View larger
1SDA070876R1
070876
ABB
1 Pcs.
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
| ABB EcoSolutions | |
|---|---|
| ABB EcoSolutions | Yes |
| ABB Site Meeting Group Waste To Landfill Target | UL 2799 Zero Waste To Landfill Validation available |
| End Of Life Disassembling Instructions | 9AKK108468A2360 |
| Environmental Product Declaration - EPD | 9AKK108468A1900 |
| 9AKK108468A3028 | |
| Extended Product Lifetime | Lifetime Extension Services are Offered |
| Recyclability Rate of the Product acc. to EN45555 | Design for Closing Resource Loops - Standard EN45555 - 76.4 % |
| Material Compliance | |
| REACH Declaration | 9AKK108466A1425 |
| RoHS Declaration | 9AKK108466A1424 |
| RoHS Information | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
| Conflict Minerals Reporting Template (CMRT) | 9AKK108467A5658 |
| Toxic Substances Control Act - TSCA | 9AKK108467A8326 |
| SCIP | 729727c2-5e47-4d9b-b729-fd81ad2a60a3 Italy |
| Simplified SCIP | f4a9356e-32f4-46c5-8d0e-ca62c641968f Norway |
| 15d4fce2-a1f8-45d3-a68d-8f5472578387 Germany | |
| 8bcb496e-1646-4a84-a9e5-3ab89084e139 Poland | |
| e140f805-9f8a-44b5-afa5-bbadef1fd615 Finland | |
| fa6e87f2-a23c-442a-8f1b-60cdae1d58ac Belgium | |
| 72c3bc49-dd0f-4b1f-a294-ee70d427a3ad Denmark | |
| 0f2203ea-5e79-4f6f-8c24-3aa8a14a963b Germany | |
| 9a5be7b8-84db-4a42-bd54-f12c4348d4a4 Estonia | |
| bf87b2f6-d43d-4512-838e-de62e54efaa7 Poland | |
| 90f83436-81cd-41ac-b8fd-6f14e204f173 Greece | |
| 5de01eca-e3f1-479e-8c71-1b58617e9694 Portugal | |
| e25df736-8d1a-4ba7-ae0c-5fc929b34e85 Sweden | |
| 4de8da37-9e91-450b-b370-01a00794d40b Bulgaria | |
| d3f7d589-c84c-4198-9b5b-9b36701ea4d2 Croatia | |
| 74cc9cc9-26f4-4f0e-8307-b7550de1596e Germany | |
| 2a858a30-cada-47be-bc9c-d2f42160786a Hungary | |
| 1274c372-9c83-42df-8741-379b8fbd843f Netherlands | |
| 81062acc-e38d-4471-b7a7-3cbee73087b8 Czech Republic | |
| fb69c74a-b0cf-492a-abf2-6912ee754563 Poland | |
| 08aa8b3d-32a6-4954-8a0d-6a25bada3b11 Sweden | |
| 9028254c-e52d-4c22-8a7c-f298b0402d37 France | |
| f50c9406-fc9d-43c1-9d26-17ed462cfea3 Germany | |
| b50dea58-6a7a-42cb-b2bf-0e5dae44ce53 Germany | |
| f2deb187-5511-4343-8e7e-28f70f236b7b Hungary | |
| 55ce39ca-5f2c-4df5-9faa-48467dda629b Spain | |
| fb4044a9-678e-4f6d-b8a1-202c698c6e72 France | |
| a3053544-8868-439d-886d-44136e7b427e Belgium | |
| Environmental | |
| Environmental Information | 9AKK108467A6707 |
| Ordering | |
| Order Code US and Canada | Z1CSEJBF000A000000XX |
| EAN | 8015644747268 |
| Minimum Order Quantity | 1 piece |
| Customs Tariff Number | 85362090 |
| Dimensions | |
| Product Net Width | 210 mm |
| Product Net Height | 296 mm |
| Product Net Depth / Length | 183 mm |
| Product Net Weight | 14 kg |
| Container Information | |
| Package Level 1 Units | box 1 piece |
| Package Level 1 Width | 270 mm |
| Package Level 1 Height | 350 mm |
| Package Level 1 Depth / Length | 330 mm |
| Package Level 1 Gross Weight | 16 kg |
| Package Level 1 EAN | 8015644747268 |
| Additional Information | |
| Product Main Type | SACE Emax 2 |
| Product Name | Air Circuit Breaker |
| Product Type | Air Circuit Breaker |
| Version | F |
| CAD Dimensional Drawing | 1SDH001252R0001 |
| Technical | |
| Connecting Capacity | 1200 mm² |
| Current Type | AC |
| Electrical Durability | Ue =< 440 V 3000 cycle |
| Ue = 500 ... 690 V 6500 cycle | |
| 30 cycles per hour | |
| Mechanical Durability | 20000 cycle |
| 60 cycles per hour | |
| Number of Poles | 3P |
| Power Loss | 201 W |
| Rated Current (In) | 1600 A |
| Rated Impulse Withstand Voltage (Uimp) | acc. to IEC 60947-2 12 kV |
| Rated Insulation Voltage (Ui) | AC 1000 V |
| Rated Operational Voltage | 690 V AC |
| Rated Service Short-Circuit Breaking Capacity (Ics) | (220 V AC) 50 kA |
| (230 V AC) 50 kA | |
| (380 V AC) 50 kA | |
| (400 V AC) 50 kA | |
| (415 V AC) 50 kA | |
| (440 V AC) 50 kA | |
| (500 V AC) 42 kA | |
| (660 V AC) 42 kA | |
| (690 V AC) 42 kA | |
| Rated Service Short-Circuit Breaking Capacity, in % of Icu (Ics) | 100 % |
| Rated Short-time Withstand Current Low Voltage (Icw) | for 1 s 42 kA |
| for 3 s 24 kA | |
| Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (400 V AC) 50 kA |
| (415 V AC) 50 kA | |
| (440 V AC) 50 kA | |
| (500 V AC) 42 kA | |
| (525 V AC) 42 kA | |
| (690 V AC) 42 kA | |
| Rated Uninterrupted Current (Iu) | 1600 A |
| Rated Voltage (Ur) | 690 V |
| Recommended Screw Driver | M12 |
| Release | Ekip Touch LSIG |
| Release Type | EL |
| Short-Circuit Performance Level | C |
| Standards | IEC |
| Sub-type | E1.2 |
| Suitable for IT Networks | Yes, 690V |
| Terminal Connection Type | Front |
| Terminal Type | Bolt |
| Tightening Torque | 45 N·m |
| Certificates and Declarations | |
| ATEX Certificate | No certification needed |
| CSA Certificate | No certification needed |
| CSA Certificate (Intrinsic Safe) | No certification needed |
| Data Sheet, Technical Information | 1SDC200023D0209 |
| Declaration of Conformity - CE | 9AKK106713A5546 |
| EU Data Act Compliance Declaration | 1SDH002560A1001 |
| UL Certificate | No certification needed |
| VDE Certificate | No certification needed |
| Mechanical Drawings | 1SDH000999R0101 |
| Wiring Diagram | 1SDM000091R0001 |
| Instructions and Manuals | 1SDH000999R0002 |
| Instructions and Manuals (Part 2) | 1SDH001316R1002 |
| External Classifications and Standards | |
| ETIM 9 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
| ETIM 10 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
| IDEA Granular Category Code (IGCC) | 4926 >> Air circuit breakers |
| Object Classification Code | Q |
| UNSPSC | 39121615 |
| WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) |
| eClass | V11.1 : 27370409 |
| Feature Name | Feature Value |
|---|---|
| Rated permanent current Iu (EF001389) | 1600 A |
| Rated voltage (EF003977) | 690 V |
| Rated short-circuit breaking capacity Icu at 400 V, 50 Hz (EF007048) | 50 kA |
| Overload release current setting (EF002336) | 1600 A |
| Adjustment range short-term delayed short-circuit release (EF007129) | 16000 A |
| Adjustment range undelayed short-circuit release (EF007131) | 2400.0 A |
| Integrated earth fault protection (EF007296) | Yes |
| Type of electrical connection of main circuit (EF006819) | Bolt connection |
| Device construction (EF008240) | Built-in device fixed built-in technique |
| Suitable for DIN rail (top hat rail) mounting (EF007250) | No |
| DIN rail (top hat rail) mounting optional (EF008904) | No |
| Number of auxiliary contacts as normally closed contact (EF001377) | 0 |
| Number of auxiliary contacts as normally open contact (EF001376) | 0 |
| Number of auxiliary contacts as change-over contact (EF003531) | 4 |
| With switched-off indicator (EF007006) | Yes |
| With integrated under voltage release (EF001390) | No |
| Number of poles (EF001391) | 3 |
| Position of connection for main current circuit (EF006671) | Back |
| Type of control element (EF006976) | Push button |
| Complete device with protection unit (EF008906) | Yes |
| Motor drive integrated (EF006697) | No |
| Motor drive optional (EF007386) | Yes |
| Degree of protection (IP) (EF005474) | IP30 |