View larger
1SDA072814R1
072814
ABB
1 Pcs.
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
| ABB EcoSolutions | |
|---|---|
| ABB EcoSolutions | Yes |
| ABB Site Meeting Group Waste To Landfill Target | UL 2799 Zero Waste To Landfill Validation available |
| End Of Life Disassembling Instructions | 9AKK108468A2360 |
| Environmental Product Declaration - EPD | 9AKK108468A1900 |
| 9AKK108468A3028 | |
| Extended Product Lifetime | Lifetime Extension Services are Offered |
| Recyclability Rate of the Product acc. to EN45555 | Design for Closing Resource Loops - Standard EN45555 - 76.4 % |
| Material Compliance | |
| REACH Declaration | 9AKK108466A1425 |
| RoHS Declaration | 9AKK108466A1424 |
| RoHS Information | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
| Conflict Minerals Reporting Template (CMRT) | 9AKK108467A5658 |
| Toxic Substances Control Act - TSCA | 9AKK108467A8326 |
| SCIP | 2c3098a4-6fb0-40f5-9996-e2bc8455f38a China |
| Simplified SCIP | e2ea9bbd-eac7-49d4-85be-f9699c7aa8fc Portugal |
| aba39e41-3edf-45e4-88b0-df3f9acbd01e Denmark | |
| dae7715d-810a-42c2-953a-adccd51ff50a Belgium | |
| fe247898-62db-442b-ae90-7a1ea14752cf Germany | |
| f0317b9a-c5e0-4644-ae65-ae187d5d530e Finland | |
| 5e8a4b6b-ae14-49ed-8485-e4b4c4b56e7b France | |
| bb07c731-5156-419d-b7d3-2f9f1f35538a Germany | |
| 337c4d0a-a8c4-4fdc-be5c-9c814240d43a Germany | |
| db5a9a08-8f56-4cd7-906b-01f0ec83de27 Sweden | |
| 2eeb3a2b-54e6-4648-953a-e630e980d861 Bulgaria | |
| 25f69054-2e44-4748-86b7-4705f3644732 Estonia | |
| 1ad66df3-ec39-47de-849f-7498c0996471 Poland | |
| f8ed61b4-8ed9-4ce1-be02-673723802cd8 Spain | |
| 543e9cab-2080-424d-b0b4-25bff5f5bf23 France | |
| 2d7df915-333d-4a05-aa8a-9711e00324c2 Poland | |
| a63f501a-9fc8-47ea-bcbf-852d82ce3730 Sweden | |
| 6d9b4f35-bc21-4dcb-8545-ea2a9c93e9cc Croatia | |
| 7b31ef0e-b318-41f0-b048-a79d6ef4b504 Greece | |
| cf971e5f-710c-46f3-895c-a124f71a0982 Norway | |
| 53907b17-cc8f-491b-9d2d-22761f437677 Hungary | |
| 1a08b368-41ed-428f-a99b-5478598c7470 Belgium | |
| 89f2433b-e377-4a33-a5f8-ecd4c7584095 Germany | |
| 2740cedd-5de2-48fc-8ea8-11f71dfe0c26 Czech Republic | |
| 7f06f4bc-75ba-4254-aabf-3c967ceedbb3 Germany | |
| 7dff58fc-7061-4292-bcc1-44c5aa336a4e Poland | |
| 203ed4c2-0deb-4d55-97fd-aa428594a538 Netherlands | |
| 0e372004-07c1-4da4-9df8-f139dd9efd3b Hungary | |
| Environmental | |
| Environmental Information | 9AKK108467A6707 |
| Ordering | |
| Order Code US and Canada | ZACREHAD000A000000XX |
| EAN | 8015644766641 |
| Minimum Order Quantity | 1 piece |
| Customs Tariff Number | 85362090 |
| Dimensions | |
| Product Net Width | 348 mm |
| Product Net Height | 363.5 mm |
| Product Net Depth / Length | 271 mm |
| Product Net Weight | 20 kg |
| Container Information | |
| Package Level 1 Units | box 1 piece |
| Package Level 1 Width | 350 mm |
| Package Level 1 Height | 350 mm |
| Package Level 1 Depth / Length | 330 mm |
| Package Level 1 Gross Weight | 23 kg |
| Package Level 1 EAN | 8015644766641 |
| Additional Information | |
| Product Main Type | SACE Emax 2 |
| Product Name | Air Circuit Breaker |
| Product Type | Air Circuit Breaker |
| Version | W |
| CAD Dimensional Drawing | 1SDH001252R0065 |
| Technical | |
| Connecting Capacity | 1000 mm² |
| Current Type | AC |
| Electrical Durability | Ue =< 440 V 8000 cycle |
| Ue = 500 ... 690 V 6500 cycle | |
| 30 cycles per hour | |
| Mechanical Durability | 20000 cycle |
| 60 cycles per hour | |
| Neutral Pole Current ([%Iu]) | 100 % |
| Number of Poles | 4P |
| Power Loss | 244 W |
| Rated Current (In) | 1250 A |
| Rated Impulse Withstand Voltage (Uimp) | acc. to IEC 60947-2 12 kV |
| Rated Insulation Voltage (Ui) | AC 1000 V |
| Rated Operational Voltage | 690 V AC |
| Rated Service Short-Circuit Breaking Capacity (Ics) | (220 V AC) 50 kA |
| (230 V AC) 50 kA | |
| (380 V AC) 50 kA | |
| (400 V AC) 50 kA | |
| (415 V AC) 50 kA | |
| (440 V AC) 50 kA | |
| (500 V AC) 42 kA | |
| (660 V AC) 42 kA | |
| (690 V AC) 42 kA | |
| Rated Service Short-Circuit Breaking Capacity, in % of Icu (Ics) | 100 % |
| Rated Short-time Withstand Current Low Voltage (Icw) | for 1 s 42 kA |
| for 3 s 24 kA | |
| Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (400 V AC) 50 kA |
| (415 V AC) 50 kA | |
| (440 V AC) 50 kA | |
| (500 V AC) 42 kA | |
| (525 V AC) 42 kA | |
| (690 V AC) 42 kA | |
| Rated Uninterrupted Current (Iu) | 1250 A |
| Rated Voltage (Ur) | 690 V |
| Recommended Screw Driver | M12 |
| Release | Ekip Touch LI |
| Release Type | EL |
| Short-Circuit Performance Level | C |
| Standards | IEC |
| Sub-type | E1.2 |
| Suitable for IT Networks | Yes, 690V |
| Certificates and Declarations | |
| ATEX Certificate | No certification needed |
| CSA Certificate | No certification needed |
| CSA Certificate (Intrinsic Safe) | No certification needed |
| Data Sheet, Technical Information | 1SDC200023D0209 |
| Declaration of Conformity - CE | 9AKK106713A5546 |
| EU Data Act Compliance Declaration | 1SDH002560A1001 |
| UL Certificate | No certification needed |
| VDE Certificate | No certification needed |
| Mechanical Drawings | 1SDH000999R0103 |
| Wiring Diagram | 1SDM000091R0001 |
| Instructions and Manuals | 1SDH000999R0002 |
| Instructions and Manuals (Part 2) | 1SDH001316R1002 |
| External Classifications and Standards | |
| ETIM 9 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
| ETIM 10 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
| IDEA Granular Category Code (IGCC) | 4926 >> Air circuit breakers |
| Object Classification Code | Q |
| UNSPSC | 39121615 |
| WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) |
| eClass | V11.1 : 27370409 |