View larger
1SDA071341R1
071341
ABB
1 Pcs.
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
| ABB EcoSolutions | |
|---|---|
| ABB EcoSolutions | Yes |
| ABB Site Meeting Group Waste To Landfill Target | UL 2799 Zero Waste To Landfill Validation available |
| End Of Life Disassembling Instructions | 9AKK108468A2360 |
| Environmental Product Declaration - EPD | 9AKK108468A1900 |
| 9AKK108468A3028 | |
| Extended Product Lifetime | Lifetime Extension Services are Offered |
| Recyclability Rate of the Product acc. to EN45555 | Design for Closing Resource Loops - Standard EN45555 - 76.4 % |
| Material Compliance | |
| REACH Declaration | 9AKK108466A1425 |
| RoHS Declaration | 9AKK108466A1424 |
| RoHS Information | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
| Conflict Minerals Reporting Template (CMRT) | 9AKK108467A5658 |
| Toxic Substances Control Act - TSCA | 9AKK108467A8326 |
| SCIP | b3f3aa6c-6745-4bf0-8ca8-d1acc1942cbc China |
| Simplified SCIP | af7b219e-2e5a-45d6-9a28-7cbb480f44c0 Denmark |
| 9f6ec933-82d3-4e3f-bd6c-5158e4018758 Belgium | |
| c0aec563-5780-4a24-bee6-0d2c13cbe432 Finland | |
| 1f130a79-ebe4-42f9-9bc6-3cad5b944cf9 Germany | |
| 04417081-67bc-4070-9c80-433a180e9993 France | |
| 2e5299e7-11b6-4595-915d-f2b50e5e28e2 Germany | |
| 68be5da0-83d7-4e93-8e9c-b93e9656f725 Hungary | |
| 1c72bea6-4ddd-4c24-8355-dc7cc5b28812 Estonia | |
| a319658b-4f12-497b-96bd-964e9db93e98 Poland | |
| bb21fd83-8cff-42a0-8eb4-d2b81c06c998 Poland | |
| 35e8e7a8-6ede-4c32-a1d2-0f99e9956635 Bulgaria | |
| ca59ee31-b930-423d-b0b8-1fe7dac5e7f1 Portugal | |
| 820e7014-f37f-4545-9a91-184ff033f40c Belgium | |
| 18683cf6-6ed4-40c0-8e4e-6c80637b0bea Greece | |
| a4e34e5e-6fb3-44f1-b656-971efa782410 Norway | |
| 593fa74a-b336-465a-a1a6-87b1f532b77e Croatia | |
| 6c15ce1c-a30c-45f6-8f72-fc0dad156614 Germany | |
| a7fdb515-11da-4d72-9129-e1a883f1ed0d Hungary | |
| 2e3fa8be-dfbd-42e1-adb3-b24d2fca63b7 Spain | |
| a8890b6d-cd9f-4f55-99bb-fa50139f55fd Sweden | |
| f882fb54-69f2-443e-a1e7-3532c94b05bb Czech Republic | |
| 9f4dda86-86bb-4c8d-a56a-1c1599b04c65 Netherlands | |
| 6a737401-18cc-4008-b397-f3ccb0a3ab78 Poland | |
| 9e61bc3e-e06b-476e-bb6e-5d618864be1f Germany | |
| a3a04c95-369c-455b-a3f4-28b5092074ff Sweden | |
| 5320d983-8e16-4a2b-a558-c1ce23a82ae1 Germany | |
| 48dc9801-f4dc-4ba6-9ab1-1e6fbb6f2c03 France | |
| Environmental | |
| Environmental Information | 9AKK108467A6707 |
| Ordering | |
| Order Code US and Canada | ZACNEEBA000A000000XX |
| EAN | 8015644751913 |
| Minimum Order Quantity | 1 piece |
| Customs Tariff Number | 85362090 |
| Dimensions | |
| Product Net Width | 280 mm |
| Product Net Height | 296 mm |
| Product Net Depth / Length | 183 mm |
| Product Net Weight | 16 kg |
| Container Information | |
| Package Level 1 Units | box 1 piece |
| Package Level 1 Width | 350 mm |
| Package Level 1 Height | 350 mm |
| Package Level 1 Depth / Length | 330 mm |
| Package Level 1 Gross Weight | 18 kg |
| Package Level 1 EAN | 8015644751913 |
| Additional Information | |
| Product Main Type | SACE Emax 2 |
| Product Name | Air Circuit Breaker |
| Product Type | Air Circuit Breaker |
| Version | F |
| CAD Dimensional Drawing | 1SDH001252R0042 |
| Technical | |
| Connecting Capacity | 400 mm² |
| Current Type | AC |
| Electrical Durability | Ue =< 440 V 8000 cycle |
| Ue = 500 ... 690 V 8000 cycle | |
| 30 cycles per hour | |
| Mechanical Durability | 20000 cycle |
| 60 cycles per hour | |
| Neutral Pole Current ([%Iu]) | 100 % |
| Number of Poles | 4P |
| Power Loss | 31 W |
| Rated Current (In) | 630 A |
| Rated Impulse Withstand Voltage (Uimp) | acc. to IEC 60947-2 12 kV |
| Rated Insulation Voltage (Ui) | AC 1000 V |
| Rated Operational Voltage | 690 V AC |
| Rated Service Short-Circuit Breaking Capacity (Ics) | (220 V AC) 50 kA |
| (230 V AC) 50 kA | |
| (380 V AC) 50 kA | |
| (400 V AC) 50 kA | |
| (415 V AC) 50 kA | |
| (440 V AC) 50 kA | |
| (500 V AC) 42 kA | |
| (660 V AC) 42 kA | |
| (690 V AC) 42 kA | |
| Rated Service Short-Circuit Breaking Capacity, in % of Icu (Ics) | 100 % |
| Rated Short-time Withstand Current Low Voltage (Icw) | for 1 s 42 kA |
| for 3 s 24 kA | |
| Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (400 V AC) 50 kA |
| (415 V AC) 50 kA | |
| (440 V AC) 50 kA | |
| (500 V AC) 42 kA | |
| (525 V AC) 42 kA | |
| (690 V AC) 42 kA | |
| Rated Uninterrupted Current (Iu) | 630 A |
| Rated Voltage (Ur) | 690 V |
| Recommended Screw Driver | M12 |
| Release | Ekip Dip LI |
| Release Type | EL |
| Short-Circuit Performance Level | C |
| Standards | IEC |
| Sub-type | E1.2 |
| Suitable for IT Networks | Yes, 690V |
| Terminal Connection Type | Front |
| Terminal Type | Bolt |
| Tightening Torque | 45 N·m |
| Certificates and Declarations | |
| ATEX Certificate | No certification needed |
| CSA Certificate | No certification needed |
| CSA Certificate (Intrinsic Safe) | No certification needed |
| Data Sheet, Technical Information | 1SDC200023D0209 |
| Declaration of Conformity - CE | 9AKK106713A5546 |
| EU Data Act Compliance Declaration | 1SDH002560A1001 |
| UL Certificate | No certification needed |
| VDE Certificate | No certification needed |
| Mechanical Drawings | 1SDH000999R0101 |
| Wiring Diagram | 1SDM000091R0001 |
| Instructions and Manuals | 1SDH000999R0002 |
| External Classifications and Standards | |
| ETIM 9 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
| ETIM 10 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
| IDEA Granular Category Code (IGCC) | 4926 >> Air circuit breakers |
| Object Classification Code | Q |
| UNSPSC | 39121615 |
| WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) |
| eClass | V11.1 : 27370409 |
| Feature Name | Feature Value |
|---|---|
| Rated permanent current Iu (EF001389) | 630 A |
| Rated voltage (EF003977) | 690 V |
| Rated short-circuit breaking capacity Icu at 400 V, 50 Hz (EF007048) | 50 kA |
| Overload release current setting (EF002336) | 252.0 A |
| Adjustment range undelayed short-circuit release (EF007131) | 945.0 A |
| Integrated earth fault protection (EF007296) | No |
| Type of electrical connection of main circuit (EF006819) | Bolt connection |
| Device construction (EF008240) | Built-in device fixed built-in technique |
| Suitable for DIN rail (top hat rail) mounting (EF007250) | No |
| DIN rail (top hat rail) mounting optional (EF008904) | No |
| Number of auxiliary contacts as normally closed contact (EF001377) | 0 |
| Number of auxiliary contacts as normally open contact (EF001376) | 0 |
| Number of auxiliary contacts as change-over contact (EF003531) | 4 |
| With switched-off indicator (EF007006) | Yes |
| With integrated under voltage release (EF001390) | No |
| Number of poles (EF001391) | 4 |
| Position of connection for main current circuit (EF006671) | Back |
| Type of control element (EF006976) | Push button |
| Complete device with protection unit (EF008906) | Yes |
| Motor drive integrated (EF006697) | No |
| Motor drive optional (EF007386) | Yes |
| Degree of protection (IP) (EF005474) | IP30 |