View larger
1SDA072062R1
072062
ABB
1 Pcs.
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
| ABB EcoSolutions | |
|---|---|
| ABB EcoSolutions | Yes |
| ABB Site Meeting Group Waste To Landfill Target | UL 2799 Zero Waste To Landfill Validation available |
| End Of Life Disassembling Instructions | 9AKK108468A2360 |
| Environmental Product Declaration - EPD | 9AKK108468A1900 |
| 9AKK108468A3028 | |
| Extended Product Lifetime | Lifetime Extension Services are Offered |
| Recyclability Rate of the Product acc. to EN45555 | Design for Closing Resource Loops - Standard EN45555 - 76.4 % |
| Material Compliance | |
| REACH Declaration | 9AKK108466A1425 |
| RoHS Declaration | 9AKK108466A1424 |
| RoHS Information | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
| Conflict Minerals Reporting Template (CMRT) | 9AKK108467A5658 |
| Toxic Substances Control Act - TSCA | 9AKK108467A8326 |
| SCIP | 72e59724-c663-4e32-96da-9046e6041459 Italy |
| Simplified SCIP | a6b70380-cc44-40a1-bffd-82f2875c329e Germany |
| b5c4b82f-9016-4cae-8f39-7ce8afe52ad7 Sweden | |
| b1418205-a79a-4775-8143-541ae0973409 Poland | |
| 4791b573-aba7-4d91-ae03-2e245d926e23 Belgium | |
| 35b15014-7265-4d2a-b737-4eac590db788 Norway | |
| bd565c6c-7d25-4a1c-a655-896059ec6721 Poland | |
| 25a0d197-85f4-4b70-8de5-64a9ff9335db France | |
| 5faaa75d-4be1-4c4f-b46d-60bd6aa4c1a5 Croatia | |
| 3e3d0ec5-61b3-4f55-8926-536cbbaf2c0e Sweden | |
| e35780f5-0a12-40e8-ab30-695800767c24 Finland | |
| caf3fc7d-3462-4e47-a304-dc154c632e04 Germany | |
| 996eb4e9-7f44-4e48-807d-f0a22f38eeeb France | |
| 21704a53-4fd0-43bd-aaf0-f20cb4218df3 Germany | |
| 09b27337-f7fb-42cc-965e-b8d309480394 Germany | |
| 4a7dc21c-cca6-4646-814b-b688d90a6dac Netherlands | |
| db8c63ce-5cef-44d0-bf4f-13af802fa9e5 Belgium | |
| 407c92ee-8952-46d4-a084-836a3d53c3c5 Czech Republic | |
| ca5466d1-37df-4c66-9548-022cd4ec4abe Poland | |
| f68feded-7410-49fe-9567-ddc730ada469 Hungary | |
| 8873b133-0eb2-400c-8d61-93a088be52d4 Spain | |
| 47dbca06-e25f-4ee5-8926-4d15e93a9e2c Germany | |
| b4154a5a-3288-4044-bd2e-6288dc735cb5 Portugal | |
| ee4ad8a5-a5e2-4d72-afd5-b257d5d70a9b Bulgaria | |
| 24148717-8f3c-4b1d-b4ee-3113fed94607 Denmark | |
| 7e014499-6ae3-4a0a-ae34-f836a4538712 Estonia | |
| 28f77918-c9c5-4476-bfb2-476021ad5d21 Greece | |
| ba9ce17e-080d-442b-8f86-859b4ac3bd0e Hungary | |
| Environmental | |
| Environmental Information | 9AKK108467A6707 |
| Ordering | |
| Order Code US and Canada | Z1CNEEAB000A000000XX |
| EAN | 8015644759124 |
| Minimum Order Quantity | 1 piece |
| Customs Tariff Number | 85362090 |
| Dimensions | |
| Product Net Width | 278 mm |
| Product Net Height | 363.5 mm |
| Product Net Depth / Length | 271 mm |
| Product Net Weight | 18 kg |
| Container Information | |
| Package Level 1 Units | box 1 piece |
| Package Level 1 Width | 270 mm |
| Package Level 1 Height | 350 mm |
| Package Level 1 Depth / Length | 330 mm |
| Package Level 1 Gross Weight | 20 kg |
| Package Level 1 EAN | 8015644759124 |
| Additional Information | |
| Product Main Type | SACE Emax 2 |
| Product Name | Air Circuit Breaker |
| Product Type | Air Circuit Breaker |
| Version | W |
| CAD Dimensional Drawing | 1SDH001252R0024 |
| Technical | |
| Connecting Capacity | 400 mm² |
| Current Type | AC |
| Electrical Durability | Ue =< 440 V 8000 cycle |
| Ue = 500 ... 690 V 8000 cycle | |
| 30 cycles per hour | |
| Mechanical Durability | 20000 cycle |
| 60 cycles per hour | |
| Number of Poles | 3P |
| Power Loss | 62 W |
| Rated Current (In) | 630 A |
| Rated Impulse Withstand Voltage (Uimp) | acc. to IEC 60947-2 12 kV |
| Rated Insulation Voltage (Ui) | AC 1000 V |
| Rated Operational Voltage | 690 V AC |
| Rated Service Short-Circuit Breaking Capacity (Ics) | (220 V AC) 50 kA |
| (230 V AC) 50 kA | |
| (380 V AC) 50 kA | |
| (400 V AC) 50 kA | |
| (415 V AC) 50 kA | |
| (440 V AC) 50 kA | |
| (500 V AC) 42 kA | |
| (660 V AC) 42 kA | |
| (690 V AC) 42 kA | |
| Rated Service Short-Circuit Breaking Capacity, in % of Icu (Ics) | 100 % |
| Rated Short-time Withstand Current Low Voltage (Icw) | for 1 s 42 kA |
| for 3 s 24 kA | |
| Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (400 V AC) 50 kA |
| (415 V AC) 50 kA | |
| (440 V AC) 50 kA | |
| (500 V AC) 42 kA | |
| (525 V AC) 42 kA | |
| (690 V AC) 42 kA | |
| Rated Uninterrupted Current (Iu) | 630 A |
| Rated Voltage (Ur) | 690 V |
| Recommended Screw Driver | M12 |
| Release | Ekip Dip LSI |
| Release Type | EL |
| Short-Circuit Performance Level | C |
| Standards | IEC |
| Sub-type | E1.2 |
| Suitable for IT Networks | Yes, 690V |
| Certificates and Declarations | |
| ATEX Certificate | No certification needed |
| CSA Certificate | No certification needed |
| CSA Certificate (Intrinsic Safe) | No certification needed |
| Data Sheet, Technical Information | 1SDC200023D0209 |
| Declaration of Conformity - CE | 9AKK106713A5546 |
| EU Data Act Compliance Declaration | 1SDH002560A1001 |
| UL Certificate | No certification needed |
| VDE Certificate | No certification needed |
| Mechanical Drawings | 1SDH000999R0103 |
| Wiring Diagram | 1SDM000091R0001 |
| Instructions and Manuals | 1SDH000999R0002 |
| External Classifications and Standards | |
| ETIM 9 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
| ETIM 10 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
| IDEA Granular Category Code (IGCC) | 4926 >> Air circuit breakers |
| Object Classification Code | Q |
| UNSPSC | 39121615 |
| WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) |
| eClass | V11.1 : 27370409 |
| Feature Name | Feature Value |
|---|---|
| Rated permanent current Iu (EF001389) | 630 A |
| Rated voltage (EF003977) | 690 V |
| Rated short-circuit breaking capacity Icu at 400 V, 50 Hz (EF007048) | 50 kA |
| Overload release current setting (EF002336) | 252.0 A |
| Adjustment range short-term delayed short-circuit release (EF007129) | 378.0 A |
| Adjustment range undelayed short-circuit release (EF007131) | 945.0 A |
| Integrated earth fault protection (EF007296) | No |
| Type of electrical connection of main circuit (EF006819) | Connection at separate chassis part |
| Device construction (EF008240) | Built-in device slide-in technique (withdrawable) |
| Suitable for DIN rail (top hat rail) mounting (EF007250) | No |
| DIN rail (top hat rail) mounting optional (EF008904) | No |
| Number of auxiliary contacts as normally closed contact (EF001377) | 0 |
| Number of auxiliary contacts as normally open contact (EF001376) | 0 |
| Number of auxiliary contacts as change-over contact (EF003531) | 4 |
| With switched-off indicator (EF007006) | Yes |
| With integrated under voltage release (EF001390) | No |
| Number of poles (EF001391) | 3 |
| Position of connection for main current circuit (EF006671) | Connection at separate chassis part |
| Type of control element (EF006976) | Push button |
| Complete device with protection unit (EF008906) | Yes |
| Motor drive integrated (EF006697) | No |
| Motor drive optional (EF007386) | Yes |
| Degree of protection (IP) (EF005474) | IP30 |