaker |
| Version | W |
| CAD Dimensional Drawing | 1SDH001252R0024 |
| Technical | |
| Connecting Capacity | 500 mm² |
| Current Type | AC |
| Electrical Durability | Ue =< 440 V 8000 cycle |
| Ue = 500 ... 690 V 8000 cycle | |
| 30 cycles per hour | |
| Mechanical Durability | 20000 cycle |
| 60 cycles per hour | |
| Number of Poles | 3P |
| Power Loss | 100 W |
| Rated Current (In) | 800 A |
| Rated Impulse Withstand Voltage (Uimp) | acc. to IEC 60947-2 12 kV |
| Rated Insulation Voltage (Ui) | AC 1000 V |
| Rated Operational Voltage | 690 V AC |
| Rated Service Short-Circuit Breaking Capacity (Ics) | (220 V AC) 50 kA |
| (230 V AC) 50 kA | |
| (380 V AC) 50 kA | |
| (400 V AC) 50 kA | |
| (415 V AC) 50 kA | |
| (440 V AC) 50 kA | |
| (500 V AC) 42 kA | |
| (660 V AC) 42 kA | |
| (690 V AC) 42 kA | |
| Rated Service Short-Circuit Breaking Capacity, in % of Icu (Ics) | 100 % |
| Rated Short-time Withstand Current Low Voltage (Icw) | for 1 s 42 kA |
| for 3 s 24 kA | |
| Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (400 V AC) 50 kA |
| (415 V AC) 50 kA | |
| (440 V AC) 50 kA | |
| (500 V AC) 42 kA | |
| (525 V AC) 42 kA | |
| (690 V AC) 42 kA | |
| Rated Uninterrupted Current (Iu) | 800 A |
| Rated Voltage (Ur) | 690 V |
| Recommended Screw Driver | M12 |
| Release | Ekip Dip LI |
| Release Type | EL |
| Short-Circuit Performance Level | C |
| Standards | IEC |
| Sub-type | E1.2 |
| Suitable for IT Networks | Yes, 690V |
| Certificates and Declarations | |
| ATEX Certificate | No certification needed |
| CSA Certificate | No certification needed |
| CSA Certificate (Intrinsic Safe) | No certification needed |
| Data Sheet, Technical Information | 1SDC200023D0209 |
| Declaration of Conformity - CE | 9AKK106713A5546 |
| EU Data Act Compliance Declaration | 1SDH002560A1001 |
| UL Certificate | No certification needed |
| VDE Certificate | No certification needed |
| Mechanical Drawings | 1SDH000999R0103 |
| Wiring Diagram | 1SDM000091R0001 |
| Instructions and Manuals | 1SDH000999R0002 |
| External Classifications and Standards | |
| ETIM 9 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
| ETIM 10 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
| IDEA Granular Category Code (IGCC) | 4926 >> Air circuit breakers |
| Object Classification Code | Q |
| UNSPSC | 39121615 |
| WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) |
| eClass | V11.1 : 27370409 |